Servo Overheat Alarm With a Cold Motor: Test the Thermal Switch
Short answer
A servo overheat alarm with a cold motor is almost never heat. The winding thermal switch is normally closed and reads near 0 Ω cold, so the alarm means the loop is open somewhere between the windings and the amplifier, usually the cable, a splice or a connector. Measure the loop end to end while flexing the cable before you replace the drive or another motor.

On this page
An overheat alarm on a servo axis whose motor is cold is, in most cases, an open circuit in the motor's thermal-switch input, not heat. The winding thermostat is normally closed and reads near 0 Ω cold; the amplifier reports overtemperature when that loop goes open, and a spliced or damaged cable can open it intermittently while the motor stays cold. Measure the loop end to end at the amplifier connector while flexing the cable, before you replace a drive or another motor. The test needs a multimeter and a few minutes, and every possible result points to one specific repair.
Read the alarm name before you touch anything #
Three different conditions get reported as an overheat on a servo axis, and the exact alarm text or code tells you which loop to test. The first is a motor overtemperature input: a discrete, normally closed thermostat embedded in the windings, wired to two designated input terminals on the amplifier. The Kinetix 7000 high-power servo drive user manual, for example, lists the normally closed motor thermal switch among its overtemperature faults and names open motor wiring as the item to check.
The second is an amplifier overtemperature from the drive's own heatsink sensor. The third is calculated protection: some drives build a thermal image from motor current and time, and some servos carry no discrete switch at all, reporting winding temperature through a sensing element inside the encoder instead. One documented example is CNC servo alarm SV0430, which trips on encoder-measured motor temperature, so its fault path is the feedback cable rather than a switch loop. Write down the exact alarm text first: with a motor cold to the touch, a motor-thermal alarm means the sensed circuit went open, while a drive-thermal alarm sends you straight to the drive's cooling.
Why a cold motor still alarms #
The winding thermostat is a bimetal snap disc. Heated to its set point, the disc reverses and the normally closed contacts open; when it cools, the disc snaps back and closes them again. That automatic reset is why genuine trips also clear themselves, so an alarm that comes and gone cannot be judged by its behavior alone. But the switch cannot be open below its set point, so a cold motor plus a motor-thermal alarm means the loop opened somewhere else: a conductor, a splice, a connector or a terminal. Intermittency is the signature of a mechanical open, because the cable moves with the axis and the circuit makes and breaks with the bend.
If the motor has already been swapped and the alarm survived, the swap convicted everything it did not change: cable, connectors and the amplifier input. Before condemning another part, read how to tell if a servo motor is actually faulty and test it deliberately rather than by substitution.
What a healthy loop reads #
At the thermostat terminals, cold, expect the same reading you get with your probes shorted together: effectively 0 Ω. End to end through the cable you add only conductor resistance.
Calculated example, not a measured result: 8 m of cable carrying the thermal pair in 22 AWG copper at 0.0529 Ω per metre.
- Loop conductor length: 2 × 8.0 m = 16.0 m
- Conductor resistance: 16.0 m × 0.0529 Ω/m = 0.85 Ω
- Two crimped joints at about 0.02 Ω each: +0.04 Ω
- Expected at the amplifier connector: about 0.9 Ω, plus your meter leads
The decision for those inputs: a stable reading within about an ohm of the calculated value is a good loop; an open circuit, or any flicker toward open when the cable moves, is the fault. For a longer or thinner cable, redo the arithmetic: 26 AWG at 0.134 Ω/m over the same 16 m loop gives 2.1 Ω. The pass condition is stable and near the arithmetic, not one universal number.
| Measurement point | Cold reading | Verdict |
|---|---|---|
| Probes shorted (meter reference) | Typically 0.0 to 0.4 Ω | Your lead resistance |
| Across the thermostat at the motor | Equals the shorted-probe reading | Switch closed, healthy |
| Across the loop at the amplifier connector | The calculated conductor value, 0.9 Ω in the example | Loop continuous |
| Same point with the cable flexing | Unchanged | Pass; any jump toward open is an intermittent conductor |
Test the loop end to end #
- Lock the machine out with its approved electrical procedure, verify zero energy, and unplug the motor cable at the amplifier before measuring. The input may carry a detection voltage, and a resistance measurement on a powered circuit is wrong at best.
- Identify the pair from the motor's wiring diagram. On many servos it is a small-gauge pair, often white, routed out under the encoder cover and run through the motor cable to the amplifier. Color is a hint, not documentation.
- At the motor, measure across the thermostat. It should match your shorted-probe reference.
- At the amplifier connector, measure across the two loop pins and compare against the calculated conductor resistance.
- Keep the meter connected and flex the cable through the axis's full travel range, especially any splice and both strain reliefs. A reading that holds is a pass; a flicker toward open has found your fault.
- Inspect the terminations at both ends: pulled ferrules, backed-off terminal screws, a cold solder joint at a splice, a shield strand bridging into the wrong pin.
If the loop measures good #
A solid, stable loop means the alarm is not coming from the switch circuit, so work the other paths in order of cost. First the amplifier's own overtemperature: a failed or blocked cooling fan and a fouled heatsink latch an overtemp fault with a cold motor. Second, the drive's calculated thermal protection, which integrates motor current against time and can trip on duty cycle with a motor that is only warm. Third, on motors that report temperature through the feedback device, re-check the encoder path; on an older axis, start with identifying geared resolver and encoder feedback on old servos so you know which sensing you actually have.
The jumper is a discriminator, not a repair #
Shorting the two thermal-input terminals at the amplifier separates the drive from the wiring. If the alarm stops, the open is in the external loop: switch, cable or connectors. If it continues, the alarm source is inside the drive, in its heatsink sensing or its calculated model. Treat the jumper as a time-boxed, supervised diagnostic on an axis under control, and remove it before the machine returns to production: while it is installed the motor has no direct winding protection, and where the drive also runs a thermal model, that model estimates from current and time rather than measuring the winding. If the axis must run while a cable is on order, the legitimate path is repairing the loop, not operating with the input jumpered.
Rebuild the cable so the fault stays gone #
Before unplugging anything, record the assembly pin for pin: connector types and orientations, pin numbers, conductor colors and gauge, shield and drain termination, and which amplifier terminals the pair lands on, taken from the drive manual's terminal designation rather than memory. A generic motor cable is not evidence of compatibility. At the splice, solder the conductors, insulate each with adhesive-lined heat shrink, and add strain relief so flex loads the jacket instead of the joint, or replace the whole assembly. After the repair, repeat the end-to-end flex test, then run the axis through the exact moves that used to provoke the alarm and watch the alarm history: an intermittent open is only proven fixed by the motion that exposed it.
What each result tells you to do #
| Test result | Decision |
|---|---|
| Thermostat open at the motor, cold | The switch itself has failed; replace the motor. This is the one motor-side fault the test catches, and it is rare. |
| Thermostat closed, loop open at the amplifier | Cable or connector fault; repair or replace the cable assembly. |
| Reading flickers toward open on flex | Intermittent conductor or joint; rebuild the splice or the termination that moves. |
| Loop stable near the calculated value, alarm persists | Not the switch circuit; check drive cooling, then the calculated thermal model, then encoder-carried temperature sensing. |
| Alarm stops with the jumper installed during the diagnostic | External loop confirmed; fix the cable and remove the jumper before production. |
Whatever branch you land on, verify with the axis moving through the fault's provoking conditions, not just a static measurement, and log the alarm history before and after so the fix is evidence rather than hope.
Questions asked
Can a servo motor overheat alarm be genuine when the motor is cold?
Only through the sensing path, not through heat. A normally closed winding thermostat cannot open below its set point, so a cold motor with a motor-thermal alarm means the loop is open, most often in the cable, a splice or a connector, and only rarely in the switch itself. A drive-overheat alarm with a cold motor instead points at the amplifier's own cooling.
What resistance should the thermal switch circuit read?
At the thermostat itself, the same as your probes shorted together, effectively zero ohms. End to end through the cable, add the loop conductor resistance: 22 AWG copper is 0.0529 Ω per metre, so an 8 m cable reads about 0.9 Ω, and 26 AWG over the same run reads about 2.1 Ω. A stable reading near your arithmetic is a pass; an open, or a value that changes with cable movement, is the fault.
Is it ever acceptable to leave a jumper across the thermal input?
No. The jumper is a supervised diagnostic that separates the drive from the wiring, and it comes out before the machine returns to production. Left in place it removes the only direct winding protection; where a drive also runs a calculated thermal model, that model estimates from current and time rather than measuring the winding. If the axis must run, repair the loop first.
Where do I find the thermal switch wires on the motor?
Usually a small-gauge pair, often white, leaving the winding area, commonly routed under the encoder cover and running through the motor cable to the two terminals the amplifier manual designates for the motor thermal switch. Identify them from the motor's wiring diagram before measuring; conductor color is a hint, not a specification.
Do I need the thermostat's trip temperature for this diagnosis?
No. The diagnosis only needs continuity: the switch must be closed when the motor is cold, and the loop must stay closed through the cable's full motion range. The set point matters when the motor genuinely runs hot, and you take it from the motor datasheet then, because it is a winding-specific value, not a generic one.