What Decides a Step and Direction Drive on a PRT Fourth Axis
Short answer
A step-and-direction drive can run a PRT fourth axis, but the controller board decides it first: 4G, Alpha and developer boards expose usable pulse outputs, while third-generation or earlier boards do not without unsupported board surgery. With a usable board, the drive's input voltage and current, its pulse timing and the pulse rate your top speed needs decide the rest; wire, set the scaling, commission at low speed.

On this page
- The board generation decides whether you can wire it at all
- What the step and direction inputs actually draw
- Pulse width and direction timing set a second limit
- Pulse rate for a fourth axis at 60 rpm and 5,000 steps per revolution
- Commissioning order
- Three failure classes at commissioning
- A servo drive on step and direction
- The decision, case by case
- Questions asked
A step-and-direction drive can run a PRT fourth axis, and the decision arrives in a fixed order: the controller board first, the drive's input electronics second, the pulse rate your top speed demands third. A 4G, Alpha or developer board exposes usable pulse outputs for an external drive; a third-generation or earlier PRT board does not, because connecting one calls for scraping traces and soldering on the control board, and that is not a connection to build. With a qualifying board, three checks decide the rest: the current your outputs must deliver into the drive's step and direction inputs, the pulse width and direction timing the drive accepts, and the pulse rate your axis speed requires. This article runs the checks in order and works the pulse-rate arithmetic for one example axis.
The board generation decides whether you can wire it at all #
A 4G, Alpha or developer board is the practical starting point: its outputs are accessible and documented for external step-and-direction drives. On a third-generation or earlier PRT board, an external drive connection calls for intricate scraping and soldering of traces on the control board. Treat that as a disqualifier, not a plan. The work is unsupported, it can leave the machine without a working controller, and there is no documented way back if the axis ever needs its original drive again.
The decision here is binary. Board identified as 4G, Alpha or developer: continue to the electrical checks below. Third generation or earlier: stop, and obtain a documented upgrade or interface path from the controller manufacturer instead of modifying the board. And a board generation name is not a pinout - read the connection documentation for the installed board before drawing a single wire, because an accessible output still needs the right reference and the right current path.
What the step and direction inputs actually draw #
A step input requests one increment of motion; a direction input sets its sign. Neither signal carries motor power. The drive's power stage supplies motor current, and the controller only switches the small signal current the input circuit needs - small, but specified. Each input is one of three types, and the type decides the connection:
- Single-ended: a signal conductor with a shared reference.
- Differential: a conductor pair, and both conductors connect.
- Optically isolated: an LED inside the drive that needs a defined forward current, most simply delivered through a series resistor; onsemi's application note AN-3001, Optocoupler Input Drive Circuits, documents this drive method.
Compare the drive's stated input voltage and current with the controller output's stated voltage and available source or sink current, before power-up. A hungry input can overload an output while the motor never turns - the damage a PRT owner fears happens on the signal side, not the motor side. Connector labels on the two boards prove nothing; the input diagrams decide.
Pulse width and direction timing set a second limit #
A pulse shorter than the drive's minimum pulse width may not register at all, and a direction change closer to a step edge than the specified setup and hold intervals can produce one wrong increment. Both limits come from the drive's command documentation, almost always drawn as a timing diagram, and they are compared against the controller output's documented capability. Raising commanded speed increases pulse frequency and never repairs marginal voltage or insufficient input current, so speed is not the cure for an interface problem. If you verify at the bench, measure at the drive's input terminals with a method compatible with that circuit's grounding and isolation - an optically isolated input is not probed like a logic gate on a shared ground.
Pulse rate for a fourth axis at 60 rpm and 5,000 steps per revolution #
Example inputs, for a typical rotary fourth axis; this is a calculated example for these inputs, not a measured result:
- S = 5,000 steps per axis revolution - the scaling you would set in the control software. In a real machine it equals the drive's configured steps per motor revolution multiplied by any gearbox ratio between motor and axis, so take the real value from the drive's configuration and your scaling setup.
- n = 60 rpm - an example top speed for a rotary axis carrying a workpiece.
The rule in words: pulse frequency in hertz equals steps per revolution multiplied by speed in revolutions per minute, divided by 60 seconds per minute.
The arithmetic: f = S × n ÷ 60 = 5,000 × 60 ÷ 60 = 5,000 Hz. The same axis pushed to 300 rpm needs 5,000 × 300 ÷ 60 = 25,000 Hz.
Result: the command chain must carry 25 kHz continuously, with pulse widths that still clear the drive's minimum.
Decision: read the controller output's documented maximum pulse rate; the axis speed ceiling is that rate multiplied by 60 and divided by S. A 25 kHz output caps this example axis at 25,000 × 60 ÷ 5,000 = 300 rpm; a 10 kHz output caps it at 120 rpm. If the ceiling sits below the speed the work needs, reduce S with coarser microstepping if position resolution still suffices, or use an output with a higher documented rate - the controller side of that limit is the subject of Why three stepper axes need dedicated high-speed outputs. The scaling arithmetic behind S is worked out step by step in How to Calculate Step and Direction Servo Pulse Scaling.
Commissioning order #
- Confirm the installed board is a 4G, Alpha or developer board, and read its connection documentation.
- Isolate power to the controller and drive and follow the machine's stored-energy discharge procedure before touching any wiring.
- Draw the signal circuit from the two wiring diagrams - conductor, reference or differential pair, and where the input current returns. Motor supply voltage never goes on the signal terminals.
- Check voltage and current ratings in both directions, and the drive's minimum pulse width and direction setup against the controller's documented output capability.
- Wire step, direction and any enable signal, keeping motor power wiring physically separate from the low-level command wiring.
- Configure the drive for its documented pulse-command mode and motor current, then the fourth-axis assignment and scaling in the control software.
- Command a small move in each direction at low speed, watch position and motor temperature, then raise speed toward the ceiling calculated above.
Three failure classes at commissioning #
- No pulses appear at the controller: an axis-assignment, enable or output-access problem in the configuration. Solve it in software before touching wire.
- Pulses appear at the controller but the drive rejects them: an electrical-interface or timing problem - input type, input current, pulse width or direction setup.
- The drive accepts pulses but the motor stalls or overheats: motor wiring, current setting, mechanical load or motion demand. Not the interface.
Keeping the three apart prevents the expensive swap: retuning software over a wiring fault, or rewiring over a load problem.
A servo drive on step and direction #
If the drive in hand is a servo rather than a stepper, step-and-direction compatibility describes only the command interface. The axis is not valid until that drive has its motor's feedback connected and its tuning done - the same pairing checks that govern any servo drive and motor, set out in Matching a servo drive to a motor: four checks before you buy. What a step-and-direction command interface does and does not close the loop on, compared with an open-loop stepper, is the subject of A step and direction servo drive versus an open-loop stepper.
The decision, case by case #
- 4G, Alpha or developer board, drive input current within the controller output's rating, pulse timing met, and the calculated pulse rate within both devices' limits: wire it, set the scaling, commission at low speed. The combination is sound.
- Third-generation or earlier PRT board: do not modify the board. Take the controller manufacturer's documented upgrade or interface path, or leave the axis on its original drive.
- A failed input current, timing or pulse-rate check on any board: resolve that item before connecting - a converter whose input and output specifications match both ends fixes electrical mismatches, coarser scaling or a slower ceiling fixes rate - then run the checks again.
Questions asked
Does the drive's built-in power supply power the step and direction signals?
Usually not for your connection planning. The built-in supply feeds the drive's own circuits; the step and direction inputs take their signal current from the controller side, through the path the input diagram specifies. Whether the drive permits any external signal supply take-off at all is answered by its wiring diagram, and motor supply voltage never belongs on the signal terminals.
Why does a stepper motor run hot while it only holds position?
Winding heat rises with the square of winding current times winding resistance, so a motor held at standstill with full current set dissipates nearly as much winding heat as it does while moving. If your axis holds position for long stretches, check whether the drive provides a reduced idle-current setting, and set it within the drive's documented limits for your holding load.
Can these drives be commanded from a controller other than the PRT board?
Yes. A step-and-direction drive has no loyalty to a controller family; it needs outputs whose voltage and available current meet its input specification, timing that meets its minimum pulse width and direction setup, and enough pulse rate for your top speed. Qualify those four items from the two datasheets and every check in this article applies unchanged.
Where do I find the minimum pulse width a drive accepts?
In the drive's command-interface documentation, normally drawn as a timing diagram showing the minimum step pulse duration and the direction setup and hold intervals. If those numbers are not published for the drive you own, it cannot be qualified from its catalog page alone; request the command specification from the manufacturer before wiring anything.