Troubleshooting
Why resolver mounting angle faults an induction motor drive
Short answer
An induction motor under field-oriented control uses its resolver for speed and flux estimation, not for permanent-magnet commutation, so the drive must run at any resolver mounting angle. When encoder amplitude and load encoder faults appear only at certain angles, one channel is going invalid at the receiver: fix the channel, the excitation or the pole-count and motor-type settings instead of setting the angle by trial and error.

On this page
- Does an induction motor need its resolver aligned to the shaft keyway?
- Why would the resolver's mounting angle trigger faults then?
- What do faults 7032 and 6057 actually report?
- How do you check the resolver signals across a full revolution?
- Which settings must match before you touch the mounting angle?
- What order do you fix things in, and when are you done?
- Questions asked
Your induction motor does not need its resolver phased to the shaft keyway. Field-oriented control of an asynchronous machine estimates the rotor-flux angle and compensates slip, so a constant mounting offset changes only the reported absolute shaft angle, never the speed derived from it. When 7032 (encoder signal amplitude too small) and 6057 (position loop: load encoder error) appear only at certain mounting angles, one sine or cosine channel is going invalid at those shaft angles. The angle you found by trial and error is masking a signal or configuration defect; fix that defect, and the drive runs at any mounting angle.
Does an induction motor need its resolver aligned to the shaft keyway? #
No. An induction motor under field-oriented control has no permanent-magnet rotor axis for the resolver zero to match: the controller estimates the rotor-flux angle and accounts for slip, so commutation phasing by mechanical adjustment does not apply. That procedure, described in the drive's online help, belongs to synchronous machines — the rules and limits for those are covered in swapping a servo resolver for an encoder: commutation rules.
A constant resolver offset shifts the reported absolute shaft angle and nothing else. Speed is the rate of change of that angle, so it is untouched. If your machine needs a shaft-position reference for homing or coordinates, you establish it with a homing routine or a position offset in the axis configuration — never by mechanical alignment to a keyway.
Why would the resolver's mounting angle trigger faults then? #
Because the alarm is about signal amplitude, not magnetic alignment: at some shaft angles one channel is naturally zero, and if the other channel is weak at the receiver, the monitored amplitude dips below the drive's valid-signal threshold exactly there.
A resolver is a rotating transformer. The drive excites the primary and reads two amplitude-modulated secondaries; after demodulation an ideal pair gives S = A sin θ and C = A cos θ, where θ is the resolver electrical angle and A the common signal amplitude. The magnitude R = √(S² + C²) equals A at every angle. One channel crossing zero is normal; a collapse of the combined magnitude is not. An angle-dependent amplitude fault therefore means the received pair no longer behaves like that ideal, and the causes rank by how cheap they are to check:
| Order | Likely cause | Confirming check |
|---|---|---|
| 1 | Motor type set to synchronous | Read the motor-type entry in the axis configuration |
| 2 | Fault raised on the wrong feedback path | Read which input raised 7032, and the load-encoder assignment behind 6057 |
| 3 | Wrong resolver pole count entry | Compare the entry with the resolver datasheet and the displayed speed |
| 4 | Excitation low at the resolver | Measure the excitation voltage at the resolver terminals |
| 5 | Weak sine or cosine channel | Differential sweep at the drive connector through the faulting angles |
What do faults 7032 and 6057 actually report? #
They are two different complaints: 7032 is the amplitude monitor of a feedback input tripping, and 6057 names the load-feedback path, which is not automatically the motor resolver.
| Fault | What it names | Where to confirm |
|---|---|---|
| 7032 Encoder: Incremental signal amplitude too small | The amplitude monitor of a feedback input sees a signal under its valid threshold; the drive groups resolver inputs under its encoder diagnostics | The diagnostic history: which feedback channel, at what shaft angle |
| 6057 Position loop controller: Load encoder error | The configured load-feedback path, not automatically the physical motor resolver | The axis configuration: the load-encoder assignment |
The wording "incremental signal" in 7032 is a reason to identify the actual reporting channel before reading it as a resolver measurement. Trace the physical resolver to its configured motor-feedback input, and inspect the load-encoder assignment separately.
How do you check the resolver signals across a full revolution? #
Measure both channels differentially at the drive's feedback connector while the shaft is turned slowly through the angles that produced the alarm, comparing the sine and cosine envelopes against each other and against the excitation. Never loosen the resolver housing or its coupling on an energized axis.
- Save the axis configuration and the diagnostic history. Record which mounting positions faulted and whether the shaft was stationary or turning.
- Inhibit motion and secure the machine, then rotate the shaft by hand where the mechanical design permits it.
- Measure the excitation at the resolver terminals, then both channels differentially at the receiver with probes suited to the interface. A single conductor measured against ground does not show the voltage the differential receiver evaluates.
- Record S and C at intervals, for example every 30 degrees of shaft rotation, and compute R at each point.
Worked example, calculated for these inputs and not a measured result. Suppose the resolver datasheet gives a transformation ratio of 0.5 and the interface excites it with 7 Vrms. The peak amplitude of each channel at the receiver is A = 0.5 × 7 Vrms = 3.5 Vrms, and for a healthy pair:
| Resolver electrical angle | S (Vrms) | C (Vrms) | R = √(S² + C²) (Vrms) |
|---|---|---|---|
| 0° | 0.00 | 3.50 | 3.50 |
| 30° | 1.75 | 3.03 | 3.50 |
| 90° | 3.50 | 0.00 | 3.50 |
Now suppose connector resistance leaves the cosine channel delivering only 2.0 Vrms. At 0°, R = √(0² + 2.0²) = 2.0 Vrms, while at 90°, R = 3.5 Vrms because the healthy sine channel is at its peak. If the interface's documented valid-signal threshold sits between those two figures, the monitor trips near 0° and 180° and passes everywhere else — an angle-dependent fault with waveforms that look smooth on a scope. Take the real threshold from the feedback-interface documentation of your drive.
Which settings must match before you touch the mounting angle? #
Four entries in the axis configuration must match the hardware: the motor type, the resolver pole count, the transformation ratio against the interface input range, and the feedback assignment.
- Motor type. An asynchronous machine needs the induction selection. A synchronous selection makes the controller expect a rotor angle locked to the shaft and changes its whole behavior. Read the entry and compare it with the motor's documentation; do not change it experimentally.
- Resolver pole count. This is the number of resolver electrical cycles each mechanical revolution; a single-speed resolver gives one. A wrong entry scales the reported angle and speed, and no mounting offset can substitute for correcting it.
- Transformation ratio and input range. The received amplitude is the ratio times the excitation, and it must land inside the interface's documented input window; some interfaces require attenuation or filtering of the resolver signals to match their input specifications.
- Excitation. Voltage and frequency must satisfy both the resolver datasheet and the interface documentation at the same time.
- Feedback assignment. Motor feedback and load encoder are separate paths; 6057 lives on the load path, so confirm which physical device is assigned there.
What order do you fix things in, and when are you done? #
Fix in the order of the checks above, one change at a time, and you are done only when the axis runs alarm-free with the resolver back at an arbitrary mounting angle, including the angles that used to fault.
- Correct the motor type if it is wrong, then repeat the same angular test.
- Correct the feedback assignment so each physical device sits on its intended path.
- Enter the resolver pole count and transformation ratio from the datasheets.
- Restore the excitation to the documented voltage and frequency.
- Repair the weak channel — wiring, connector, shield termination — or add the attenuation the interface documentation calls for.
After each change, rerun the identical angular test so the result means something. If a verified-healthy channel still produces angle-dependent faults, the defect is still in the acquisition path: keep measuring and do not accept a sweet-spot mounting angle. When the machine needs a shaft-position reference, enter a position offset in the axis configuration; never remount the resolver to create one.
Questions asked
Does the resolver's electrical zero matter when commissioning an induction motor?
Not as an alignment reference. The drive derives the shaft angle from the sine and cosine signals themselves, and on a multipole resolver the electrical zero repeats several times each revolution, so it cannot mark a unique shaft position anyway. Neither the electrical zero nor the keyway is a commissioning reference on an asynchronous motor; only signal validity and the scaling entries matter.
How do I recognize a wrong resolver pole count entry?
Commanded and displayed speed disagree by a clean factor. Calculated example: with the axis running at a steady 1500 rpm confirmed by a handheld tachometer, a drive monitor showing 3000 rpm means the configured pole count is half the resolver's real value, because the scaling error doubles the derived speed. Correct the entry to the datasheet value; no offset repairs a factor error.
Can the cable run alone cause an angle-dependent amplitude fault?
Yes. The excitation carrier attenuates along the cable and connector resistance, so an amplitude that looks healthy at the resolver terminals can arrive low at the drive, and a channel that is marginal at the receiver dips under the threshold only at the shaft angles where the other channel is zero. Measure at the drive connector, check the shield termination as the drive documentation specifies, and repair the cable rather than re-aiming the housing.