Explainer
Hydraulic clinch control: pump, cylinder and high-pressure solenoid
Short answer
A hydraulic clinch unit runs reliably when each phase transition - advance, high-pressure, retract, ready - is gated by measured feedback, never by a timer alone, and every physical output is written by exactly one routine. The high-pressure solenoid command must be distinguished on the HMI from achieved pressure.

On this page
A handheld hydraulic clinch unit is controlled reliably when every phase transition - advance, high-pressure, retract, ready - is gated by measured feedback such as a pressure switch or position sensor, never by a timer alone, and every physical output is written by exactly one routine in the program. The high-pressure solenoid command and achieved pressure are two different things, and the HMI has to show them separately. This article sets out the sequence structure, the feedback gates, one worked sizing example, and where a software permissive is ordinary sequencing versus a validated safety function.
The four phases and their gates #
Split the cycle into four phases, each with one entry condition, one exit condition, and one timeout:
- Ready: entry is the retracted-position feedback present and no faults; exit is a valid cycle request from the operator controls.
- Advance: entry is the cycle request; exit is the clinch position or die-closed feedback (or the pressure beginning to rise, depending on the tool); timeout is a fault.
- High-pressure: entry is the advance exit feedback; exit is the pressure switch input; timeout is a fault.
- Retract: entry is the pressure-switch input or the high-pressure timeout fault acknowledged; exit is the retracted-position feedback again.
A timer measures elapsed time only. Use it as a watchdog on each phase, sized from the machine's own measured behavior, and never as the exit condition when the clinch result depends on force or position. A phase that ends on time alone runs to completion even when the tool is off the sheet, the die is worn, or the pump cannot build pressure.
Worked example: pressure, flow and the watchdog #
Take a handheld clincher with a 32 mm bore cylinder making a joint requiring 25 kN of force, with a 50 mm advance stroke and a 0.75 L/min pump:
- Bore area: A = π/4 × (0.032 m)² = 8.04 × 10⁻⁴ m² (8.04 cm²).
- Pressure for 25 kN: p = 25000 N ÷ 8.04 × 10⁻⁴ m² = 31.1 MPa, about 310 bar. Set the pressure switch below that - for example at 290 bar - so the switch trips with margin and confirms the joint, while the high-pressure watchdog timer is the fault path.
- Advance volume: 8.04 cm² × 5 cm = 40.2 cm³ per cycle.
- Advance time at 0.75 L/min: 40.2 cm³ ÷ 750 cm³/min = 0.054 min, about 3.2 s.
These are calculated example figures for those inputs, not measurements of any tool. The decision they produce: set the advance watchdog at roughly twice the calculated 3.2 s (call it 6 s to start, verified against a real cycle), set the pressure switch at 290 bar for this example geometry, and gate the high-pressure phase exit on that switch input. If your cylinder bore, force requirement or pump flow differ, the pressure and times move with them - redo the two divisions above with your datasheet values before setting anything.
For a real tool, take the switch rating and the pump displacement from the datasheets of the exact components fitted - no figure here substitutes for them.
Pump, valves and the de-energized state #
Before writing logic, map every command to its hydraulic action from the schematic: how the pump starts, which valve states give advance and retract, and what energizing the high-pressure solenoid actually opens. Record each valve's de-energized position and the cylinder behavior that follows, because the idle and fault states are built on it. A pump-running bit or an energized coil does not prove cylinder motion or developed pressure; only the measured inputs do.
Where the pump start comes from a pair of operator or interlock signals, the start/stop memory belongs in the conditions routine, and the pattern in the article on latching two level inputs for pump start and stop control applies directly. If a pump command appears to be issued but nothing runs, the troubleshooting in why a hydraulic pump command should follow the cycle, not the valves, and the pressure-switch article on a switch that will not trip below its setpoint, cover the two failure points this sequence depends on most: the command path and the feedback device.
One owner per output #
Organize the program as inputs, conditions and interlocks, cylinder control, timers and counters, faults, then outputs, called in that order. Multiple writes to one physical output make the final state depend on scan order, which is not a design. Assign each output - pump contactor, advance solenoid, retract solenoid, high-pressure solenoid - to exactly one output routine, called last, after permissives and fault inhibition have been applied. Use cross-reference search to confirm no other routine writes the same coil. This gives conflicts one place to be rejected.
Anti-tie-down: sequencing versus safety #
Two conditions belong in the interlock routine as ordinary sequencing: a cycle request is accepted only when both operator controls are released, and both must be released and re-pressed before the next cycle. That prevents a button held or tied down from repeat-cycling the tool.
Whether two-hand control is a safety function is set by your risk assessment, not by this article. When it is, ISO 13851 is the applicable standard: it defines the design principles for two-hand control devices and three types with increasing requirements, and a required safety function belongs in hardware with the appropriate safety architecture rather than in a software bit in the sequence. One safety note to carry: loss of the safety permission must produce the required machine response independently of the normal sequence logic - verify that during commissioning with the sequence deliberately interrupted.
Faults and the HMI #
Give each phase a fault when its exit feedback does not arrive before its timeout, and record which gate failed: advance commanded without position feedback is a different fault from high-pressure commanded without the pressure switch tripping. On the HMI, show the solenoid command and the achieved pressure as separate indications - a commanded lamp driven by the output image next to a live indicator driven by the pressure switch input. When an operator reports that a command shown on the screen never reaches the machine, the HMI-to-output tracing method in the article on tracing an HMI command that never reaches the PLC output applies.
The decision #
Build the sequence on the four gated phases, size each watchdog from the machine's own measured cycle time (in the example, about 3.2 s of advance becomes a 6 s starting watchdog), gate the high-pressure exit on the pressure switch rather than the solenoid coil, keep every output in one routine, and treat anti-tie-down as sequencing unless the risk assessment makes it a validated safety function under ISO 13851. If any phase cannot be gated on a real measurement - no position sensor, no pressure switch - fit the sensor; a timer in its place is the one design choice that turns a worn die or an empty reservoir into an undetected bad joint.
Questions asked
Why does the high-pressure solenoid command not prove the joint was made?
The command only energizes a coil; the joint is proven when the measured pressure reaches the switch setpoint within the phase. If the tool slips off the sheets, a die wears, or the pump cannot build pressure, the solenoid is still commanded and the cycle still appears to run. Gate the phase exit on the pressure switch input, and raise a fault with a diagnostic when that input does not arrive.
How long should the high-pressure dwell timer be set?
Take it from the machine, not from a handbook: measure the elapsed time from solenoid energize to pressure-switch trip on a good joint, and set the timer as a fault watchdog at roughly twice that measured value. In the worked example the pump reaches 310 bar in about 1 second, so a 2 second watchdog is a starting point to verify on the actual tool.
Is anti-tie-down a safety function?
Only if your risk assessment says so. When two-hand control serves a safety purpose, ISO 13851 defines three types with increasing requirements, and the function belongs in validated safety hardware, not a PLC bit. Where it only stops an operator from tying down a button to keep the cycle repeating, the two released-and-repressed conditions in the interlock routine are ordinary sequencing.
What feedback proves the cylinder is back at start?
A switch or sensor at the fully retracted position - a reed switch on the cylinder, a proximity sensor on the tool, or a position signal. Ready is declared from that measured input after the retract command ends, not from the retract output having been on for a set time. Without position feedback the unit can be declared ready against a partially retracted cylinder, and the next advance starts off-center.
Can the pump run continuously instead of per cycle?
It can, but on a handheld tool a per-cycle pump command cuts heat input and noise, and it makes no-pressure faults visible at the phase where they matter. If the tool holds against a load between phases, you need a check valve or accumulator in the hydraulic circuit so the cylinder does not sag while the pump is off.