Identifying Wiring on an Obsolete Brushless Servo Motor
Short answer
Never energize an undocumented obsolete brushless servo motor and never guess connector pins. Photograph the full nameplate, record which joint the motor came from, map winding and feedback conductors only with everything isolated, and match vendor documentation to the complete catalog and spec markings before connecting a drive. A nameplate alone cannot prove a pinout or size a drive.

On this page
An obsolete brushless servo motor with no wiring drawing is not a wiring problem you solve by experiment: you solve it by identification. Photograph the complete nameplate, record which joint the motor came from, map winding versus feedback conductors only with every power source and drive disconnected, and then match the manufacturer's documentation to the full catalog and spec markings. Do not energize the motor and do not put power on encoder conductors until that documentation is in hand. The nameplate itself, however complete it looks, cannot size a drive or prove a pinout, and the worked example below shows why.
Read the nameplate as a lead, not as a spec sheet #
The nameplate gives you the strings you need to search for documentation, and a set of ratings that mean nothing until a datasheet defines them. Take the reported example of a late-1990s brushless AC servo motor salvaged from a robot arm, carrying these markings:
| Marking | Reported value | What it actually establishes |
|---|---|---|
| Catalog marking | a complete string such as N067/0070 20612E D121 02A | The search key; use the whole string, never a fragment |
| Spec marking | first character ambiguous between G and 6, so G1897003 or 61897003 | Unresolved; photograph the physical nameplate and keep both readings until resolved |
| Torque field | 1.65 Nm | Ambiguous wording: stall torque or torque constant, not confirmed |
| Continuous stall current | 4.8 A RMS | A motor rating, not a drive or cable rating |
| Speed | 6000 rpm | A motor rating |
| Voltage | 200, no unit | Undefined: not proven DC bus, winding or supply volts |
| Peak current | 19 A, no duration | Cannot be converted to RMS or continuous without duration, waveform and duty |
Every row after the catalog string is a reported marking, not a verified rating. The voltage value in particular is the classic trap: 200 what, referred to where? Only the manufacturer's documentation for that motor family says. Treat the ambiguity in the spec marking the same way: order or request documentation against the resolved nameplate reading, and say which reading you used.
Record where the motor came from before you touch a wire #
On a multi-axis machine, joint identity can distinguish otherwise identical motors and feedback assemblies. Before disconnecting anything:
- Photograph the motor, its connectors, its cable labels and the machine location from two angles.
- Write down which axis or joint the motor drives, and the machine's serial number and build date.
- Photograph the nameplate in full, including every small line, and zoom-check the ambiguous characters.
- Label each connector and each cable at both ends before removal, with tape and a marker, not memory.
Two motors from similar machines of the same year are not automatically wired the same way. If a joint used a gearbox or a different feedback assembly, the connector population alone may differ. The identification data from this section is what makes a documentation request answerable, and the same habit of recording origin before matching hardware is what salvaged robot servos need before any drive selection at all, as covered in identifying salvage robot servo motors before drive selection.
Map the conductors with everything isolated #
One safety note before any measurement: lock out and verify zero energy on the machine, disconnect the motor from every drive and supply, and discharge any drive bus capacitors per the drive manufacturer's procedure before you put a meter lead on a conductor.
With the motor isolated, use a digital multimeter for three measurements, in this order:
- Winding continuity and resistance. Measure resistance between every pair of heavier power conductors. Three phases give three pairings; three similar readings group those conductors as the winding. Readings involving a feedback conductor that are wildly different, or open, separate the feedback bundle from the power conductors.
- Insulation to ground. Measure from each power conductor to the motor frame and to the protective earth conductor. A low reading here is a winding-to-frame fault; the motor stops being a reuse candidate until that is investigated.
- Feedback bundle separation. Identify the lighter-gauge conductors or the separate multi-pin connector as the feedback group, and leave its individual pin functions unknown. Resistance can tell you which wires are not winding wires; it cannot tell you which wire is encoder power, which is a signal, or what supply the encoder expects.
Worked example: what the winding readings do and do not prove #
Say the isolated motor has five heavy conductors and one multi-pin feedback connector, and your pairings read 2.4 ohm, 2.4 ohm and 2.4 ohm between three of them, with the other two showing tens of ohms to the first three and no continuity to ground. That is a calculated-example pattern, not a measured result: three equal phase resistances of 2.4 ohm identify a three-phase winding group, and the other two conductors most likely belong to a thermal switch or brake, not to phases.
What those readings prove: which conductors carry phase current, and that the winding is not shorted to the frame. What they do not prove: the phase order (U, V, W assignment), the commutation alignment between winding and feedback, the encoder's supply voltage and signal format, or a single pin function in that feedback connector. Getting any of those wrong on power-up can destroy the encoder instantly. The measurements give you a cable map; a verified drawing or the manufacturer's documented identification procedure gives you a pinout.
Match documentation to the full markings, then verify before commissioning #
With the cable map in hand, go back to the manufacturer or its distributor for documentation matched to the complete catalog string and the resolved spec number. Discontinued motor families are often covered by archived specification and compatibility guides published by the drive manufacturer; search with the whole string, and when the spec character is ambiguous, request against both candidate numbers and let the nameplate photograph decide. Do not accept a wiring diagram that matches only part of the marking: brushless families of the same frame size frequently share windings but differ in encoder type, and a wrong feedback drawing is worse than none.
Before the motor ever sees a drive, verify each item against the documentation:
- Motor identifier and originating joint match the drawing.
- Power conductor grouping matches the drawing's phase assignment.
- Protective earth path is continuous from frame to plug.
- Feedback type, supply requirement and signal assignment match, pin by pin.
- Phase-to-feedback commutation alignment is documented, not assumed.
Only then configure the drive, and configure it from the datasheet's verified motor data, not from the nameplate fragments. If the original drive family is gone, the same verification logic governs matching a new drive to an old motor's feedback, which is exactly the subject of selecting a replacement servo drive for resolver motors. And if the reuse does not survive verification, replacement is the fallback: a new brushless servo motor with documented wiring and a matching drive ends the risk that a salvaged winding or a guessed encoder pin takes out the drive on first power-up.
The decision #
Energize nothing until the catalog string is complete, the spec character is resolved, the joint of origin is recorded and vendor documentation matches all of it. Your multimeter work decides only which conductors are phases, which are not, and whether the winding is sound; the documentation decides every pin function, every commutation alignment and every drive setting. If documentation cannot be matched to the full markings, do not reuse the motor: the 19 A peak marking with no duration, the unitless 200 volts and the unresolved spec number are not a foundation for a drive, and a wrong first power-up costs the encoder, possibly the drive, and always the time you thought you were saving.
Questions asked
The nameplate says Voltage: 200 with no unit. What does that tell me about the drive I need?
Nothing by itself. A bare 200 on a brushless servo nameplate could mean DC bus volts, winding RMS volts or a maximum supply figure, and the nameplate does not say which. Do not size a drive from it. Find the manufacturer's catalog page or datasheet for the exact catalog and spec marking; that document defines what the voltage field means for that motor family.
Can I use the peak current marking, for example 19 A, to set the drive's continuous current?
No. A peak current figure without a duration, a waveform and a repetition period tells you nothing about what the winding tolerates continuously, and you must not convert it to an RMS or continuous value by assumption. Set drive current limits from the continuous stall current and the drive's own configuration procedure for that motor, or leave the motor unmatched until documentation confirms the numbers.
Is a torque constant of 1.65 Nm per amp hidden in the nameplate line Torq Const. Stall: 1.65 Nm?
Not proven. The line may state stall torque rather than torque per ampere, and the wording is too ambiguous to build on. If 1.65 Nm were stall torque, dividing it by the 4.8 A RMS continuous stall current gives about 0.34 Nm/A, which is a plausible torque constant for a small brushless motor, but that division is an illustration, not a documented rating. Take the torque constant from the manufacturer's datasheet for the exact part.
Can resistance readings between wires give me the connector pinout?
They give you a cable map, not a pinout. Resistance and continuity group conductors into likely winding phases and separate the feedback bundle from the power conductors, but they cannot prove phase order, commutation alignment, encoder supply requirements or signal format. A verified wiring drawing or the manufacturer's documented identification procedure is still required before connecting a drive.