Incremental Encoder Missing Counts After a Cut Cycle
Short answer
When an incremental cutter encoder reads a nonzero count after returning to its home position, the first suspect is mechanical slip between the encoder shaft and the cutter, not lost pulses — above all when a replacement encoder changed nothing. Read the count stationary at a repeatable physical mark, convert the leftover counts into shaft angle, and watch a scribed coupling line: the decision follows from those three checks.

On this page
- Is the encoder actually missing counts?
- Why does an unchanged fault after an encoder swap point at the coupling?
- How do you turn the leftover count into real shaft angle?
- Which checks should you run first, cheapest to dearest?
- When do wiring and counter configuration become the suspects?
- What is the fixed sequence from home to home?
- What decision closes each case?
- Questions asked
A cutter encoder that will not read zero when the cutter is back at its home mark is usually not losing pulses at all — it is losing motion somewhere between its shaft and the cutter, and the replacement encoder already proved that by changing nothing. The decision comes from three checks made with the machine stopped: read the PLC count at a repeatable physical mark, convert the leftover count into shaft angle, and inspect a scribed line across the coupling. The sequence below gives the steps, the arithmetic and the decision for each outcome.
Is the encoder actually missing counts? #
Most likely not: when a replacement encoder reproduces the same error, the pulses are arriving intact and the missing motion sits between the encoder shaft and the cutter, so the physical home moves while the counting stays honest. A number watched on the HMI during motion is not evidence either way — screen refresh and communication delays can make a valid count look late, frozen or discontinuous.
The only observation that counts is made with everything stopped: park the cutter at a physical mark that repeats, such as a hard stop or a scribed line on the frame, and read the PLC counter value directly. If the cutter is on the same mark it was zeroed at and the count is not zero, you have a real position-system error — but not yet a counting error. Cut pieces that vary in length confirm a machine-level error; they do not identify the encoder as the cause.
Why does an unchanged fault after an encoder swap point at the coupling? #
Because the swap already ran the most expensive test for you: a new encoder with the same fault removes the encoder from the suspect list and leaves everything it shared with the old one — coupling, shaft, mounting, cable, counter configuration and zeroing logic. Relative movement at any of those points changes the indicated position while every pulse is counted correctly.
The confirming check is a scribe mark. Lock out the cutter drive before putting a hand near it, then draw a fine line across the coupling hub and the encoder shaft, and a second line across the coupling and the driven shaft. Run one cut with the guards back in place, stop, lock out again, and inspect the marks under good light. Any offset between the lines is measured slip, and its direction tells you which way the error accumulates.
How do you turn the leftover count into real shaft angle? #
Divide the leftover count by the counts the counter records in one revolution and multiply by 360 degrees, taking the counts-per-revolution from the configured decoding rather than from the pulse rating alone. The decoding mode — one edge of one channel, both edges of one channel, or both edges of both channels — multiplies the pulse rating by 1, 2 or 4, and it lives in the counter configuration of the input path.
Worked example, calculated for the numbers below and not a measurement. Assume a 2048 PPR quadrature encoder and a counter decoding both edges of both channels, so counts per revolution = 2048 × 4 = 8192. You park the cutter on the home mark and the stationary PLC count reads 410. The shaft angle is:
410 × 360° / 8192 = 147,600 / 8192 = 18.0 degrees
If the counter decodes only one edge of one channel, the same leftover count is 410 × 360° / 2048 = 72.1 degrees — which is why the decoding mode must be read before anyone converts counts to motion.
Either angle is visible at the coupling. If the scribe lines still align, the shaft genuinely sits that far from home and the mechanism's stop, cam or home switch has moved. If the lines have slipped, the coupling itself is the fault and the encoder is innocent.
Which checks should you run first, cheapest to dearest? #
Start with the free checks — scribe the coupling, run one cycle, measure the cut piece, read the stationary PLC count — in that order, because each step can end the diagnosis before the next one starts. Every symptom below has a confirming check; do not assign a cause from the symptom alone.
| Observation | What it means | Confirming check |
|---|---|---|
| Scribe marks offset after one cut | Slip in the coupling or on the shaft | Check set screws, key and bore fit; replace the coupling and rerun |
| Marks aligned, same home mark, count still nonzero | Counting, configuration or reset-logic problem | Read the stationary PLC value and review the zero and reset path |
| The home mark itself has moved | Mechanical stop, cam or switch shifted | Re-establish the physical home and re-zero; the encoder is correct |
| Cut pieces vary while cutter home repeats | Feed-side error: length encoder path, roller slip, strip tension | Inspect the measuring wheel or roller and the strip tension, not the cutter encoder |
| PLC value correct while the HMI jumps during motion | Display or communication latency in the observation only | Compare PLC and HMI values with the machine stopped |
When do wiring and counter configuration become the suspects? #
Only when the cutter returns to the exact physical home, the coupling marks still line up and the stationary count is still wrong: then the mechanics are cleared and the fault is in the signal path, the counter setup or the reset logic. From that point the work is electrical and logical, and it follows the same order every time.
- Verify the encoder cable is routed away from the cutter's motor and valve wiring, and that the shield is terminated the way the input module's documentation requires.
- Confirm the configured decoding mode matches the signals actually connected, since a channel wired but not decoded halves the count silently; matching an incremental encoder to a PLC high speed counter walks through that step.
- Review the zeroing and reset logic in the program, because a reset that lands one scan late after a cut leaves a small nonzero count that looks exactly like lost pulses. The wider counting chain is covered in counting encoder pulses on a PLC without losing position.
What is the fixed sequence from home to home? #
Run the same seven steps every time, reading every value with the machine stopped: a diagnosis built on moving numbers cannot be repeated, and a check you cannot repeat is not evidence.
- Lock out the cutter drive and scribe alignment lines across the coupling hub, the encoder shaft and the driven shaft.
- Jog the cutter onto its physical home mark and stop; record the PLC count and the HMI value as a pair.
- Apply the existing zero operation and confirm the PLC count reads zero while the cutter stays stationary.
- Restore the guards, run one cut, return to the same home mark and stop.
- Read the stationary PLC count and convert it to shaft angle using the configured decoding factor.
- Measure the cut piece and record the length.
- Lock out and inspect the scribe marks for relative movement; record direction and amount.
What decision closes each case? #
Four outcomes cover every run of the sequence, and each names the part you touch next: the coupling, the home stop, the signal and reset path, or the feed side of the machine.
- Marks offset: slip is confirmed between the encoder and the cutter. Repair the coupling — set screws, key, bore fit — and rerun the sequence. Do not change PLC logic; no counting fault has been shown.
- Marks aligned, same home mark, repeatable nonzero count in one direction: the error is electrical or logical. Scope both channels at the input for clean, equal edges, correct the routing and shield termination, then review the reset logic.
- Home mark has moved: re-establish the mechanical home, re-zero, and rerun. The encoder and counter were right all along.
- Cutter home repeats but cut pieces vary: move the diagnosis to the rod-length encoder path — measuring wheel or roller slip, wheel wear, strip tension. The cutter encoder is not part of that fault.
The case is closed only when the cutter returns to the same physical mark and the stationary count reads zero after a cut — everything short of that is a hypothesis with a next check assigned.
Questions asked
Can electrical noise drop counts only when the cutter fires?
Yes. The cutter's motor or valve current draws a burst at the same moment every cycle, and that burst can couple into the signal cable and corrupt an edge. If the leftover count appears on cutting cycles but not on a dry cycle without cutting, move the encoder cable away from the power wiring, verify the shield termination the input module documentation requires, and rerun the sequence.
Does the cutter encoder control the cut length?
No, not in this arrangement. The rod-length encoder measures the feed and the cutter encoder only positions the cutter at home. If cut pieces vary while the cutter returns to the same physical home every time, the error is in the length-measuring path — roller or measuring-wheel slip, wheel wear or strip tension — and the cutter encoder is not part of the fault.
How many cut pieces should I measure to confirm a length error?
As a rule of thumb, measure at least ten consecutive pieces from one setup with a caliper or tape suited to the print tolerance, and record them. A steady drift in one direction points to a setup or tension problem; scatter around the mean points to intermittent slip. Either way the error is machine-level and the mechanical path is where you go next.
What is the difference between the PPR rating and the counts the PLC sees?
PPR is the pulses one channel produces in a revolution. Decoding one edge of one channel gives that many counts per revolution; decoding both edges of one channel doubles it; decoding both edges of both channels quadruples it. For a 2048 PPR encoder the counter therefore records 2048, 4096 or 8192 counts per revolution depending on the configured mode. Read that mode before converting a leftover count into angle.