Why a servo open collector status output reads nothing on a PLC

Servo and stepper motion Published 6 min read By AutomateDirectUSA engineering team

Short answer

S-RDY, INP and ALM style servo status outputs are open collector: each can only pull the PLC input toward common, never drive it high. Fit a pull-up resistor to the PLC input supply, then assign and enable the signal to that output channel in the drive parameters; only then will the input change state.

On this page
  1. Why does a servo status output read nothing on a PLC input?
  2. What wiring does an open collector status output need?
  3. What value of pull-up resistor should I use?
  4. Why is the PLC input still flat even with the resistor fitted?
  5. How do I test each status signal end to end?
  6. When should I use an optocoupler instead of a pull-up resistor?
  7. Questions asked

Your servo status output is almost certainly open collector, and an open collector output has no high side: it can pull the PLC input down to common when the signal is active, but it cannot drive the input up. With no pull-up resistor the input simply floats, so the PLC reads nothing or reads a value that never changes, even though the wiring diagram was followed exactly.

Why does a servo status output read nothing on a PLC input? #

S-RDY, INP and ALM-style status outputs are open collector transistor outputs: the transistor sits between the output terminal and the drive's internal common, with nothing on the supply side. The first sentence of the drive manual's output circuit diagram usually says so, and the symptom confirms it.

When the signal turns on, the transistor conducts and pulls the output terminal to common, which a sink-wired PLC input reads as a logic low. When the signal turns off, the transistor stops conducting and the terminal is connected to nothing at all. A plain digital input with no pull-up has no defined voltage in that state, so the input may read high, low or drift, but it never gives you a clean, repeating transition tied to servo state.

This is the single most common cause of a servo status input that reads nothing: the wiring matches the manual, the meter shows the output change at the terminal, and the PLC still sees a flat input. The fix is on the PLC side, not the servo side.

What wiring does an open collector status output need? #

Give each status output its own pull-up resistor from the output terminal to the PLC input module's supply, so the input supply defines the high level and the drive output pulls it low. Wire the PLC input for sink operation, and make the common reference connection between the drive output common and the input module's common as both manuals' diagrams show.

The circuit is one loop: input supply, pull-up resistor, output terminal, transistor, common. Two things to keep straight:

  • Pull up to the PLC input supply (typically the 24 VDC field supply), not to the drive's internal control supply, unless both manuals show that arrangement.
  • Do not add a supply voltage in series that exceeds the open collector output's rated off-state voltage; take that rating from the output specification table of your exact drive manual.

If the input module is source-type rather than sink-type, the polarity flips and a resistor alone is not enough. Our article on why a stepper pulse output reads about 12 VDC on a meter covers how input wiring type changes what a meter shows on the same terminal.

What value of pull-up resistor should I use? #

Size the resistor from three numbers in your own manuals: the input supply voltage, the PLC input's required on-state current, and the drive output's maximum sink current. As a calculated example for a 24 VDC input supply, a PLC input that needs about 5 mA to register reliably, and an open collector output that drops roughly 1 V when conducting, the resistor is:

R = (24 V - 1 V) / 0.005 A = 4600 ohm  ->  use the standard value 4.7 kOhm
I = (24 V - 1 V) / 4700 ohm  = 4.9 mA
P = I^2 * R = (0.0049 A)^2 * 4700 ohm = 0.11 W  ->  use a 0.25 W resistor

Those input-current and saturation-voltage figures are example assumptions, not universal values; take the input's rated on-current from your PLC module datasheet and the output's saturation voltage and maximum sink current from your servo drive manual, then redo the arithmetic. The upper bound on current is the drive output's rated sink current, and the resistor wattage must exceed the calculated dissipation. If you are sizing a pull-up for a dedicated alarm output specifically, the worked example in pull-up resistor sizing for a servo drive fault output walks the same calculation in more detail.

Why is the PLC input still flat even with the resistor fitted? #

Because on most servo drives the status signals are monitoring functions that must be assigned to a physical output terminal and that terminal enabled through the drive's output-assignment parameters before any signal appears. A correct resistor and correct wiring produce nothing until the drive is told to route the signal to the terminal.

Check, in this order:

  1. Find the drive's output signal assignment parameters (the section of the manual covering output signal selection or monitoring output setting).
  2. Link the status you want, servo ready, positioning complete or alarm, to the terminal number you wired.
  3. Set that output channel's enable or active setting so the assignment takes effect.
  4. Cycle drive power or apply the save-and-reset action the manual requires, because many drives only re-read output assignments at power-up.

The same parameter logic applies on the monitoring side: some drives also let you configure what their monitor outputs carry, and the manual's parameter chapter is where both the assignment and the polarity settings live. A flat input after this step points back to wiring polarity, so swap to the sink wiring diagram before changing the resistor.

How do I test each status signal end to end? #

Prove the loop one device at a time, because the drive, the resistor and the PLC input each fail differently.

  1. At the drive, command a known state: power up for servo ready, complete a small indexed move for positioning complete, and force or induce an alarm condition per the manual for the alarm output.
  2. With a meter across the output terminal and common, confirm the terminal drops from the pull-up voltage to near zero at each transition. If it never pulls low, the parameter assignment or the transistor is at fault.
  3. With the meter across the PLC input terminal and common, confirm the same transition appears after the pull-up resistor. If the drive terminal changes but the input terminal does not, the resistor, its supply connection or the common reference is wrong.
  4. Watch the PLC input bit change in the logic or the input status table at the same transitions. If the hardware is right but the bit does not move, check the input's filter or delay setting, which can be long enough to hide a short pulse such as a positioning-complete window.

When should I use an optocoupler instead of a pull-up resistor? #

Use a documented optocoupler interface when the drive's output voltage rating and the PLC input supply cannot be reconciled by one resistor, when the input module is source-type, or when the two devices do not share a clean common reference. The servo manual's I/O chapter shows the recommended interface circuit; build it as drawn.

An optocoupler also gives you galvanic isolation, which is worth having when the drive and the PLC cabinet are fed from different supplies. The transistor-level behavior behind all of this, including why a pull-up fixes a floating open-collector node, is laid out in the open-collector output voltage drop and pull-up fix knowledge-base page.

One safety note: an alarm output is a status signal, not a safety function. Never wire S-RDY or ALM in place of the drive's dedicated safety or STO inputs, and never treat a working status readback as verification of an emergency stop path; that is validated against the machine's risk assessment and the applicable functional safety standard, not against a PLC input bit.

The decision: if your servo status input reads nothing, add a pull-up resistor from the output terminal to the PLC input supply, sized from the two manuals, and assign and enable the signal to that terminal in the drive's output parameters. If the resistor alone leaves the input flat, the parameter assignment is the next thing to check, and the optocoupler circuit in the drive manual is the fallback when voltage ratings or input wiring types do not line up.

Questions asked

Can I connect a servo status output straight to a PLC input with no resistor?

Only if the input module already provides the pull-up to its own supply, which source-type wiring does not. With plain sink wiring and no resistor the input sits at whatever the drive output leaves it: pulled low when the signal turns on, floating otherwise, so it reads nothing useful. The resistor or a documented optocoupler interface is not optional.

Which supply should the pull-up resistor go to?

To the supply that the PLC input module is rated for, usually the same 24 VDC field supply wired to its input common. Pulling up to the servo drive's internal control supply instead puts that supply's voltage and current budget on the drive and can exceed the open collector output's rated voltage, so keep the pull-up on the PLC side unless both manuals say otherwise.

Does an open collector output need parameter setup as well as wiring?

On many servo drives, yes. The status signal such as servo ready or positioning complete is a monitoring function that must be linked to a physical output terminal and that terminal enabled through the drive's output assignment parameters. Wiring that is correct on the terminals still shows a flat input until the assignment exists, so check parameters before blaming the resistor.

Keep reading

  • Explainer

    Pull-up resistor sizing for a servo drive fault output

    An active-low servo fault output needs a pull-up resistor from the controller input to its supply. At 24 V, keep the resistor at or above 2.4 kΩ so a 1/4 W part stays within rating; 5.6 kΩ is a commonly documented value, dissipating about 0.10 W. Set the encoder-count alarm as allowed mechanical deviation times counts per millimeter, then verify it against deviation measured during normal moves.

    Servo and stepper motion

  • Troubleshooting

    Servo Position Counts Up While the Motor Is Stationary

    Counts that rise while the motor shaft is held still are false feedback counts, not motion. Compare the controller's tell-position reading against the drive's rotor-position display: a drive value steady within 1 count while the controller climbs condemns the simulated-encoder path. Isolate the encoder output, cable, breakout and counting input by substitution, one part at a time, cheapest check first.

    Servo and stepper motion

  • How-to

    Configuring a PLC pulse-output servo axis before PLS2 moves

    The drives are not plug and play: keep command scaling in one place, the drive's gearing or the PLC program, and stay under the 100 kHz pulse ceiling, which at 10,000 pulses per revolution caps the motor at 600 rpm. Prove direction, limits and homing first, then tune for the load.

    Servo and stepper motion