Troubleshooting

Why a differential step input voltage drop stops a stepper

Servo and stepper motion Published 6 min read By AutomateDirectUSA engineering team

Short answer

A differential step input that pulls a controller output from 3.64 V open-circuit to roughly 2.6-3.0 V per leg is loading the output, which is normal optocoupler input behavior, not proof of a weak signal. The decision comes from current through PUL+ and PUL- and an independent trigger test: if the drive ignores that trigger while another drive runs on the same outputs, the input stage is faulty.

On this page
  1. Does a voltage drop across a differential step input mean the signal is too weak?
  2. How much current does the input actually draw, and how do you estimate it?
  3. What did removing the controller's series resistors actually change?
  4. How do you measure a differential step input correctly under load?
  5. How do you prove the drive input stage is faulty?
  6. Why did the single-ended wiring attempt show a different waveform?
  7. When is the fault the controller, and when is it the drive?
  8. Questions asked

A loaded drop on a differential step input does not prove the signal is too weak. A controller output that sits near 3.64 V open-circuit and falls to roughly 2.6-3.0 V per leg with the drive connected is simply delivering current into the drive's optocoupler input, and the deciding test is whether the drive responds to an independent trigger applied straight to its input terminals at the level the manual requires.

Does a voltage drop across a differential step input mean the signal is too weak? #

No. The drop is the input loading the output, and a differential optocoupler input responds to current through its LED and its series resistor, not to a fixed supply level at a terminal. In the case behind this article the outputs measured 3.64 V peak unloaded and 2.95 V and 2.55 V per leg loaded, and the replacement drives later ran on the same outputs unchanged.

A stepper drive input stage is, in the typical design, an optocoupler LED in series with a current-limiting resistor on the drive PCB. Drawing that current necessarily pulls the driving output down. Measuring each signal leg to controller ground shows that loading, but it does not show the differential voltage across the pair, which is what the input circuit experiences. Judge compatibility from the drive's documented input-current requirement, not from the open-circuit voltage of the controller.

How much current does the input actually draw, and how do you estimate it? #

You estimate it from the loaded voltage drop and the input resistance, and you confirm it against the drive manual. The input-current specification is not in the case records here, so it is unknown; here is how to get a number once you have the two inputs.

Worked example, using an assumed input resistance of 300 Ω, a value you must replace with the figure from your drive's manual: with a loading drop of 0.65 V across that input circuit, the input current is 0.65 V ÷ 300 Ω = 0.00217 A, about 2.2 mA. If the manual requires 5 mA through the input, 2.2 mA is marginal; if it requires 2 mA, the signal is adequate and a drive that still ignores pulses is faulty. That arithmetic is a calculated example for the assumed resistance, not a measured result, and a different drive with a different input resistor changes the answer.

What did removing the controller's series resistors actually change? #

It raised the available current and improved the loading loss from about 0.65 V to about 0.4 V, and the motor still did not move. That result is the pivot of the diagnosis: more drive capability on the controller side did not cure the fault, so the limiting factor was not the output strength.

Series resistors exist to limit current into the input and protect both the controller output and the drive. Removing them raises the current the input can draw and increases the risk of damaging either side if the drive's input is a low-resistance design. Before changing any resistance, take the input-current value from the drive's manual and the output capability from the controller's documentation. This is a hardware modification made at the controller manufacturer's direction, not a routine compatibility adjustment.

How do you measure a differential step input correctly under load? #

Measure across PUL+ and PUL- at the drive terminals with the drive connected, during a continuous low-speed jog. A continuous jog gives repeated edges that a scope can trigger on; a single step command gives one edge that is easy to miss.

Procedure:

  1. Verify the power side first: drive supply voltage at its terminals, no alarm indication, and motor phase pairing from the drive and motor documentation. A shaft that locks solid on power-up proves winding current only, not pulse reception.
  2. Confirm the enable input: read its required polarity in the drive manual and measure the actual state at the terminal instead of trusting wire color or terminal name.
  3. Restore paired differential wiring: S+ to Step+, S- to Step-, and the direction pair the same way. Keep the cable short; a 75 cm run in this case picked up induced noise from the adjacent step line on the direction line.
  4. Command a continuous low-speed jog from the controller.
  5. Put the scope across PUL+ and PUL-, as close to the drive terminals as possible, and read the differential swing and edge quality.
  6. Repeat each leg to controller ground only if you want to quantify loading, never as the pass or fail measurement.

How do you prove the drive input stage is faulty? #

Apply an independent, controlled 5 V test signal directly to the drive's step input, and run a different drive on the same controller outputs. Two results decide it: if the drive ignores the independent trigger, its input stage is not responding to a signal that satisfies the common 5 V requirement; if another drive steps normally on the identical outputs and wiring, the controller can command a compatible drive through those terminals.

In this case the original drives failed both tests: no motion from the independent trigger, and no motion from the same outputs that immediately ran the replacement drives wired S+ to Step+, S- to Step- without added resistors. Three stored units failing identically is plausible when they share age and storage conditions, so unit count alone proves nothing; the independent trigger test and the substitute-drive test do.

Why did the single-ended wiring attempt show a different waveform? #

Because connecting the drive's input negative to controller ground changes the input circuit. With the scope on PUL+ referenced to ground, the measured voltage was higher than the differential arrangement produced, but the waveform shape changed, and the drive still did not move. A different measured voltage on a rearranged input is not a compatibility improvement; it is a different circuit. If you try it as a last-resort diagnostic, bond the supplies' negatives together first and re-check the input-current requirement, and expect the waveform to differ from the paired wiring.

When is the fault the controller, and when is it the drive? #

When the outputs pulse unloaded, load and drop only by the amounts above, and a different drive runs on them, the controller is exonerated. Keep the drive as the suspect and bench-test or replace it. Symptoms in order of cheapest check first:

  • Shaft locks on drive power-up but never steps: check enable state and polarity, then differential wiring, then input response; holding torque proves nothing about pulses.
  • Loaded voltage drops to roughly 2.6-3.0 V per leg: normal loading; confirm against the input-current specification before blaming it.
  • Resistor removal improves the drop but motion stays absent: stop changing the controller; run the independent trigger test.
  • Independent trigger at the correct level produces no motion: the drive input stage is faulty; no resistor or wiring change will fix it.
  • A different drive steps on the same outputs and wiring: replace the original drive and return the controller resistors to their original configuration if you removed them.

The decision: a differential step input that loads a 3.64 V output to about 2.6-3.0 V per leg is working as designed, and the drive that ignores an independent trigger while a different drive runs on the same outputs is the failed part. Measure across PUL+ and PUL- under a continuous jog for the real signal, use the manual's input-current figure for compatibility, and replace the drive. For the wider signal-side picture, the pulse budget that governs whether these edges arrive at all is covered in Stepper Drive Pulse Frequency Limit vs Microstep Demand, a related one-direction-only failure is covered in Troubleshooting a stepper axis that moves in one direction only, and if the axis moves the moment drive power is applied with no software loaded, that separate input-enable fault is covered in Why a Stepper Axis Runs at Drive Power-Up Before Software Loads.

Questions asked

My controller outputs measure about 3.6 V instead of 5 V. Is that why my stepper drive will not trigger?

Not by itself. An unloaded differential output near 3.6 V is normal for a logic driver with internal drops, and a differential optocoupler input responds to current through its LED and series resistor, not to 5 V exactly. Judge compatibility from the input current specification in the drive manual and the loaded differential voltage measured across PUL+ and PUL- while jogging.

How much input current does a stepper drive pulse input need?

The drive manual states it, and it varies by design. A typical input stage is an optocoupler LED with a current-limiting resistor on the drive PCB, so the requirement is a few milliamps through that circuit. Take the exact figure from the input specification table of the exact drive part, because one design's requirement does not transfer to another.

Can removing series resistors on the controller outputs fix a drive that will not step?

Removing series resistance raises available current and reduced the loading loss from about 0.65 V to about 0.4 V in the case behind this article, and the motor still did not move. If the drive ignores an independent trigger applied at the correct level, the fault is inside the drive input stage and no resistor change will fix it. Treat resistor removal as a hardware change made only at the controller manufacturer's direction.

Where should I put the oscilloscope probes to check a differential step signal?

Scope between the pulse input's positive and negative terminals right at the drive, with the drive connected and the controller running a continuous low-speed jog, which repeats the edges and makes them easy to catch. Ground-referenced measurements on each leg show loading but do not show the differential voltage the input actually experiences.

Keep reading

  • Explainer

    What a Stepper Driver Control Connector Needs From a PC

    A PC can drive a stepper driver's control inputs only when the step and direction signals meet the driver's documented input voltage and current, and the current-select inputs are grounded or pulled high to match the motor's rated current before power-up. Buffer the PC outputs whenever their levels or drive current are uncertain.

    Servo and stepper motion

  • Troubleshooting

    Why a Closed Loop Stepper Will Not Move Above 200 kHz

    The axis sits dead because the kernel exceeds the drive's documented step input limit, making each high or low state narrower than the input can latch. Set the kernel to half the ceiling, derive steps per mm from the drive's command resolution divided by the screw's travel per revolution, and verify the encoder A-channel polarity at the drive terminals.

    Servo and stepper motion

  • How-to

    Stepper rail binary position selection: one writer, all bits

    Five digital inputs, read as a binary address, select any of 32 stored positions on the drive. The reliable way to run this from a robot controller is a single continuously running thread that owns the five selection outputs, writes the complete bit pattern for every selection, and leaves each profile's next field blank so the drive never chains to a move the program did not request.

    Servo and stepper motion