Why a Hydraulic Axis Can Run in the Servo Fast Cycle

Servo and stepper motion Published 8 min read By AutomateDirectUSA engineering team

Short answer

Yes. A hydraulic axis can run in the servo fast and IPO fast execution levels while its encoder feedback arrives through a DRIVE-CLiQ encoder module and its ±10 V valve command leaves through a high-speed ET 200 S analog output on PROFINET. The fast cycle changes when the axis processing runs, not how fast each device exchanges data; the timing budget of encoder exchange, axis cycle, bus update, conversion time and valve response decides usable closed-loop performance.

On this page
  1. What the fast servo cycle actually changes
  2. The feedback path: an SMC module on DRIVE-CLiQ does not exclude it
  3. The command path: ±10 V out of the ET 200 S on PROFINET
  4. What synchronization adds, and what it cannot fix
  5. Worked example: the timing budget
  6. Enabling order, and the decision
  7. Questions asked

Yes. A hydraulic axis can run in the servo fast and IPO fast execution levels while its position feedback arrives through an SMC encoder module on DRIVE-CLiQ and its ±10 V valve command leaves through a high-speed ET 200 S analog output on PROFINET. Nothing in either path excludes the assignment. The fast cycle decides when the axis processing runs; the two networks decide how fast data reaches the periphery. Those are separate settings made in separate places, and switching on one does not turn up the others. What decides whether the closed loop works is the timing budget — encoder exchange interval, axis cycle, bus update time, analog conversion time, valve response — added end to end. This article separates the two decisions, works the budget with example numbers, and ends with what to enable and what to change first.

What the fast servo cycle actually changes #

The controller runs axis calculations on scheduled execution levels. The interpolation level generates the motion setpoints from the programmed positions; the servo level closes position and speed control on each axis against its actual values. In this controller family — the SIMOTION D435-2 PN/DP the configuration described here uses — both levels exist in a standard and a fast version: the cycle time of the servo execution level is a setting in the project's task configuration, and the fast synchronous servo task is documented in the motion-control basic functions manual as ServoSynchronousTask_fast. Assigning the hydraulic axis object to servo fast and IPO fast moves its control calculations onto that shorter cycle.

That assignment changes one thing: when the axis processing runs. It does not change the update time the PROFINET interface has negotiated with the ET 200 S station, it does not change the interval at which the SMC module delivers encoder values, and it does not touch the valve. Those quantities are configured in three other places and have to be checked in their own right. An axis can compute on a fast cycle while a peripheral exchanges data several times slower; the controller then re-uses feedback samples and re-sends held commands between exchanges instead of creating a faster physical loop.

The feedback path: an SMC module on DRIVE-CLiQ does not exclude it #

The SMC module is the encoder connection, not an execution-level property. The fast servo task reads the actual position every cycle from wherever the axis's actual-value assignment points, and DRIVE-CLiQ is one of the documented routes for that. Whether the loop closes on a drive-integrated encoder or on encoder values delivered to the controller is the decision covered in where the position loop closes decides your servo conversion; in this configuration the loop closes in the controller, on values that crossed DRIVE-CLiQ.

Commissioning has to prove the feedback is fit for that loop, which is separate from proving the axis can run fast. Trace the actual-value assignment to the module and channel fitted to this axis. Check that scaling reports millimeters, that positive physical travel increases the displayed position, and that diagnostics stay clean while the ram moves a controlled, independently measured displacement. The timing question is one number: the interval at which encoder values are exchanged. If it is slower than the fast cycle, consecutive cycles see the same sample and the loop's effective feedback rate drops to the exchange interval. Some drive families let acquisition run faster than the communication cycle — Beckhoff documents oversampling on its AX8000 multi-axis servo drives as multiple feedback samples per communication cycle — which shows acquisition rate and bus cycle are separate design quantities.

The command path: ±10 V out of the ET 200 S on PROFINET #

The analog output channel turns the controller's digital setpoint into a bipolar voltage: magnitude is command magnitude, sign is direction, according to the valve electronics and wiring. It is a command, not a position; the hydraulic response also depends on pressure, load and the valve itself. The mapping and verification of such a command — neutral voltage at zero command, correct sign and scaling at the valve input for small positive and negative commands — is covered step by step in controlling hydraulic cylinder position from a 0-10V analog input.

"High speed" in the module name is a family label, not a timing figure. The conversion time is documented for the fitted module in its function manual, defined as the interval from the digital value arriving in the module's internal memory to the analog output being settled. The bus side has its own setting: the station's update time is configured in the engineering tool's device properties under Advanced options > Real time settings > IO cycle by selecting Set update time manually, as described in the support article on PROFINET IO device update times. If that update time is slower than the fast cycle, each new setpoint the fast cycle computes is held until the next exchange, and the loop's command rate is the update time — the same rate effect covered for servo axes in what a fieldbus command update rate decides for servo axes.

What synchronization adds, and what it cannot fix #

PROFINET's real-time behavior is specified in the IEC 61158 and IEC 61784 fieldbus standards: a fixed, repeatable update time per device, with an isochronous mode that locks the exchange to the controller's cycle. In synchronized operation the controller reads inputs and provides output data in time for the start of the next data cycle, on a schedule the whole chain follows. The gain is determinism: every output value is at most one exchange old, at a fixed phase, instead of being anywhere from fresh to a full interval old depending on where the cycle happened to land.

Synchronization does not shorten the chain. It does not remove the module's conversion time, does not change the valve's response, and does not speed up a device whose configured update time is slower than the axis cycle. Activating servo fast and IPO fast is therefore not evidence that the PROFINET output path is synchronized to them; check the interface configuration and record which connections actually participate in the synchronous schedule.

Worked example: the timing budget #

Before the loop is verified end to end, budget each stage's waiting time at its full interval. The five inputs below are illustrative example figures chosen to make the arithmetic checkable; take each one for your hardware from the document in the right-hand column.

Timing element Example value Real value comes from
Fast execution cycle (servo/IPO fast) 2 ms Task configuration in the controller project
Encoder exchange interval on DRIVE-CLiQ 2 ms Axis and encoder configuration
PROFINET update time of the ET 200 S station 4 ms Device real-time settings
Analog output conversion time 1 ms Function manual of the fitted module
Valve spool step response 20 ms Valve datasheet

Worst-case delay from a real position change to the corrected voltage arriving at the valve is one encoder interval (2 ms) plus one axis cycle (2 ms) plus one bus update interval (4 ms) plus conversion (1 ms) plus valve response (20 ms): 2 + 2 + 4 + 1 + 20 = 29 ms. Feedback ages on the way in as well: at 500 mm/s, one exchange interval of 2 ms lets the load cover 1 mm (500 mm/s × 0.002 s = 1 mm), and the tuning has to know that lag.

Now the comparison that makes the point. Leave the station at a 32 ms update instead, and the same sum becomes 2 + 2 + 32 + 1 + 20 = 57 ms, with the fast cycle re-sending the same voltage 16 cycles in a row (32 / 2 = 16): the axis computes corrections it cannot output.

In the 29 ms budget the valve is by far the largest term. Matching the bus update to the cycle is configuration and worth doing first; after that, most of the remaining delay is hydraulic and no controller gain removes it. A rule of thumb, and it is only a rule of thumb: keep total loop delay under about one tenth of the governing move time. For a 250 mm positioning move executed in 400 ms the target is 40 ms (400 ms / 10) and the example budget fits; for a 50 mm move in 80 ms the target is 8 ms (80 ms / 10), which sits below the valve term alone, so this hardware cannot serve that move closed loop and the valve has to change before the cycle helps at all.

Enabling order, and the decision #

Enable the loop in this order, because each step can invalidate the ones after it:

  1. Trace the actual-value assignment to the fitted encoder channel; confirm scaling and direction against a controlled, independently measured displacement.
  2. Verify the command channel at the valve input: neutral voltage at zero command, intended sign and scaling for small positive and negative commands.
  3. Record the five budget intervals and set the station's update time to the fast cycle if the device supports it; note which connections participate in the synchronous schedule.
  4. Before first closed-loop motion, confirm travel limits and the machine's protective functions against the machine's risk assessment and the applicable safety standard, and test command polarity with the pump unloaded or at low pressure — a reversed sign turns corrective action into a larger error, fast.
  5. Close the loop and tune. Gains come last because tuning cannot repair a stale feedback path or a held command; the gain side of a slow hydraulic loop is covered in why PI tuning is slow on a high-inertia hydraulic drive.

The decision, for each question this configuration raises:

  • Can the hydraulic axis object run in servo fast/IPO fast with feedback via the SMC on DRIVE-CLiQ and the command via the ET 200 S on PROFINET? Yes. The fast level is a property of the axis processing schedule; neither network path excludes the assignment.
  • Does enabling it make the physical loop faster? No. The loop performs like the slowest chain of encoder exchange, axis cycle, bus update, conversion and valve response — budget them and treat the fast cycle as necessary, not sufficient.
  • Where does the improvement come from first? Configuration: match the bus update to the cycle and confirm synchronization. The valve term is usually the largest that remains, and it is hardware; change it before changing gains.

Questions asked

Does the encoder module type decide whether the hydraulic axis can use the fast cycle?

No. The fast execution level is assigned to the axis object in the controller project, and any feedback path that delivers valid actual position at the configured cycle can serve it. The module choice decides the exchange interval, the scaling options and the diagnostics you get, so it shapes loop performance, but it never blocks the fast-level assignment itself.

What update time should the PROFINET station for the valve output be set to?

Set the ET 200 S station's update time equal to the fast execution cycle when the station supports it, and otherwise to the smallest value its real-time settings offer. A slower update does not stop the fast cycle from computing; it only means each new voltage is held until the next exchange, so the command rate equals the update time.

Why does a faster cycle not make the hydraulic axis hold position tighter?

Steady-position accuracy is bounded by feedback quality, valve deadband and drift, not by how often the correction is recomputed. Once the correction is computed faster than the valve and load can respond, extra cycles produce repeated identical commands. Improving hold accuracy means a cleaner encoder signal, a valve with less deadband, and gains tuned to the measured delays, not a shorter cycle.

What should be measured first after enabling the fast cycle?

The end-to-end delay, not the cycle time. Step the command slightly and time the voltage change at the valve input; then step the ram and time the first visible change in reported position. Compare both against the budget. Whatever stage adds more than its document promised is the one to fix before any gain is touched.

Does isochronous synchronization shorten the delay to the valve?

It removes the randomness, not the length. Synchronized exchange gives each output value a fixed phase in the bus cycle, so the wait between computing a setpoint and sending it becomes constant instead of varying from zero up to a full update interval. The update interval itself, the conversion time and the valve response are unchanged.

Keep reading

  • Explainer

    Servo Motor as a Linear Axis: Scaling and Feedback Choices

    A rotary servo motor becomes a linear axis through one scaling number — travel per motor revolution, wheel circumference or screw lead divided by gear ratio — and one decision on where the position loop closes. A 0.1 m wheel at 10:1 gearing gives 0.01 m of travel per motor revolution, or 628.3 rad/m. An analog distance sensor on an input card is monitoring data, not axis feedback, until a documented feedback input binds it to the axis.

    Servo and stepper motion

  • How-to

    Switching a hydraulic rotary axis between position and speed control

    Switch modes as a state machine: hold with position control at joystick neutral, leave neutral into traversal without position control, scale override.velocity with the deflection, decelerate to a verified standstill, then write the hold target to the stopped angle before re-enabling position control. Speed mode provides no force limiting, so supervise differential pressure against a torque-derived threshold in your own cyclic logic.

    Servo and stepper motion

  • Explainer

    When a Step and Direction Servo Drive Is Closed Loop

    A step and direction servo drive is closed loop because the drive itself reads the motor encoder and corrects position with its internal PID loop, thousands of times a second; the step pulses are only a position command. Feed encoder pulses to the controller as well only when its logic must know actual position, and only after the encoder, drive and controller documentation agree on signal format, levels and loading.

    Servo and stepper motion