Troubleshooting
Where the Position Loop Closes in an Ultra 200 Servo Drive
Short answer
The letter on the Ultra 200's front display answers the question. In Analog or Follower mode the drive closes only the velocity and current loops and the 1746-HSTP1 module owns position; in Preset mode the drive closes the position loop itself. The feedback words returned to the SLC 500 are monitoring data, never a correction path, so PLC logic does not compare encoder position and re-command the drive.

On this page
The answer sits on the drive's front display. When an Ultra 200 series drive shows A (Analog) or F (Follower) on its status display, the drive closes only the velocity and current loops and the 1746-HSTP1 module closes position; when it shows P (Preset), the drive closes the position loop itself. So no: your SLC 500 program does not need to compare the encoder feedback against the distance moved and send a correction back through the HSTP1. The actual-position and encoder-feedback words the module returns are monitoring data. What follows is how each mode assigns the loops, when a distance command sent every scan actually starts a new move, and how to get the configuration tool the legitimate way.
Read the mode letter before touching anything else #
The Ultra 200 user manual (publication 1398-UM000) documents that the drive display shows an operational status letter — A, F or P, for Analog, Follower or Preset mode — and the series product data (1398-2.0) describes the same drive family as configurable as indexing drives, velocity servo drives, stepper drives, or master encoder followers. That single letter tells you which device owns position before you change a parameter. If you do open the panel to trace command wiring, lock out and tag the drive's incoming power and follow the manual's bus-discharge procedure first; the DC bus holds charge after power-off.
What each operating mode assigns to which device #
- Analog (A): the command input is an analog demand, normally velocity. The drive closes the velocity loop and the current loop; the HSTP1 is the position controller, comparing commanded position against feedback and driving that analog demand.
- Follower (F): the drive regulates velocity against a master encoder so the axis tracks the master. The position relationship comes from the master, and the drive again closes only velocity and current.
- Position tracking (step and direction, or separate forward and reverse step pulses): the HSTP1 generates the pulse trajectory and the drive closes velocity and current while tracking those pulses. This is the same division of labor as configuring a PLC pulse-output servo axis before PLS2 moves.
- Preset or index (P): the moves are stored in the drive. The drive closes position, velocity and current itself; the PLC selects and triggers a move like an output word and watches done and fault bits, treating the drive as I/O.
Whatever the mode, position is corrected in exactly one device. The mode letter tells you which one.
Feedback in the data table is monitoring, not control #
The actual-position and encoder-feedback values the HSTP1 returns to the SLC 500 serve operator display, sequencing, completion checks and fault detection. None of that closes a loop. If you add ladder logic that subtracts feedback from the target and writes a corrected command back every scan, you build a second position controller on top of the existing one — running at scan rate, far slower than the correction rate inside whichever device legitimately owns the loop. Two controllers on one axis do not average; they fight, and the usual symptoms are hunting around target and oscillation on every move. Keep the PLC's role to move requests, permissives and status. A fault where the axis moves before any PLC output is written is a different problem from loop ownership; that diagnosis is in why a stepper axis runs at drive power-up before software loads.
When the same distance every scan really starts a new move #
Sending the same distance word every scan is only a fault if the module re-executes it. Example numbers, illustrative and not catalog ratings: suppose the HSTP1 command is configured as a relative distance, the machine scaling is 1000 feedback counts for each inch of table travel, and the cycle needs a 2-inch move, so the distance word carries 2000 counts (2 in × 1000 counts/in = 2000 counts). If the start request in the ladder is a maintained bit instead of a one-shot, each qualifying transition can execute that relative distance again and the axis creeps another 2 inches per retrigger. If the same 2000-count word is an absolute target, a maintained bit is harmless: the axis holds at 2000 counts and no new motion starts.
Confirming check: command one move and watch the execute and done handshake bits for a single scan. If the request stays true across scans while a relative command is configured, fix the ladder to an edge-triggered one-shot — not the drive tuning.
| Symptom | Check first (cheapest) | Confirming check |
|---|---|---|
| Axis makes extra moves | relative distance plus a repeated execute | watch the execute and done handshake for one scan |
| Target fixed, move never completes | command scaling or feedback wiring | compare commanded counts with measured travel |
| PLC position disagrees with physical travel | feedback scaling or direction sign | command a known displacement and measure it |
| Drive faults mid-move | drive-side limit or feedback loss | read the drive fault display before resetting |
Getting Ultra Master the legitimate way #
Ultra Master is the manufacturer's configuration tool for this drive family. Get it, and the user manual, from the manufacturer or an authorized distributor — quote the full catalog number from the drive nameplate, not just the DDM-075 shorthand, plus any firmware revision shown on the display. Do not accept copies from forums or emailed attachments: you cannot verify the release or whether it matches your drive. The tool dates from an era that assumes an older Windows release, so put it on a dedicated service computer that meets the documented requirement and keep that machine off the plant network under your site's IT policy. Before changing anything, read the drive's configuration and save it to file: operating mode, command scaling, feedback setup, motion limits and the recorded fault history.
The decision for each case #
- Display A or F: the HSTP1 closes position; the drive closes velocity and current. Ladder logic handles moves, permissives and status, and the feedback words are read-only. Add no correction logic.
- Display P: the drive closes the entire loop. The PLC is an I/O-level trigger. Add no correction logic.
- Pulse position-tracking configuration: the HSTP1 generates the trajectory and the drive tracks it. The rule is the same.
In every case one device closes position, and the SLC 500 never becomes a second controller.
Questions asked
How can I tell which mode the drive is in without connecting software?
The drive's front display shows the operational status letter continuously: A for Analog, F for Follower and P for Preset operation. That letter is the first answer to any loop-ownership question. Connect the configuration tool only when you need to change the mode, examine the full parameter set or save the configuration to file.
Does the 1746-HSTP1 module need encoder feedback wired to it?
In Analog or Follower mode the module is the position controller, so it must receive a position signal to close the loop; take the exact wiring from the drive and module manuals for your combination. In Preset mode the drive closes position from its own motor feedback and the module reduces to command, trigger and status signals.
What is the right way to obtain Ultra Master and the drive manual?
Request both from the drive manufacturer or an authorized distributor, quoting the full catalog number on the drive nameplate and the firmware revision shown on its display. The manual is published literature and the configuration tool is licensed software. Copies passed around through forums or email attachments cannot be verified for release or revision match.
Could the PLC scan rate ever handle position correction itself?
It does not need to. Position correction belongs to whichever device closes the loop: the HSTP1 module in Analog or Follower mode, the drive itself in Preset mode. Both update far faster than a PLC scan, which is why a scan-based correction adds only a second, slower controller that fights the first one.