Why a hydraulic pump command should follow the cycle, not the valves

Pneumatics and hydraulics Published 6 min read By AutomateDirectUSA engineering team

Short answer

Own the pump run command in one place: a hydraulic-cycle demand set by the active sequence, released by a retriggerable off-delay just longer than the longest measured valve-command gap. Per-stage ANDs and a raw OR of valve outputs both drop the request during break-before-make transitions, so the pump stop-start cycles; the overrun bridges those gaps at the cost of relief heat.

On this page
  1. Why the pump should not follow the valves one for one
  2. The two common fixes and how they fail
  3. The structure that works
  4. The heat cost of overrun, with numbers
  5. Measuring the delay instead of guessing it
  6. Implementation steps
  7. Questions asked

Put the pump run command under the control of one owner: the active hydraulic-cycle state, released after the cycle ends by a retriggerable off-delay set just above the longest measured gap between valve commands. Per-stage AND instructions and a raw OR of valve outputs both fail the same way, because a break-before-make stage transition drops the request for at least one scan and the pump stop-start cycles. A short overrun against the relief valve bridges that gap cleanly; its only cost is heat, and the delay is a measured number, not a guess.

Why the pump should not follow the valves one for one #

A sequence that starts a stage on a valve output, waits for an inductive sensor, then turns the valve off before the next stage's valve turns on has an unavoidable dead interval at every transition. If the pump request is built from the same valve bits, that interval reaches the pump output. The gap may last one program scan in the chart and far longer at the physical starter, because output-image update, task order, and communications cycles all add latency.

The result is not a logic nuisance. Every stop-start of a fixed-speed pump motor puts inrush current on the windings and switching duty on the contactor, and the hydraulic pressure collapse and rebuild at each restart can disturb the motion in progress. A pump that runs steadily through the whole cycle avoids all of it.

This is the same family of transition problem that makes a hydraulic cylinder jerk when a valve shifts; the related article Why a Hydraulic Cylinder Jerks When the Valve Shifts covers the valve-side effect in detail.

The two common fixes and how they fail #

A pump AND inside every stage block. Each sequence step gets its own copy of the pump request, ANDed with the stage's activity flag. The failure is ownership: one physical output is now driven from several blocks, and a step transition can clear the old request before the new step establishes its own. Whichever block runs last in the scan wins, and the pump output chatters.

A direct OR of all valve outputs. This centralizes the logic but keeps the same hazard. If one valve turns off before the next turns on, every OR input is false momentarily and the pump drops with them. It also holds the pump on whenever a valve is on, including states where no hydraulic power is actually needed.

Sensor flags as the demand. An inductive sensor reports position or stage completion, not energy demand. It can stay true after motion ends, fail to arrive, or be true while the machine idles. It is a status, not a request.

None of these is the right basis. The right basis is a state that says "the hydraulic cycle is active," held true across every legitimate transition.

The structure that works #

Assign the physical pump output to exactly one routine. The sequence supplies one logical demand; the pump routine applies permissives, shutdowns, and feedback checks, and only its final result drives the starter or pump-starting device.

The demand itself is simply:

Set it when the sequence begins (or when an operator commands a permitted manual hydraulic function) and clear it only when the final motion reaches its completion state or the cycle is cancelled. Then release the pump on a retriggerable off-delay: the request goes true immediately when any valid demand appears and stays true for the configured interval after the last demand disappears. A new demand inside that interval retriggers the timer, so normal handoff gaps never drop the output.

Two rules bound the delay. First, set it above the longest measured valve-command gap plus a margin for scan time and output response — the worked example below shows how. Second, every emergency stop, overload, and fault path must override the timer and remove the pump command immediately. The delay bridges normal sequencing gaps; it must never conceal a stop condition whose purpose is to remove hydraulic power. That override belongs to the machine's defined safe-state logic and its risk assessment, not to this article.

The heat cost of overrun, with numbers #

The overrun works because this pump can run against its relief valve with no sequence interruption. The price is thermal: every unit of pump power delivered across the relief valve turns into heat in the oil.

Worked example. Take a pump delivering 10 L/min across a relief setting of 2000 psi (about 138 bar = 1.38e7 Pa):

  • Flow: 10 L/min = 0.167 L/s = 1.67e-4 m³/s
  • Power to heat = pressure × flow = 1.38e7 Pa × 1.67e-4 m³/s ≈ 2300 W

So one second of unnecessary overrun on this example system adds about 2.3 kJ to the oil — with no useful work done. Scaled over hundreds of cycles per shift, that is what drives a reservoir warm, and oil temperature is the limit that decides how long an overrun is acceptable. The delay should be as short as the measured handoff gaps allow, and the relief path must be rated for continuous flow at that setting.

Measuring the delay instead of guessing it #

Trend four signals together for at least one full forward-and-reverse cycle: every valve command, the pump request, the final pump output, and motor-running feedback (plus pressure if it is available). At each stage transition, measure the interval between the old valve command dropping and the new one coming on.

Worked example of the delay selection. Suppose the trace shows a longest handoff gap of 150 ms, with scan and output-update overhead adding up to 50 ms in the worst observed transition. The retriggerable off-delay should be 150 ms + 50 ms ≈ 200 ms — comfortably above the gap, far below anything that produces measurable heating at 2.3 kW. Then retest under the slowest normal controller and communications conditions, because task scheduling and network updates stretch the gap at the device.

Do not pick the number from a habit like "always one second." One second of relief-flow overrun per cycle at the example's power level is 2.3 kJ per cycle of pure heat; a 200 ms delay costs a fifth of that and does the same job.

Implementation steps #

  1. List every state that legitimately requires hydraulic power: each sequence stage, the reversing motion, permitted manual functions, and any pressure-hold state. Exclude idle sensor indications.
  2. Create one hydraulic-cycle demand, set at cycle start and cleared only at true completion or cancellation.
  3. Route the demand, plus the manual demand, into the single pump routine. Apply run permissives and feedback checks there, and map only the final command to the pump-starting output.
  4. Start the pump early enough that usable pressure exists before motion needs it. Read the required lead time from a pressure trace, not from a timer habit.
  5. Shift stage valves as the hydraulic circuit requires. If overlap could connect opposing paths, use the circuit's intended neutral or interlocked transition; do not force make-before-break merely to keep the pump alive — the off-delay already covers the gap.
  6. At normal completion, put the valves in their designed stopped state, clear the demand, and let the off-delay expire.
  7. On fault or cancellation, execute the machine's defined safe state immediately, overriding the timer.

The end result for each case: per-stage ANDs — replace with the single-cycle demand; valve-output OR — keep only as a secondary request behind the off-delay; sensor flags — never a pump demand; overrun — measured, short, and always subordinate to the stop paths.

Questions asked

Can I just OR all the valve outputs to run the pump?

It works only if no two valve commands ever overlap with a gap, which most sequences cannot guarantee. When one valve turns off before the next turns on, the OR goes false for at least one scan and the pump output drops with it. Use the OR only as a secondary request feeding a retriggerable off-delay, never as the sole source of the pump command.

How long should the pump overrun delay be?

Slightly longer than the longest measured gap between the old valve command dropping and the new one coming on, plus a margin for scan time and output response. In the example, a 150 ms measured gap with 50 ms of margin gives a 200 ms off-delay. The number comes from a trace of valve commands and pump output, not from a datasheet.

Is a short pump overrun against relief pressure harmful?

It costs heat, nothing else, provided the relief path is rated for continuous flow and the fluid temperature stays within the system's limit. All pump power delivered across the relief valve turns into heat in the oil, so a long overrun on every cycle will warm the reservoir. Keep the delay as short as the measured handoff gaps allow.

Should an emergency stop delay the pump shutdown?

No. Emergency stop, overload trips, and fault shutdowns must remove the pump command immediately, ahead of any off-delay. The delay exists to bridge normal sequencing gaps only; it must never keep hydraulic power available when a stop condition is meant to remove it. Wire or program the protective paths so they override the timer directly.

Do the same rules apply to a fixed-speed pump on a motor starter?

Yes, with more reason: every pump stop-start puts inrush current on the motor and switching wear on the starter, so frequent cycling is worse than a brief overrun. Keep the single-cycle demand, the single pump routine, and the measured off-delay, and check the motor and starter documentation for the permitted number of starts per hour.

Keep reading

  • Troubleshooting

    Why a CNC Hydraulic Pump Shows Zero Pressure After a Shop Move

    A hydraulic pump that reads zero right after a shop move is usually fed with two supply legs swapped: reversed phase sequence spins the pump motor backward, and a pump running against its rotation arrow cannot build pressure. Verify voltage and phase sequence at the disconnect first, jog the motor and compare with the pump's arrow, and only then test the hydraulics.

    Pneumatics and hydraulics

  • Troubleshooting

    Why a Hydraulic System Hums Under Load at Full Speed

    Check the pump delivery hose first. A hydraulic hum that grows as the machine loads is pump pressure ripple meeting a line that no longer damps it: a smaller bore adds restriction and a stiff wall removes the compliant cushion that smooths each pulse. Restore the specified bore and a compliant construction before touching the relief valve, which is the second suspect.

    Pneumatics and hydraulics

  • Selection guide

    Controlling Hydraulic Cylinder Position From a 0-10V Analog Input

    No. An analog voltage into a hydraulic valve commands spool position and therefore flow, not cylinder position. Use it as the position reference to a closed-loop motion controller with an in-cylinder displacement transducer, and size the valve near 10 L/min for the 7.8 L/min peak of the 1.5-inch-bore example.

    Pneumatics and hydraulics