Troubleshooting
Why Max Travel Range Can Exceed an Absolute Encoder Range
Short answer
The configured Max. travel range is wider than the absolute encoder's span once the gear ratio converts it to load millimeters: usable absolute revolutions times load travel per load revolution, divided by motor revolutions per load revolution. If that span is below the configured travel, the drive refuses absolute evaluation; enter the real stroke or change the feedback.

On this page
The drive is not doubting your encoder. Absolute Encoder Evaluation is refused because the configured Max. travel range — 10000 mm in this setup — is wider than the position span the encoder can identify uniquely once the gear ratio converts motor revolutions into load millimeters. The check is one comparison: usable absolute revolutions × load travel per load revolution ÷ gear ratio. If the result is smaller than the configured travel, the drive cannot guarantee that one encoder reading means one load position, so it declines absolute evaluation. Read the encoder's span on the Encoder 1 /motor encoder page in ctrlX DRIVE Engineering, convert it through the transmission, and either enter a travel range the span actually covers — in most cases the machine's real stroke — or change the feedback arrangement. Forcing the evaluation does not widen the span.
What the drive compares when it refuses absolute evaluation #
An absolute encoder reports position without a reference run, but only inside its absolute range: a single-turn encoder distinguishes positions within one revolution of the motor shaft, a multi-turn encoder across many revolutions. The drive shows the multi-turn property in the absolute position range of Encoder 1 /motor encoder whenever that range is greater than 1 U.
The machine, meanwhile, commands position at the load in millimeters, and the encoder measures the motor shaft in revolutions. The comparison therefore runs through the whole transmission chain: gearbox first, then feed mechanism. The drive needs the entire configured position interval to fit inside the absolute span the encoder can guarantee at the load. When Max. travel range is wider than that converted span, absolute evaluation is refused.
The refusal is a configuration comparison, not a verdict on the encoder. A perfectly healthy encoder is refused whenever the configured range outgrows its span — exactly what happens when a travel range is entered as generous headroom or a high reduction multiplies the motor revolutions the encoder must tell apart.
The load-side span in one formula #
For an encoder mounted on the motor shaft, a fixed-ratio gearbox and a linear feed mechanism, the span the encoder can identify at the load is:
Span [mm] = N [motor revolutions] × L [mm of load travel per load revolution] ÷ G [motor revolutions per load revolution]
- N — usable absolute range of the motor encoder, in revolutions; read it from the absolute position range display.
- G — motor revolutions per load revolution; take it from the gearbox datasheet and check it against the configured transmission.
- L — load travel per load revolution; take it from the feed mechanism: screw lead, pinion circumference on a rack, or pulley circumference on a belt-driven feed.
Watch the ratio direction. G is motor revolutions per load revolution; entering the reciprocal inflates or deflates the calculated span by the ratio squared — a factor of 400 at a 20:1 gearbox. And check the units the drive reports: a range already expressed in load-side millimeters must not be divided by the gear ratio a second time.
The formula assumes the encoder sees the motor shaft. If the encoder sits somewhere else — behind the reduction, or directly on the moving load — use the transmission between that encoder and the load instead, the situation covered in mounting a motor encoder behind a belt reduction.
Checking a 10000 mm travel range behind a 20:1 reduction #
Inputs for this example:
- Max. travel range: 10000 mm, the configured value in this case.
- G = 20 motor revolutions per load revolution — an example ratio for this check, not a value read from this machine; take yours from the gearbox datasheet.
- L = 10 mm of load travel per load revolution — an example feed constant, a 10 mm lead feed screw; take yours from the mechanism drawing.
- N = 1 revolution for a single-turn encoder, or 4096 revolutions as an example multi-turn value — the real figure comes from the absolute position range display.
The rule in words: multiply the encoder's usable absolute revolutions by the load travel per load revolution, then divide by the motor revolutions per load revolution.
- Single-turn encoder: 1 × 10 ÷ 20 = 0.5 mm of unique load travel.
- Example multi-turn encoder: 4096 × 10 ÷ 20 = 2048 mm.
- Absolute revolutions the configured range would need at these inputs: 10000 × 20 ÷ 10 = 20000 revolutions.
Result: both spans fall short of the configured 10000 mm — the single-turn span by a factor of 20000, the multi-turn example by roughly five.
Decision: with these inputs the refusal is correct and no setting trick changes it. A single-turn encoder covers half a millimeter, so absolute evaluation can never carry this range. The example multi-turn encoder covers 2048 mm, so a Max. travel range of at most 2048 mm is the largest value these inputs support — and it should only be that wide if the real stroke needs it. Reaching the configured range through this reduction and lead screw would take 20000 absolute revolutions, more than ordinary motor encoders provide, so the practical fix is a shorter range or a different measurement chain, covered below. Force absolute encoder evaluation suppresses the refusal, not the ambiguity underneath it.
Checks in order, cheapest first #
- Read the encoder's span. Open the Encoder 1 /motor encoder page in ctrlX DRIVE Engineering and record the absolute position range with its units. Confirming check: convert it with the formula above; if the converted span is smaller than Max. travel range, the message is explained and the encoder is not implicated.
- Check the transmission ratio entry. Compare the configured ratio's value and direction with the gearbox datasheet. Confirming check: an inverted or mistyped entry moves the calculated span by the ratio squared, so correcting it can clear the refusal without touching the travel range.
- Check the feed constant. Compare L with the mechanism drawing — screw lead, pinion circumference, pulley circumference. Confirming check: turn the load screw one full revolution by hand and measure the travel; it must match L.
- Check the configured range against the real stroke. Read the actual travel envelope from the machine drawing and the installed stops. Confirming check: a range far beyond the physical stroke is a configuration allowance, and trimming it to the real stroke removes a conflict the machine never needed.
- If the span covers the range and the refusal persists, look elsewhere. Confirming check: verify that the selected feedback type matches the installed encoder and read the encoder diagnostics; a wrong selection or a signal fault needs a different repair than a range edit.
Fixing the range or the measurement chain #
Two legitimate outcomes exist, and the numbers pick between them.
If the configured range was headroom, enter the real stroke. The value must both cover the application and fit the converted span. Max. travel range also bounds where the drive believes the axis may move, so verify the corrected interval against the machine's risk assessment and guarding before the axis runs again.
If the stroke genuinely exceeds any motor-side span, change where position is measured: a load-side absolute linear scale sized to the full stroke, a motor encoder with a higher absolute revolution count, or incremental evaluation with a reference run at startup — the last route is covered in homing an absolute encoder axis to a reference sensor. More reduction is never the fix: it only shrinks the span further.
Proving position agreement after the change #
- Apply the corrected configuration through the documented commissioning process and re-read the encoder status: the refusal should be gone and the diagnostics clear.
- Power the system down and up again; the absolute position must return without a reference run and match a known physical mark.
- Compare displayed position with known physical positions across the whole stroke, including close to both ends, where the span boundary sits. A jump or a repeated coordinate near an end means the configured interval still crosses the edge of the span.
- Check direction and displacement scaling during a controlled move before releasing the axis to production.
The decision, restated: the refusal is arithmetic, not a fault. Make the configured travel fit the span the encoder can guarantee at the load, or measure position where the span is.
Questions asked
Does Force absolute encoder evaluation fix the range conflict?
No. Bosch Rexroth's ctrlX DRIVE documentation places that option in the Expert view of the encoder dialog, and it only tells the drive to treat the feedback as absolute despite the failed range check. It adds no absolute revolutions, so one encoder reading can still correspond to more than one load position. Correct the travel range or the measurement chain first, and treat forcing as a deliberate, documented commissioning decision.
Where does the encoder's absolute range appear in ctrlX DRIVE Engineering?
On the Encoder 1 /motor encoder page. The absolute position range is displayed there, and the multi-turn property appears with it whenever the range is greater than 1 U. U counts revolutions of the motor shaft, so 1 U marks a single-turn encoder and a larger value marks a multi-turn one. Use that revolution count as the N value in the span formula.
Which changes buy more load-side absolute span?
Three levers, and the formula gives each a direction. A motor encoder with more absolute revolutions multiplies the span. A feed mechanism with more travel per load revolution, such as a higher-lead screw or a larger pinion, multiplies it too. Less reduction between encoder and load enlarges the span, while more reduction divides it down, which is why high-ratio axes hit this refusal first.