Troubleshooting

Why conveyor tracking stays at null speed with green LEDs

Sensors, encoders and machine vision on the machine Published 9 min read By AutomateDirectUSA engineering team

Short answer

Green MS, NS, Comm and HL T LEDs only prove the boards and DeviceNet talk; c1NullSpeed held at 1 says the tracking module counts no encoder transitions. Check the pulse path in order: encoder rotation, supply, output levels, then the module terminals. The frequency inverter does not need to connect just to measure belt position.

On this page
  1. Why does POS1 of CNV1 stay put while the belt runs?
  2. What does c1NullSpeed stuck at 1 actually mean?
  3. Do green MS, NS, Comm and HL T LEDs prove the encoder is working?
  4. Do I have to connect the frequency inverter to the robot?
  5. What do I check first when c1NullSpeed never clears?
  6. How do I prove pulses reach the tracking module terminals?
  7. When is it scaling and mapping instead of wiring?
  8. How do I verify the fix before trusting tracking?
  9. Questions asked

Your LEDs are telling the truth, and they are not the fault. With MS and NS green on the DSQC 377B tracking board and the DSGC 652 I/O board, and Comm and HL T green on the DeviceNet path through the sst-dn3-pci-1 card, every module and the network itself are communicating. CNV1.POS1 frozen while the belt runs, with c1NullSpeed permanently at 1, is the tracking module reporting that it has counted no encoder transitions: zero measured belt speed, not a scaling or robot-side problem. Work the pulse path boundary by boundary — prove the encoder turns with the belt, prove it is powered, prove its outputs switch, then prove the same pulses arrive at the module terminals — and repair the first boundary where the signal disappears. The short answer to the question behind the symptom: no, the frequency inverter does not need to talk to the robot for tracking to measure position.

Why does POS1 of CNV1 stay put while the belt runs? #

POS1 stays fixed because the tracking path sees zero conveyor motion: c1NullSpeed held at 1 is the module's report that no valid encoder transitions have arrived, so there is no measured speed to accumulate into position.

The chain the position depends on is short. Belt motion turns the encoder shaft, the encoder emits electrical transitions on its output channels, the wiring carries them to the tracking board's encoder connections, the board counts them, applies the configured distance per count, and publishes the result as CNV1.POS1 in the Jogging view on the Flex Pendant. A break anywhere before the counting step — a shaft that never turns, a missing supply, a dead output stage, a broken conductor, an input mapped to the wrong terminals — leaves POS1 exactly where it was while every status LED stays green. That is why this symptom reads like a configuration fault but is usually electrical or mechanical.

What does c1NullSpeed stuck at 1 actually mean? #

c1NullSpeed at 1 is the module stating that its measured conveyor speed is zero, and the cheapest reading is that no valid transitions are being counted: causes range from a stationary encoder shaft through a dead output stage or broken conductor to an input mapped to the wrong terminals.

Treat c1DReady toggling between 0 and 1 as consistent with that same picture rather than as a second fault. The module is powered, visible in the I/O system and communicating; what it never receives is the pulse stream it needs to settle and start counting, so chase the toggling only after pulses are proven. Clear the trivial case first, too: confirm the belt section the encoder is driven from actually moves while you jog. A measuring wheel spinning without grip, or an encoder driven from an idle section of the line, produces the same all-green stillness.

Do green MS, NS, Comm and HL T LEDs prove the encoder is working? #

No — those green LEDs prove only that the tracking board, the I/O board and the DeviceNet link are communicating without a network fault; they carry no information about the encoder's supply, rotation, output levels or wiring.

Nothing on the network side depends on the pulse wires, so a completely dead encoder leaves every one of those LEDs green. The healthy picture is exactly what makes this symptom misleading: it invites a search through robot programs and configuration while the fault sits on a terminal block. Read the LEDs once as confirmation that the network and modules are fine, then diagnose the pulse path on its own terms.

Do I have to connect the frequency inverter to the robot? #

No — measuring belt position needs nothing but valid encoder pulses, so the robot tracks from the counting module alone and a manually started drive is enough for position tracking.

A drive connection changes who commands the conveyor, not where the conveyor is. Add one only when the application needs the robot to start and stop the drive, hand it a speed reference, gate motion on drive permissives, or monitor drive faults. For a line of unsorted parts where an operator or a separate control starts the belt and the robot only observes and tracks, leave the inverter under its existing control and spend the effort on the pulse path.

What do I check first when c1NullSpeed never clears? #

Work from the cheapest check to the dearest and stop at the first boundary where the signal disappears: encoder rotation, encoder supply, output levels at the encoder, the same levels at the module terminals, then channel assignment and mapping.

  1. Encoder rotation. Mark the shaft or coupling, jog the belt briefly and confirm the mark turns with the belt. Confirming check: a mark that stands still while the belt moves means a loose set screw, a slipping coupling or a measuring wheel that has lost grip. If the coupling between the drive shaft and the encoder is worn or slipping and re-clamping it is not worth it, a matched flexible shaft coupling sized for those two shafts is the replacement part.

  2. Encoder supply at its terminals. Measure polarity and level under operating conditions against the wiring plan, and feed the encoder from the connection the manual assigns — the manufacturer's conveyor tracking application manual documents an encoder power output on each encoder connection (X11 through X14), so an encoder hanging off an unrelated auxiliary output is a wiring deviation worth questioning. For what the supply pair must deliver on a 24 V incremental encoder, see HTL incremental encoder supply terminals.

  3. Output levels at the encoder. Turn the shaft slowly — by hand where the mechanical arrangement allows it, or with the belt at its lowest speed — and watch each required output channel with an oscilloscope or frequency counter. Confirming check: every channel toggles cleanly, and the measured high and low levels match the interface specification of the installed encoder, because a 5 V differential output does not reliably drive an input that switches at 24 V logic levels and probing a differential pair single-ended can show a misleading mid-rail. For channel-by-channel level matching at a receiver, see TTL quadrature encoder wiring.

  4. The same pulses at the module terminals. Repeat the measurement with the probe at the DSQC 377B encoder connections while the belt moves. Confirming check: pulses present at the encoder but absent at the module localize the fault to a conductor, connector, missing common or shield problem; absent at both ends points back to the encoder or its supply.

  5. Channel assignment and phase. Compare the physical channels with the configured input assignment and confirm both quadrature channels toggle with their phase offset preserved. Confirming check: a swapped or single-channel connection leaves the counter without usable counts or without direction, which reproduces this symptom exactly.

  6. Mapping and scaling. Only once pulses are proven at the module terminals does the conveyor object's association, direction and distance per count deserve attention — that is the next boundary, not the first.

How do I prove pulses reach the tracking module terminals? #

Measure the identical channels twice, once at the encoder and once at the tracking board's encoder connections, while the belt runs; the difference between those two readings localizes the break to the cable, the connector or the module input.

Keep one probe and one set of channels for both measurements so the comparison is honest, and where the interface is differential, measure across the pair rather than from one conductor to an arbitrary reference. Before opening connectors or probing inside enclosures, lock and tag the conveyor drive out; measure live only at terminal points designed for access. The decisive functional test is a raw-count watch: jog the belt very slowly or generate pulses by slow hand rotation and look for the raw count, the pulse state or the null-speed state to respond before you evaluate POS1 at all. When you want the same walk-through with terminal references, the step-by-step POS1 troubleshooting guide for this tracking board follows this boundary order in detail.

When is it scaling and mapping instead of wiring? #

Only after valid pulses are proven at the module terminals: a wrong distance-per-count value moves POS1 by the wrong distance and a sign error reverses it, but neither can hold the raw count at zero with c1NullSpeed stuck at 1.

So while the count is dead, keep scaling out of the picture. Once pulses flow, confirm that the conveyor object CNV1 is associated with the tracking device Qtrack1, that direction follows the belt's real travel, and that distance per count comes from a measured belt travel rather than a nameplate wheel diameter, because wear and mount compliance move that number. Two neighbouring symptoms stay outside this article's lane: when POS1 moves but the tracked speed looks wrong as the belt speeds up or slows down, read conveyor tracking ignoring encoder speed changes; and when pulses, scaling and direction are all right but tracking accuracy differs between robots, the difference is loop tuning — why KV factor varies between axis loops explains why identical tracking behaves differently on two machines.

How do I verify the fix before trusting tracking? #

Verify in four passes: belt stopped, POS1 stable; belt creeping, raw count moves and the null-speed state clears; belt stopped again, position freezes and the zero-speed state returns; then a tape-measured belt travel compared against the POS1 change.

Worked example. Mark 500 mm of belt surface against a fixed frame point, run the belt over that measured distance, and read the raw count change. If the counter advances 10,000 counts over that travel, the distance per count for this machine is 500 mm / 10,000 counts = 0.05 mm per count. Enter that scale in the conveyor configuration, and a part detected 250 mm ahead of the pick position corresponds to 250 mm / 0.05 mm per count = 5,000 counts of lead. If POS1 advances the wrong distance for the same tape-measured travel, recompute from the measurement instead of nudging the value by eye; if it advances backward, correct the direction setting first and re-verify. These are calculated example figures for these inputs, not measured ratings of any board.

On the stopped-belt pass, a POS1 that creeps with no belt motion means noise transitions or a wandering mechanical link — fix shielding, grounding or the coupling before trusting tracking.

Decision, in one line: green LEDs with a frozen POS1 is a pulse-path fault until a measurement proves otherwise — repair the first boundary where the measured signal disappears, in the order rotation, supply, encoder output, cable and connectors, input mapping — and connect the inverter to the robot only when the robot must command or supervise the drive, never merely to measure position.

Questions asked

Can I test the tracking board without running the conveyor?

Yes, and it is often the fastest proof. Turn the encoder shaft slowly by hand where the mechanical arrangement allows it, or jog the belt at its lowest speed, and watch the raw count and the null-speed state in the I/O view. A slow hand-generated pulse stream proves the electrical path end to end: the raw count should advance while you turn and freeze the instant you stop. If the supply measures correct and slow turning still produces nothing, suspect output levels and wiring rather than belt speed.

Why does a multimeter show a steady mid-range voltage on an encoder channel?

Because a meter averages the signal it samples. A quadrature channel idles near half duty, so a healthy pulse train reads roughly half the supply voltage, a value that looks exactly like a stuck output. That reading proves neither health nor failure. Use a frequency counter, which shows transitions, or an oscilloscope, which shows clean edges between the specified high and low levels. Keep the multimeter for the supply pins, where a steady reading is exactly what a healthy feed should show.

What should the raw count do when the belt reverses?

It must run the other way. Reverse the belt and the raw count has to decrement through the same scale, because direction information lives in the phase offset between the two quadrature channels. If the count keeps rising while the belt reverses, the receiver is getting count edges without direction, usually one channel missing or two channels arriving out of phase, and tracking will trigger at the wrong position even when speeds look right. Fix the channel pair before trusting any pick.

Can I feed the encoder from an auxiliary 24 V supply instead of the tracking board?

Prefer the connection the manual assigns. The tracking board's encoder connections provide a dedicated encoder power output intended to feed the encoder wired to them, referenced to the same common as the pulse inputs. An unrelated auxiliary output may sit at a different level or float its 0 V relative to the pulse common, which corrupts the transitions without tripping any LED. If the installation truly requires a separate supply, tie its 0 V to the pulse common at one point and verify the voltage against the encoder datasheet before first power-up.

Keep reading

  • Troubleshooting

    Why Robot Conveyor Tracking Ignores Encoder Speed Changes

    A conveyor-tracking motion that ignores encoder speed has one of three faults: the controller receives no changing count, the count converts to the wrong belt distance, or the executed motion never activates the conveyor reference. Confirm the count changes with belt speed first, calibrate distance per count second, verify tracking activation third — in that order. Speed and acceleration settings cannot supply a missing reference.

    Sensors, encoders and machine vision on the machine

  • How-to

    Counting Encoder Pulses on a PLC Without Losing Position

    Count encoder pulses with a hardware high-speed counter input wired for quadrature, never with a count instruction in the scan. At 214 rpm and 75 pulses per revolution the encoder delivers 267.5 pulses per second, one every 3.7 ms, while a 10 ms scan cannot guarantee seeing even one in three. Zero the counter at a reference switch and treat every target as counts from that switch.

    Sensors, encoders and machine vision on the machine

  • How-to

    How to Track Conveyor Parts With an Encoder and a FIFO Buffer

    Load one FIFO element per slot of encoder-measured belt travel and read any element by index arithmetic instead of shifting data down a table. Worst-case registration error equals one slot length, and update cost is constant whether the block holds 100 or 100,000 elements. Size the slot from placement tolerance and the block from sensor-to-actuator distance plus 10 to 20 percent margin.