Servo External Scale Error Alarm: Fix the Feedback Path
Short answer
An external scale error alarm fires when the drive's scale-error input sits OFF while scale-error monitoring is enabled and the axis runs full-closed or hybrid control on an external encoder. Check the cable and connectors, then the scale mounting, then the scale-type and monitoring parameters, in that order. Do not silence the alarm by disabling monitoring; fix the feedback path and restore the setting before the axis runs again.

On this page
An external scale error alarm is the drive reporting that its scale-error input sits OFF while scale-error monitoring is enabled and the axis runs full-closed or hybrid control on an external encoder — the drive family that documents the fault as alarm 28 lists exactly those three conditions. In the field the cause is almost always in the external feedback path: a connector, a cable, the scale mounting or a scale-type parameter set for the wrong device. The drive itself is the last suspect, not the first. Work the path from the cheapest test to the most invasive, confirm each finding before moving on, and keep the watchdog enabled — the fix belongs in the path, never in the tolerance.
What the drive is actually reporting #
In full-closed control the position loop closes on the external scale, and the motor encoder keeps only commutation and speed. Hybrid control blends the two — commonly machine position from the external device with speed from the motor encoder — and the drive manual for the configured mode states the split exactly. Either way, the external device is the machine's position authority: the same idea as using a servo motor encoder as external machine feedback, taken one step further.
The alarm means all three of these documented conditions held at once:
| Documented condition | What it tells you |
|---|---|
| Scale-error monitoring enabled — on the drive family that names the switch Pr76, scale error invalidation, a setting of 0 keeps it active | The watchdog is on; the alarm is doing its job. |
| Full-closed or hybrid control with an external encoder | Only these modes watch the external scale, so the live position feedback really is the scale. |
| Scale error input OFF | The health line from the scale or its interface is not at the state the drive manual requires. |
Read the third row literally. The drive is not saying what failed, only that a line is wrong, and a broken wire, an unseated connector, a contaminated readhead and a dead scale board all arrive as the same symptom. That is why the order of the checks below matters more than the wording of the alarm.
Check the feedback path, cheapest test first #
Run these in order. Each one ends with the result that confirms or clears it.
- Reseat and inspect every connector in the path. Isolate and lock off the drive per your site's lockout procedure before opening any connector, because the DC bus stays charged after the axis stops. Look for bent pins, shells that never latched, backed-off couplings and corrosion. Jog the axis through full travel afterward: an alarm that stays gone confirms a seating fault was the whole problem; an alarm that returns on motion sends you to the next check.
- Follow the cable end to end. Inspect the jacket for cuts, crush points and drag wear, and confirm the shield lands the way the drive manual shows. Reroute any section that runs beside motor power leads or high-frequency wiring — the same wiring-first discipline that clears a servo encoder connection error alarm. Confirm by flexing one cable segment at a time while watching the alarm history: the fault follows the guilty segment, not the scale.
- Check scale mounting and contamination. Set readhead gap and alignment to the figures in the scale's manual and look for chip packs or an oil film on the scale face. Sweep the axis slowly through all travel by jog: an alarm pinned to one travel band confirms a mechanical fault at that band, while random timing points back to the electrical checks.
- If the external encoder is rotary, check the coupling that turns it. Verify set screws and clamp tightness first — a slipping or worn coupling changes counts without tripping the scale's own health line. A coupling worn past adjustment gets replaced with a correctly matched flexible shaft coupling, and nothing else in the path changes.
- Match the scale-type parameters to the installed scale. Scale type, resolution or signal period and input signal format come from the datasheet of the exact scale fitted, not from a similar one. A feedback device replaced or reconfigured and now wrong by a fixed ratio shows up as travel error, the same pattern as a servo travel error after swapping resolver and encoder; the worked example below puts numbers on it.
- Scope the signals, then substitute the scale. With safe test access and the scale manual's limits in hand, check the counting channels and the health line at the drive end. Dropouts synchronized to travel confirm the mechanical checks; random glitches near running motors confirm noise or shielding. If a compatible known-good scale is available, substitute it: an alarm that clears convicts the original scale, and an alarm that stays sends you into the drive's own diagnostics with the input stage as the last suspect.
Scale parameters: match the datasheet and keep the watchdog on #
Two settings decide this alarm, and only one of them is ever legitimate to touch. The first is the scale-type set from the section above: enter it exactly and leave it alone.
The second is the monitoring switch itself, scale error invalidation, Pr76 on the family that uses that name, where 0 keeps monitoring active. Leave it at monitoring-enabled. Setting it away from 0 does not fix anything — it turns the watchdog off, and the drive then closes position on counts it cannot vouch for, so a short, lost or corrupted count becomes silent position error instead of a controlled stop. The one legitimate use of disabling is a controlled bench isolation on a stand; it goes back before the axis cuts parts.
Worked example: a wrong period setting multiplies every count #
These are hypothetical example numbers, not a rating of any scale; take the real signal period and multiplier from your scale's datasheet and the drive's interface manual.
Suppose the scale's electrical period is 20 µm and the drive's interface counts four states per period, so one count is 20 µm ÷ 4 = 5 µm. The parameter is entered instead for a similar-looking scale with a 200 µm period, so the drive treats one count as 200 µm ÷ 4 = 50 µm.
Command a jog of 100 mm, which is 100,000 µm. The scale emits 100,000 µm ÷ 5 µm = 20,000 counts. The drive converts those counts at 50 µm each and believes the axis moved 20,000 × 50 µm = 1,000,000 µm = 1,000 mm. In full-closed control the axis reaches the commanded count target early: real travel = commanded travel × (actual period ÷ configured period) = 100 mm × (20 ÷ 200) = 10 mm, so the axis stops after one tenth of the move.
The decision: before a full-closed axis is first powered, compute the expected counts per millimetre from the datasheet and compare it with the configured value. A ratio mismatch produces exactly this kind of travel shortfall or following error, not the scale alarm itself.
Verify the repair before returning the axis to service #
Put the monitoring switch back where the alarm requires it — 0 on that parameter family — restart the drive and read the alarm history, not just the status line. Jog through full travel with the cables dressed exactly as they will run in the machine, then run a production cycle with nearby motors and loads switching on and off.
The decisions, in order: no recurrence through a full cycle confirms the repair; recurrence under cable movement or in one travel band sends you back to the cable and mounting checks; recurrence only when a specific load starts points at routing and shielding; recurrence with every external item cleared leaves the drive input stage. An axis whose scale alarm can be reproduced by moving a cable does not go back into service — intermittent full-closed feedback at production speed is a crash looking for a time slot.
Questions asked
What does the scale error input connect to?
It is a dedicated health line from the external scale or its interface into the drive, separate from the counting signals. The scale drives it to the state its own manual specifies when its internal checks pass, and the drive alarms whenever the line sits anywhere else while monitoring is on. Because the health line is its own conductor, the counting channels can look clean on an oscilloscope and the alarm can still fire. Check the health line, its connector pins and the scale's output specification for that line as a separate item.
Why does the alarm care which control mode is active?
The scale error input is watched only when the position loop actually uses the external encoder, which means full-closed or hybrid control. Under semi-closed control on the motor encoder alone, the same broken wire exists but cannot raise this alarm. That works as a diagnostic in reverse: if the alarm fires, the drive really is closing position on the external scale, and the external path is the live feedback worth checking.
Can scale-error monitoring be disabled to keep the line running?
Yes, the alarm can be silenced by turning monitoring off, but the fault stays exactly where it was. The drive then closes position on external counts it can no longer trust, so a short, lost or corrupted count becomes unreported position error instead of a controlled stop. Treat disabling as a bench-isolation step only. Restore monitoring before production runs, and expect the alarm back until the cable, connector, mounting or parameter fault is actually fixed.
Does the same check apply to a rotary scale?
Yes. The drive sees only the health line and the counts, so the trigger conditions are identical for a linear or a rotary external encoder. A rotary scale adds one mechanical item a linear scale does not have: the coupling or gear train that turns it. That joint can slip or wear enough to change counts without tripping the scale's own health output, so its set screws, clamp and torque get checked alongside the wiring.