Why a Servo Origin Search Misses the Encoder Z Phase
Short answer
An origin search that moves toward home but never captures the Z phase almost always has no proximity transition to key on, the wrong homing method selected, or the capture stage never armed. Work through sensor, method, polarity and capture status in that order; an index alone is ambiguous by whole screw revolutions.

On this page
The axis drives toward home, the search never completes, and the Z-phase reference never captures. That combination points at the homing sequence, not the encoder: the Z phase fires once per encoder revolution whether you watch for it or not, and a drive that is waiting for a proximity transition first will ignore every one of them until a real home sensor defines which revolution counts. Work the causes below from cheapest to check to most involved, and confirm each before moving on.
The symptom, separated from the cause #
You see two things: commanded motion toward home happens, and the completed or referenced indication never arrives. That is all the symptom tells you. It does not tell you whether the encoder failed, the input is mis-wired, or the method simply expects a sensor the machine does not have. A screen or ladder bit that never shows the Z phase proves nothing either; a 50 microsecond pulse does not survive a scan-time observation, as covered in why an input misses a short encoder event.
Causes in order of cheapness #
- No physical home sensor installed.
- Wrong homing method selected in the drive or positioner.
- Proximity input polarity or wiring wrong.
- Reference capture never armed.
- Z pulse too short for the observation point you are using.
No physical home sensor #
Check the machine drawings and the axis itself first. If there is no sensor on the ball screw cylinder, a proximity-assisted homing method has nothing to transition on, and no configuration will make it work. This is the most common root of the reported problem: the intent was to use the encoder Z phase as the "home proximity" signal. Those are two different functions. A proximity signal marks a region of machine travel, once per stroke. The Z phase of an incremental encoder generates exactly one pulse per revolution at a fixed shaft angle, so it repeats dozens of times across a stroke.
An index-only homing method, where the drive documents one, resolves position to a shaft angle but not to a screw revolution. Worked example: a 5 mm pitch ball screw with a directly coupled encoder. Successive Z pulses are 5 mm apart in linear travel. On a 250 mm stroke the axis can stop at 50 different positions that all satisfy "Z phase captured". If the axis starts near the middle this run and near a limit the next, index-only homing lands a whole number of revolutions apart. Decide: if the machine needs the same absolute slot every time, install a home sensor and use a sensor-plus-index method. If the axis always starts from a constrained end and a revolution of ambiguity is tolerable, an index-only method the drive documents can work.
Wrong homing method selected #
Read the active homing method from the drive or positioner and compare it with the sequence diagram in that drive's manual. Servo manuals, such as the MR-JE amplifier instruction set, describe sensor homing types that use the front edge of the proximity dog and then set the reference at the Z phase just before or after the dog edge. If the configured method is that type and there is no dog, the search creeps forever waiting for the transition. If the method is a documented index-only type and the machine accepts the ambiguity, the fix is elsewhere in this list. Related reading: homing with a reference sensor on an absolute axis and homing without a proximity switch.
Confirming check: the drive's homing status or sequence-step monitor. Most servo drives expose a step indicator for the homing sequence. A drive stuck in the "wait for proximity" step with a sensor present points to cause 3; a drive past that step but not completing points to causes 4 or 5.
Proximity input polarity or wiring #
With a sensor fitted, read the home input state outside and inside the sensing region. It must change state at the dog and return after it. A state that never changes means wiring, supply, input assignment or NPN-versus-PNP mismatch; the polarity mismatch case is covered in why a PNP sensor does not fit an active-low input. Also check that the input is assigned as the homing proximity input in the drive, not merely wired to a spare terminal. A sensor that works but is not the configured home input is indistinguishable from no sensor.
Confirming check: jog the axis slowly through the dog while watching the drive's home-input monitor bit, not the physical sensor LED. The drive must see the transition.
Capture not armed, or pulse too short for your observation #
If the drive sees the dog and still never captures, read the latched capture status in the drive monitor, not a PLC contact or a meter. The drive captures the Z phase inside its feedback loop at encoder resolution; external points sample far slower. If the latch never sets, either the homing method in use does not consume the Z phase, or the capture stage was never armed by the sequence.
A worked example for the timing question: homing creep speed of 100 rpm on the 5 mm pitch screw gives 100 revolutions per minute, or 1.667 revolutions per second, so the Z pulse repeats every 600 ms and the linear spacing between capture opportunities is 5 mm. Any drive capture logic resolves that easily. The Z pulse width itself depends on the encoder's duty specification in its datasheet; take it from the datasheet of the exact encoder rather than assuming a value. The pulse is never too short for the drive's own capture, only for a scan-time observer, which is why the ladder bit is the wrong instrument.
The fix and the decision #
Record the current homing settings, then apply the branch you confirmed: fit and configure a home sensor with a proximity-then-index method when the machine needs repeatable absolute zero; use a documented index-only method only when a whole screw revolution of ambiguity is acceptable and the start position is constrained. Size the dog for the homing speed: at 8.33 mm/s linear creep speed (the worked example's 100 rpm on 5 mm pitch), a 5 mm dog gives roughly 600 ms of transition, far longer than any control cycle. After the change, run the search once and confirm the drive's sequence-step monitor walks dog transition, Z capture, complete, in that order. One safety note: keep clear of the axis during any first homing run after a configuration change, since a wrong direction or missing dog can run the axis into its mechanical stop.
Questions asked
Can I home an incremental encoder axis using only the Z phase?
Only if your drive documents an index-only homing method and your machine can tolerate whole-revolution ambiguity. On a 5 mm pitch ball screw, every Z pulse is one screw revolution apart, so starting in different revolutions lands on different linear positions. That is acceptable for a gripper that clamps and re-references, and unacceptable for a machine that must return to the same absolute slot. A proximity sensor removes that ambiguity.
How wide should the home proximity dog be?
Rule of thumb, not a standard: make the dog long enough that the axis travels through it for at least 20 control cycles at homing speed. At 8.33 mm/s creep speed on the worked example, a 5 mm dog gives about 600 ms of transition, hundreds of cycles on a 1 ms drive loop, so detection is certain. If your creep speed is ten times higher, use a proportionally longer dog or slower homing speed.
Why does the Z signal show on a meter but the drive still misses it?
A multimeter or an ordinary ladder contact samples far slower than the drive's encoder electronics. The drive captures the Z phase inside its feedback loop whether or not any external point shows it. Read the drive's latched capture or homing-status monitor instead; if that latch never sets, the capture was not armed or the homing method does not use the Z phase, not that the encoder failed.