Clearing an Absolute System Down Alarm on a Servo Drive

Sensors, encoders and machine vision on the machine Published 7 min read By AutomateDirectUSA engineering team

Short answer

An absolute system down alarm means the drive lost the absolute encoder's stored position because encoder power dropped entirely. Measure the backup battery first: the common serial-encoder interface trips at 3.1 V on a 3.6 V cell. Fix the battery, run the drive's absolute encoder clear, then re-establish machine position before automatic operation.

On this page
  1. What does an absolute system down alarm really mean?
  2. What do I check first when the alarm appears?
  3. How do I measure the battery voltage the right way?
  4. Can I clear the alarm before fixing the battery?
  5. How do I run the absolute encoder clear?
  6. Does running the clear restore the machine position?
  7. Why does the alarm come back after a power cycle?
  8. When should I suspect the cable, the encoder, or the drive?
  9. Questions asked

An absolute system down alarm means the servo drive has lost the absolute encoder's stored position because every source of encoder power dropped at once: control power and the backup battery together. Fix the power before the data. Measure the backup battery and its connection first, because the widely used serial absolute encoder interface triggers this alarm at a battery voltage of 3.1 V against a 3.6 V nominal cell. Then run the drive's absolute encoder clear from its auxiliary function mode, and re-establish machine position before automatic operation. Panasonic B-series drives report this condition as Alarm 40; other vendors word it differently, but the failure and the remedy are the same.

What does an absolute system down alarm really mean? #

It means the absolute encoder lost power from every source at once, control power and the backup battery, so the position data held in battery-backed memory is invalid, and on Panasonic B-series drives the code is Alarm 40. That family's manual attributes the alarm to all of the encoder's power supplies being down, and its remedy is to connect the battery, then execute an absolute clear. That is the whole failure: the multi-turn count lives in battery-backed memory in the encoder, and when both the drive's encoder supply and the backup cell are absent, the count is gone with it.

Distinguish this from the encoder's other complaints. A status, counter, or overspeed alarm means the encoder is powered and reporting a condition; system down means it went dark. For background on how these systems hold position across power cycles at all, how servo motor absolute encoders are battery-backed covers the scheme.

What do I check first when the alarm appears? #

Measure the backup battery's voltage and inspect its holder and wiring before anything else: loss of encoder power is the documented cause, and the battery is the cheapest thing on the path to rule in or out. The battery limits that matter are published for the Tamagawa serial absolute encoder interface, which many servo encoders speak; that documentation's Table 17-39 gives the values below. Your drive's manual is the authority for your axis, so take the trigger voltage from the exact drive and encoder you have.

Battery parameter (documented for that serial interface) Value
Typical battery voltage 3.6 V
Maximum battery voltage 4.75 V
Alarm trigger voltage 3.1 V

Two decisions follow from that table. A cell reading at or below 3.1 V on this interface is due for replacement before you clear anything. And 4.75 V is a maximum, so never series two 3.6 V cells: 7.2 V is above it.

Work the causes in this order, cheapest first, and confirm each before moving on:

  • Battery holder and wiring. Confirming check: with a meter on the cell, flex the holder and harness; any flicker repairs the connection before it wastes your afternoon.
  • Battery voltage. Confirming check: rest and loaded measurements (next section); at or below the trigger, replace the cell.
  • Encoder cable. Confirming check: pin-to-pin continuity against the wiring page in the drive manual, battery line included.
  • Encoder. Confirming check: a verified battery and cable, but the alarm still returns after a clean clear.
  • Drive. Confirming check: full battery voltage present at the drive's battery input and the alarm persists; the drive's encoder supply or backup input is the suspect.

How do I measure the battery voltage the right way? #

Measure the cell at rest at its own terminals, then again with control power off so the battery alone carries the encoder: a cell that holds its voltage unloaded but collapses under the encoder's microamp backup load is finished. Measure at the cell itself and, if the manual's wiring page shows a battery input at the drive or the encoder connector, there too. A difference between the two readings puts the fault in the harness between them.

The loaded condition is easy to create: control power off is exactly the state the battery exists for, and the alarm at the next power-up is the loaded result. Write the reading and the date in the log when you take it, because a trend catches a slowly sagging cell that a single snapshot misses.

Can I clear the alarm before fixing the battery? #

No: the documented sequence is battery first, absolute clear second, and clearing with a dead or missing cell either fails outright or hands you the same alarm at the next power-up, because the encoder loses backup power again the moment control power drops. A fault reset only acknowledges an alarm; it does nothing about invalid stored data, which is why this condition needs the clear function rather than the reset key. The battery decision gates everything downstream, so make it first.

How do I run the absolute encoder clear? #

Enter the drive's auxiliary function mode and select the absolute encoder clear mode, which on the drive family documented here is exactly where the function lives, then execute it with the battery verified, following the key sequence in that manual. The sequence, in order:

  1. Verify battery voltage and connection; replace the cell if it sits at or below the trigger voltage.
  2. Put the machine in a safe state with the servo off and control power on.
  3. In the auxiliary function mode, select the absolute encoder clear mode and execute it as the manual directs.
  4. Cycle control power the way the manual specifies and confirm the alarm is gone.
  5. Re-establish machine position, next section, before enabling automatic operation.

An axis with no stored position moves when commanded, so before jogging it to a reference, apply your machine's lockout practice and the risk assessment behind it; ISO 12100 defines that method.

Does running the clear restore the machine position? #

No: the clear discards the invalid data so the encoder starts from a clean state, it does not reconstruct where the axis was, so machine position has to be re-established by homing or a set datum before any automatic move. After the clear, the encoder's single-turn datum and its multi-turn count rebuild from wherever you establish the reference, so the point where you home becomes the new zero. If the axis has no dedicated home switch, the reference-finding methods in homing an incremental encoder axis without a proximity switch carry over. Verify before trusting the result: command a known move and measure it at the machine, and agreement between commanded and measured distance confirms the datum.

Why does the alarm come back after a power cycle? #

Because the backup path is still broken: a replaced-but-stale cell, an intermittent holder, or a harness that drops the battery line all repeat the failure, and each has a confirming check that takes minutes. How long the cell should last tells you which one you are chasing. Battery life is capacity divided by backup current.

Worked example, calculated on illustrative inputs (a 2000 mAh cell and a 20 µA encoder backup draw; take the real current from the battery table in your encoder's documentation):

  • Life = capacity ÷ current = 2000 mAh ÷ 0.020 mA = 100,000 h
  • 100,000 h ÷ 8760 h/year ≈ 11.4 years

The decision that result gives you: normal life is years, not months. A new cell that dies in weeks means abnormal draw, leakage across the holder, or the wrong cell, not bad luck. When the alarm survives both a new battery and a fresh encoder, the next tier of causes is worked through in an absolute encoder error that persists after battery and encoder replacement.

When should I suspect the cable, the encoder, or the drive? #

When a verified battery sits at the encoder's battery input and the alarm still returns after a clean clear, work the remaining path in cost order: encoder cable, then encoder, then drive, because each swap costs more and proves less than the one before it. The cable is a continuity check against the wiring page, battery line and shield included. The encoder is the swap that answers the question if the cable passes. The drive is last: full battery voltage at its battery input, plus a passing encoder, plus a persisting alarm points at the drive's encoder supply or its backup input.

If the alarm code you are chasing is not in the manual's alarm table, the drive manufacturer's support channel is the documented next step. And keep the diagnosis honest about what the symptom is: a status alarm rather than system down points at the encoder's own diagnostics instead, covered in troubleshooting an absolute encoder status alarm on a servo drive.

Questions asked

How is an absolute system down alarm different from the encoder's other absolute alarms?

Status, counter overflow, and overspeed alarms mean the encoder is powered and reporting a measured condition. System down means every source of encoder power, the backup battery included, was lost at once, so the stored position is gone. That difference is why this alarm needs the battery fixed and the absolute clear run rather than a plain fault reset.

Can I clear the alarm without replacing a weak battery?

You can try, but it buys nothing. The documented sequence is battery first, clear second; a cell at or under the trigger voltage loses backup power at the next shutdown and the alarm returns. Some drives also latch a battery-low condition until the cell is physically replaced, so the reset is refused outright.

What battery voltage counts as healthy on a 3.6 V encoder cell?

A healthy cell sits close to its 3.6 V nominal and typically holds nearly flat over most of its life, then falls quickly near the end. Treat anything more than a few tenths of a volt below nominal at rest as due for replacement, and treat 3.1 V, the documented trigger on the common serial interface, as the floor: at or under it, the alarm is already justified.

How long should an encoder backup battery last?

Life is capacity divided by backup current, so it scales linearly: doubling the cell capacity in mAh doubles the years. At the worked example's figures, 2000 mAh against a 20 µA draw is about 11 years. Real replacements come sooner, because cells age on the shelf and holders corrode, so write the install date on the battery and check its resting voltage at major maintenance outages.

Does running the absolute encoder clear lose the machine's home position?

Yes. The clear discards the invalid stored data; it does not reconstruct it. Afterward, wherever you re-establish the reference becomes the new zero for the axis, multi-turn count included. If something moved the axis while control power was off, that offset left with the old data, so confirm a known mechanical reference before any automatic move.

Keep reading

  • Troubleshooting

    Absolute Encoder Error Persists After Battery and Encoder Replacement

    When an absolute-encoder alarm survives a new battery and a new encoder, stop buying parts and split the chain: verify 3.6 V at the encoder-side battery connector, continuity-check the cable and shield, confirm the controller interface, then run the documented mastering or initialization the axis needs after any encoder swap.

    Sensors, encoders and machine vision on the machine

  • Explainer

    Are Servo Motor Absolute Encoders Really Battery-Backed

    Most servo motors sold as absolute use incremental feedback whose multi-turn count lives in battery-backed memory. The battery feeds a microamp retention circuit, not the operating draw, which is why the hold runs about two years powered down. Change the battery with the control powered so the count survives.

    Sensors, encoders and machine vision on the machine

  • Troubleshooting

    Troubleshooting an Absolute Encoder Status Alarm on a Servo Drive

    The alarm has two documented triggers: the encoder failed its internal status check, or the encoder turned faster than its rated speed after control power was applied. Work from the cheapest check to the decisive one: cable and connector integrity, encoder supply voltage measured under load, shaft motion in the power-on window, then drive settings. Replace the encoder only when all of those pass and the alarm still returns.

    Sensors, encoders and machine vision on the machine