Troubleshooting
Does the servo motor fault follow the drive or the branch
Short answer
Swap one boundary at a time between two compatible drive channels; if the fault stays on the same physical drive channel, replace that drive. If the fault moves with the motor power and feedback cables, the motor, cable, connector or mechanical load is at fault. Read the drive's data tag before ordering any replacement.

On this page
The fault's travel across a swap decides the culprit. Move the complete motor-and-cable branch from the problem axis to a known-good drive channel: if the fault travels with that branch, the motor, its power or feedback cable, a connector or the mechanical load is at fault, and the drive is fine. If the fault stays on the same physical drive channel after you connect a known-good branch, replace that drive. One moved boundary, and the display gives you the answer.
Read the fault record before you touch a connector #
Swap tests are only worth running after the free checks are done. Read the drive's fault indication, the controller's diagnostic screen and any retained fault history before cycling power, because a reset can erase the trip value the drive recorded: the motor current, power-stage temperature, position error or feedback state that actually crossed its limit.
Note when the fault occurs. At power-up, at enable, at standstill, during acceleration, or only after a repeatable running time. A fault that appears only after minutes of running points to heat accumulating in the motor, the cable or the drive power stage. A fault at the instant of enable points to wiring, phasing or feedback, before heat has any role. If the trip comes in the middle of a move rather than at enable or after a soak, the pattern and its causes are laid out in Troubleshooting a Servo Axis That Faults Mid Move (article:troubleshooting-a-servo-axis-that-faults-mid-move).
The rule that decides #
A swapped connection is only a test when the moved boundary is documented. An axis is a chain: a controller assignment, a drive channel, a motor power cable, a feedback cable, a motor, and its mechanical load. Move several links at once and the axis label on the screen changes without telling you which hardware failed.
Commit to this rule, and act on it directly:
| Test result | The fault is in | Confirming check |
|---|---|---|
| Fault stays on the same physical drive channel when a known-good branch is connected | That drive channel | Repeat once on a second channel; two stays confirm it |
| Fault moves with the motor branch to a known-good drive | Motor, power cable, feedback cable, connector, or the load | Winding resistance, insulation, connector and coupling inspection |
| Fault appears on both channels after the swap | Something shared: phasing, grounding, supply or command wiring | Shared-wiring checks, not part replacement |
If the record of which side moved is unclear — both cables moved, or only the displayed axis name moved instead of hardware — the swap proved nothing. Redo it with one boundary and a written connection list.
Swap one boundary at a time #
- Record the exact alarm text, the drive indication, the motion phase at the trip, the running time, and whether the fault resets. Preserve retained diagnostics before removing power.
- Label each physical drive, motor, power cable and feedback cable with tape names independent of the screen, for example Drive 1, Drive 2, Motor Z, Motor Test. Photograph the original connector positions. Controller labels follow configuration, not hardware.
- Remove power, lock out the supply, and wait for the drive's documented bus-discharge time before touching any connector. Servo drives hold lethal voltage after the supply is off.
- Inspect the problem axis's power and feedback connectors first: bent or recessed pins, contamination, heat discoloration, loose contacts, damaged shielding, and cable damage near flex points. This costs nothing and finds the fault often enough to always come first.
- Confirm from labels and drawings that the two drive channels are compatible: same supply voltage, adequate current rating for the motor, same feedback interface. A three-board machine does not prove three identical channels.
- Move the complete suspect motor-and-cable branch — power and feedback together — to the known-good drive. Keep a written matrix of every connection.
- Run only the minimum controlled motion needed to reproduce the fault, then run the reverse test: connect the known-good branch to the suspect drive. Two complementary results are far stronger than one changed message.
Two checks that confirm a branch fault #
A servo drive user manual documents a clean discriminator for this: disconnect the motor power cable at the drive, set the drive's current limit to zero, and enable it. If the fault clears, the problem is in the wiring or inside the motor. If the same fault appears with no motor connected at all, the drive's own output stage is the suspect, and the branch test becomes unnecessary.
With power locked out, a resistance check on the branch narrows the branch fault further. Take the winding resistance from your motor's datasheet; the following numbers are an illustrative example. If the datasheet lists 1.8 Ω per winding phase, a wye-connected motor reads twice that between any two phase leads, because the current passes through two windings in series: 1.8 Ω + 1.8 Ω = 3.6 Ω. Read U-V, V-W and W-U at the drive end of the cable with the cable still connected. All three pairs reading close to 3.6 Ω, balanced within a few tenths of an ohm, says the windings and the power conductors are intact. A reading near 0 Ω on one pair means a shorted winding or shorted cable; an open reading means a broken winding or a broken conductor. Then check each phase lead to the motor frame: a healthy motor reads open there on an ohmmeter, and any reading means insulation breakdown. For the feedback side, a wiring or phasing mismatch between drive and motor typically trips at the first enabled move, and the phasing check comes before any replacement, as in Servo Drive Shows COM Fault Then Overload: Check U V W Phasing First (article:servo-drive-shows-com-fault-then-overload-check-u-v-w-phasing-first).
Identify the drive before ordering #
The machine designation is not the drive part number, and an unreadable label is not a dead end. Photograph every face of the drive after isolation, then work through the machine electrical drawings, the parts list, purchase records and any stored drive configuration until every printed identifier is on paper, exactly as printed, including prefixes, suffixes and option codes.
The replacement must match the supply voltage, the continuous and peak current the axis demands, the motor's feedback interface and the command interface. A unit that bolts into the same cutout can still be electrically wrong for the motor or the controller, and the criteria that make a drive and motor a working pair are set out in What Decides a Servo Drive and Motor Match From the Start (article:what-decides-a-servo-drive-and-motor-match-from-the-start). If no identifier can be recovered, assemble photographs of every drive face, the full motor data tag, the wiring drawings and the connection matrix, and get written confirmation of the exact replacement and any setup changes before applying power.
The decision, case by case #
- Fault stays on the physical drive channel with a known-good branch connected, twice: replace that drive.
- Fault moves with the complete motor branch to a known-good drive: the drive is good. Find the branch fault with the zero-current enable test, then winding resistance, phase-to-frame insulation, connector inspection and the mechanical load, in that order, cheapest first.
- Fault appears on both channels after the swap: stop swapping parts and check what the two sides share — phase order, grounding, the supply and the command wiring.
- No clean record of what moved: the swap proved nothing. Redo it with one documented boundary before any money is spent.
Questions asked
Should the power cable and the feedback cable move together in the swap test?
Yes, for the first test. Moving both makes the boundary one thing: the complete motor branch. If the fault moves with the branch, split the test from there: move only the power cable, then repeat with only the feedback cable. A fault that follows only the power cable points to the power conductors or the motor windings; one that follows only the feedback cable points to the feedback line or the encoder.
The fault appeared on the other motor after the swap. Is that proof the drive is bad?
No. It depends on which side moved. If the complete motor branch moved to a known-good drive and the fault moved with it, the branch is at fault, not the drive. A migrated fault only proves something when a written connection record shows exactly which side was swapped. Photograph or list the before and after connections so the result can be interpreted.
The drive label is unreadable. How do I identify the correct replacement?
Work from the machine's electrical drawings, parts list, purchase records or a stored drive configuration, and photograph every face of the drive before removal. Record every printed code exactly, including prefixes, suffixes and option codes.
Can I test a suspect drive away from the machine?
Yes, when the machine has no second identical channel or cannot stop. You need a supply at the drive's rated input voltage, a motor whose feedback type and current rating the drive supports, and a valid configuration. Reproduce the fault with the motor unloaded first; a fault that appears at enable with no load attached already confirms the drive, and no loaded test is needed.