Troubleshooting
Servo pulse input mode mismatch causes motion without rotation
Short answer
A servo axis only moves on accepted command pulses. If the PLC output channels and the drive's selected input mode describe different interfaces (A/B versus pulse/direction), a held coil or a start bit looks running on screen while the shaft twitches briefly and stops. Match the channel mapping to the drive's input mode and command with a pulse-generating instruction.

On this page
A servo axis moves exactly as far as its accepted command pulses take it. When the PLC channel assignment and the drive's selected pulse input mode describe two different interfaces — one side wired and configured for A/B signals, the other for pulse/direction — a held output coil or an energized start contact produces a brief shaft twitch of roughly a second while the programming screen still reports the motor as running. The fix is to make both ends of the cable describe the same interface: in the resolved case discussed here, assigning the first output channel to A and the second to B restored normal rotation, and the axis was then commanded with a pulse-generating instruction instead of a fixed coil.
What the symptom tells you #
Record what you actually observe before touching settings:
- The programming software displays the motor (or the motion instruction) as running.
- The shaft makes a small movement, felt by hand, lasting about one second, and then holds still.
- The movement coincides with the moment a start contact or output energizes.
- No alarm appears on the drive.
The one-second twitch is a symptom, not a specified timeout or a diagnostic code. It is the initial edge of a held signal being interpreted by the drive as one or a few command events. After that, a steady electrical state adds no further position demand. The drive is behaving correctly; the command chain feeding it is not.
The drive counts pulses, not button states #
A pulse-commanded servo derives its position demand from accepted input events. A continuing pulse sequence advances that demand at a rate set by the pulse frequency; the total count, after the drive's command scaling, sets the commanded displacement. Neither quantity has anything to do with the state of a start button or a logic bit in the PLC.
This is why an energized output coil cannot substitute for a pulse train. A normal coil output produces one transition when it turns on. The drive sees that transition, may respond with a tiny movement, and then receives nothing further. Meanwhile the screen shows the instruction as active, because the bit really is on — the display reports the logic state, not measured shaft motion.
If you are still choosing or re-checking the pulse output configuration itself, the channel-by-channel setup is covered in configuring a PLC pulse-output servo axis before PLS2 moves. And once pulses are being accepted, the counts that reach the shaft follow the scaling described in how to calculate step and direction servo pulse scaling.
The two common input modes #
The interface configuration must describe the same signals at both ends of the cable. Most PLC-based motion uses the pulse train — often called pulse and direction — interface, where one signal carries speed as a pulse rate and the other carries direction as a level. The A/B interface instead uses two command channels whose phase relationship carries the same information. These are alternatives, not interchangeable wiring labels.
| Interface | Signal interpretation | Deciding check |
|---|---|---|
| A/B | Two command channels interpreted according to the drive's selected A/B mode | PLC channel assignment and drive input mode describe the same interface |
| Pulse/direction | One channel supplies command pulses; another establishes direction | Pulse output reaches the pulse input and the direction signal reaches its designated input |
| Steady energized output | A fixed electrical state rather than a continuing pulse sequence | No repeated edges exist at the drive input, so no continuing motion command |
A/B and pulse/direction both work; neither is more correct. What fails is the mismatch — the PLC mapped to A/B while the drive's mode setting, set by its configuration table or switch positions, expects pulse and direction, or the reverse.
Worked example: mapping the channels #
Here is the resolved case, with the arithmetic of what the drive received.
Before the fix, the drive's input mode was set for A/B operation, but the PLC outputs were assigned to the wrong channels. Energizing the start contact drove one channel high and left it there. The drive's A/B input logic counted the single transition on the affected channel as roughly one command event. With a command scaling of, for example, 10000 accepted pulses per motor revolution, that single event commands 1 divided by 10000 of a revolution, which is 0.036 degrees of shaft rotation — a movement you feel as a twitch and can barely see. After about a second, no further edges arrive and the shaft holds.
The fix was to assign the first output channel to signal A and the second output channel to signal B, matching the drive's selected mode, and to run the axis with a pulse-generating motion instruction. Commanding, for instance, 10000 pulses now produces one full revolution, and a 1000-pulse-per-second rate produces 0.1 revolutions per second, or 6 revolutions per minute. Those example figures illustrate the arithmetic; take the exact command scaling for your axis from the drive's electronic gear settings and your machine's mechanics.
Confirmation checklist #
Work through the chain in order, cheapest check first:
- Record the existing configuration. Save the PLC program and note the drive's command-input mode setting, switch positions and terminal connections before changing anything.
- Identify the drive's input scheme. Read the drive's terminal diagram and mode table. Establish whether its selected mode expects A/B, pulse/direction, or another documented pulse arrangement.
- Trace both command channels. Follow the wiring from the PLC output terminals to the drive inputs, including the required signal return, and check the electrical levels against the drive's input circuit specification.
- Match the PLC assignment to the drive mode. In the resolved installation, channel A on the first output and channel B on the second. For a different drive mode, assign channels per that mode's documented meanings rather than copying any example blindly.
- Check the instruction, not just the coil. Confirm the program uses a pulse-generating motion function whose output selection matches the configured channels. A coil held on is not a pulse train.
- Check drive readiness separately. The servo-on command had already been applied in this case, so enable alone was never the problem. Inspect alarms and any motion-inhibiting conditions anyway.
- Run a bounded test. A small nonzero displacement, for example 1000 pulses, at a conservative rate, with personnel clear of the mechanism.
One safety note: a bounded commissioning test still turns a live shaft. Keep hands, tools and loose clothing out of the mechanism and use the machine's approved commissioning controls; this procedure is not a safety validation of the machine.
Confirm pulses arrive, then confirm the shaft follows #
A successful configuration download proves only that settings reached the controller. To prove the drive receives valid pulses, monitor the assigned outputs and the motion instruction's live operands during the test, and measure both command signals at the drive terminals with an instrument suited to the circuit, comparing the channel relationship against the selected input mode. A PLC input can also miss pulses that are too short for its filter, a separate failure described in why a PLC misses short input pulses and how to catch them. Then read the drive's accepted-command indication and actual-position feedback: if the accepted count tracks your commanded count, the interface is right, and any remaining motion problem lives in tuning or mechanics, not in the mapping.
If the axis later follows commands but drifts between moves, that is a different fault with its own causes — see why a pulse-command servo axis loses position between moves.
The decision #
- Screen shows running, shaft twitches briefly on the start edge, no alarm: an input mode or channel mapping mismatch. Match the PLC channel assignment to the drive's selected input mode (in this case, first channel A, second channel B) and command with a pulse-generating instruction.
- Drive not enabled or alarming: fix enable and alarms first; the mapping check comes after.
- Pulses confirmed at the drive terminals, shaft still wrong or short: check the drive's command scaling and the mechanical transmission, not the mapping.
Questions asked
Why does the servo twitch for about one second and then stop while the screen still shows running?
The twitch comes from the initial edge on a command channel when the coil or start bit energizes. After that the outputs hold a steady level, and a steady level is not a continuing pulse sequence, so the drive accepts no further command events. The running indication on the screen reflects the PLC instruction state, not shaft motion; the mismatch between channel mapping and the drive's input mode is the usual cause.
Should I set the drive to A/B mode or pulse/direction mode?
Pick the mode your PLC hardware can actually generate. A high-speed pulse-output channel pair maps naturally to A/B quadrature or to pulse-plus-direction; an ordinary output coil maps to neither, because it cannot produce a pulse train. Once you choose, set the mode selection on the drive and the channel assignment in the PLC configuration to the same interface, then run a small bounded displacement test to confirm the shaft follows.
I entered zero as the pulse value in the motion instruction. What does that mean?
Read the instruction's own description before interpreting a zero operand: it can mean zero displacement (no commanded movement at all), zero frequency, or a zero-valued mode selection, and each has a different effect. Judge the test by the live values the executing instruction is using, not by what the offline program appears to show.
The drive shows a servo-on state but the axis still will not follow the command. What next?
Drive-on and alarm-free confirm the drive is ready to accept commands; they do not confirm it is receiving any. Check the accepted-command indication and actual-position feedback in the drive's monitoring functions while you run a test, and measure both command channels at the drive terminals to see whether edges arrive and whether their relationship matches the selected input mode.