Troubleshooting
Why CVQUE instruction is missing from XRC conveyor tracking
Short answer
On XRC, conveyor tracking with shift function is an enabled option, not a parameter. Until the option record is written by the manufacturer's service side, the pendant builds its instruction list without CVQUE and its menu without the Conveyor Tracking List screen, whatever FD106 says. Verify the cheap causes, then book the maintenance-mode enable with the ROM matched to your installed system software.

On this page
CVQUE is missing because conveyor tracking with shift function on an XRC controller is an enabled option, not a parameter setting. The option record has to be written into the controller's system configuration by the manufacturer's service side, in maintenance mode, together with the application ROM that matches the installed system software. Until that record exists, the pendant builds its INFORM instruction list without CVQUE and its ROBOT menu tree without the Conveyor Tracking List screen — whatever FD106 is set to, and however many times the system software is reloaded. The UP6 case worked out below proves the point: four software loads, four matching CNVYR.ROM files and eight parameter edits later, the instruction count was still zero. Run the cheap checks first, then book the enable.
Symptoms that point at the option record #
One XRC handling cell showed all five of these together:
- No CVQUE anywhere in the INFORM instruction list, with the full language set showing.
- The ROBOT menu carries the plain Conveyor screen but no Conveyor Tracking List screen.
- Basic conveyor tracking runs correctly, so the encoder and the boards are alive.
- FD106 set to 1 is accepted and stored, and nothing new appears, at this power-up or the next.
- Two controllers show the identical absence: an XRC on a UP6 and an XRC SV3.
Tracking that works while the instruction stays absent is the signature: wiring faults kill tracking itself, not one instruction.
Rule out the cheap causes first #
Work down this list in order; each item is cheaper to check than the one after it, and each has a check that closes it.
- Access level. Instructions can be hidden below MANAGEMENT access. Re-open the INFORM list at MANAGEMENT (Yaskawa mode in this cell) and look again.
- Language level. A subset INFORM language hides advanced instructions. Switch to the expanded set, then confirm a known advanced instruction displays before concluding CVQUE is truly absent.
- ROM match. Each system software load must carry its own matching CNVYR.ROM. This cell loaded four pairs — X5.29A (US-S) -00, X5.2FA (US_ES) -00, X6.57A (U.S.) -00 and X5.70A (US-S) -15, each with its own ROM — and basic tracking came up every time, so the pairs were matched.
- Encoder counting. Jog the belt and watch the conveyor pulse value: it must increase steadily and reverse sign on reverse travel. An open channel that still counts but loses direction is the classic fault, and wiring the encoder to the controller covers the terminals and channels to meter.
- Conveyor scale. Mark a known belt travel and compare it with the distance the controller displays. A scale that is off by a constant factor still counts and still tracks, and it is one reason conveyor tracking drifts further from each box — fix it before blaming software for anything.
If all five pass and CVQUE is still missing, the cause is none of these.
Why no parameter or reflash can unlock it #
On XRC, the pendant builds its INFORM instruction table and its ROBOT menu tree from two things at startup: the system software and the controller's option records. FD106 exists precisely for this function — its documented meaning is conveyor tracking with shift function, enabled at 1 — but FD-class parameters configure a function whose option record is already present. They do not create the record. With the record clear, CVQUE is not in the instruction table for any language level to reveal, and the Conveyor Tracking List screen is never built, which is why the plain Conveyor screen can sit next to a function that technically exists in the loaded software.
Reloading system software cannot change this, because every load rebuilds the same tables from the same absent record — that is why four different loads behaved identically. The enable is written at the factory level and tied to the controller serial number, so it is not reachable as a user parameter. The documented shape of the function confirms it is an option: the Motoman robot and controller documentation list gives XRC conveyor tracking with shift functions its own instruction manual — document 148123-1, covering UP and SKX-series robots — and an option ships as a manual plus an enable record, not as a parameter appendix entry.
The enable record is also exactly the kind of item beyond boards and encoders that a conveyor tracking retrofit needs beyond an encoder: hardware, matched software and licensed enable are three separate deliverables, and buying more of the first does not deliver the third. The same split between a licensed enable and an ordinary setting shows up away from robots too — a software activation message such as the RSLogix 500 activation pop-up clears through its documented activation step, not by re-editing configuration.
Working the UP6 case: four software loads, no CVQUE #
Inputs, read off the cell itself:
- Manipulator and controllers: UP6 on XRC; a second XRC SV3 shows the same absence.
- Boards fitted: JANCD-XSL02 conveyor encoder interface, JANCD-XCP02B CPU.
- Software pairs loaded, each system software with its own matching CNVYR.ROM: X5.29A (US-S) -00, X5.2FA (US_ES) -00, X6.57A (U.S.) -00, X5.70A (US-S) -15 — 4 pairs.
- Parameters edited: FD106 plus FD20, FD113, FD116, MFXG4, S2C324, S4C515 and S2C157 — 8 parameters.
- Access settings: Yaskawa mode and extended language both on.
- Observations: basic tracking runs on 4 of 4 pairs; CVQUE appears on 0 of 4; the Conveyor Tracking List screen appears on 0 of 4.
Rule in words: the pendant can only show an instruction that the loaded software's table contains, and that table is built from system software plus option records — so a matched pair that runs basic tracking proves the software layer, and the only layer still able to hide CVQUE is the record.
Arithmetic:
- Layers the function needs: 3 — hardware, matched software pair, option record.
- Layers proven good: hardware, because tracking runs and the encoder counts = 1; matched software pair, because 4 loads with 4 matched ROMs gave an identical result = 2.
- Layers missing: 3 - 2 = 1.
- Parameter edits made: 8. Changes produced: 0. Instruction appearances across 4 loads: 0.
Result: every variable the cell can change on its own — 4 software loads, 4 ROM files, 8 parameters — has been varied, and the instruction count never left zero. The one constant through all trials is the absent option record.
Decision: when basic tracking runs on a matched software pair and CVQUE is still absent, the software layer is closed — book the enable instead of loading number five, and leave application-specific branches such as X7.13A and X7.34A alone.
Booking the enable and what to send #
Before anyone enters maintenance mode, take a complete backup of the controller's parameters, jobs and files from the pendant. That backup is the rollback for the visit, and after any system software work the restore must come from a backup taken on the same revision the controller now runs — mixing revisions across a restore leaves the parameter map inconsistent with the loaded application.
Hand the service engineer four things so the visit is one trip: the controller serial number and manipulator model, the full system software version string from the pendant's system information screen, the board list with the connector the encoder lands on, and a one-line application description — picking from a moving belt, for a handling cell. Ask explicitly for the shift-function enable on the installed handling branch.
One safety note: run the first synchronized tests as a commissioning run under the cell's existing safeguarding and its robot risk assessment, at reduced speed with test parts in the queue — a newly queue-bound axis moves differently from the basic-tracking version.
Confirm the enable took #
After the enable write and a restart, all five of these must be true:
- CVQUE is present in the INFORM instruction list.
- A Conveyor Tracking List screen appears in the ROBOT menu, separate from the plain Conveyor screen.
- FD106 still reads 1 after a power cycle.
- The conveyor condition file is editable.
- End to end, a sensor detect queues an entry, the robot tracks that part, and the entry clears after the pick.
If any one of the five is missing, the write did not take — call the representative back instead of editing parameters again.
With CVQUE in hand, the function completes the tracking loop: the detect event loads the part's encoder position into the tracking queue, the robot claims that entry when it starts the pick, and the entry leaves the queue when the part is released. The shift applied to each move comes from that queued position through the conveyor scale and direction vector, so taught paths stay in the stationary frame while the robot follows the moving part.
Questions asked
Is the encoder hardware different for conveyor tracking with shift function?
No. The conveyor encoder interface board and its wiring serve both the basic and the shift-function variant, so adding or swapping boards cannot make CVQUE appear. If basic tracking counts and tracks correctly, the hardware layer is finished; the shift variant adds the option record and a matching application ROM on top of hardware you already have.
Can I write the option record myself in maintenance mode?
Maintenance mode is reachable from the pendant, but the shift-function enable needs the option record data and the matched option ROM, which the service side brings to the visit. System configuration edits without them leave the record absent, and repeated reflashes across revisions can leave the parameter map inconsistent with the loaded application, so keep same-revision backups for the restore.
Can a security or language setting hide the CVQUE instruction?
Those settings can filter the INFORM list, which is why they are the first checks: instructions can be hidden by a lower access level and by a subset language. But a filter only hides an instruction the list already contains, so if extended language and management access are already set and CVQUE is still absent, the option record is the cause.
Does basic conveyor tracking stop while I wait for the option enable?
No. Basic tracking keeps running with the same jobs, the same encoder and the same conveyor condition data. After the enable, re-verify the encoder scaling and run a tracked pick before production, because the shift function binds the robot to queued part positions rather than to the belt condition alone.
Are the X7.13A or X7.34A loads the way to get the shift function?
No. Those are application-specific system software branches built around paint packages. The branch decides which application instruction set the controller carries, not whether a licensed option is unlocked, and putting a paint branch on a handling manipulator risks a mismatched axis and application configuration. Ask for the enable on the handling branch you already run.