What Steps per Revolution Mean for a Resolver Technology Object

Sensors, encoders and machine vision on the machine Published 5 min read By AutomateDirectUSA engineering team

Short answer

For the 1FK7032-2AK71-1UA2's three-pole-pair resolver, enter 3 steps per revolution and 11 fine-resolution bits (STARTER P418), use standard telegram 3 at both interfaces, and select Rotary incremental in the TIA Portal V13 technology object. The resulting 6144 increments per motor revolution is calculated scaling, not an accuracy rating.

On this page
  1. Confirm which feedback the motor carries
  2. Choose Rotary incremental from the encoder-type list
  3. Worked example: counts per revolution for a 3-pole-pair resolver with 11 bits
  4. Set the fine resolution and telegram on the drive side
  5. Enter the configuration in TIA Portal V13
  6. Verify the scaling before production
  7. Questions asked

An MC technology object in TIA Portal V13 counts position in increments, so it needs the drive's scaling entries, not the resolver's datasheet name. For the 1FK7032-2AK71-1UA2 servo motor and its multipole resolver, enter 3 in the technology object's steps-per-revolution field, set STARTER P418 to 11 bits, select standard telegram 3 at the drive and controller interfaces, and choose Rotary incremental as the encoder type. The three coarse steps come from the resolver's three pole pairs, and the fine resolution subdivides each of those cycles; the worked example below turns the two entries into a per-revolution count you can verify with one turn of the shaft.

Confirm which feedback the motor carries #

The identity appears in two forms: the full order number reads 1FK7032-2AK71-1UA2, while the feedback documentation for the supplied motor uses the shortened form 1FK703-2AK71-1UA2. Read the complete order number from the nameplate and match it to the feedback option it orders before entering any scaling.

For this motor the fitted feedback is a multipole resolver with 3 pole pairs. The resolver reports angle as analog signals; the drive decodes them into the digital position value the controller receives, so the technology object's encoder fields describe what the drive delivers, not the sensor's own windings. If the nameplate is missing, the procedure for identifying geared, resolver and encoder feedback on older servo motors narrows the candidates before you commit to a scaling entry. If you are specifying feedback for a new motor and drive pairing instead, the page on selecting EnDat or resolver feedback for servo drives covers that choice.

Choose Rotary incremental from the encoder-type list #

The technology object's encoder-type list offers four entries — Linear incremental, Linear absolute, Rotary incremental, Rotary absolute — and none of them says "resolver". That is expected: the list describes the measurement geometry and the value path, not the sensor technology. Choose Rotary incremental: rotary, because the feedback measures the angle of a rotating motor shaft; incremental, because the configured path is the incremental actual value, the one identified as GN_X1ST1.

A resolver indicates angle within an electrical cycle but holds no unique machine position, so nothing on this path remembers where the load stood at power-off; the axis needs a referencing step at every start-up. If the machine must hold position across power-off, the interface decision changes, and the approach for using a resolver as absolute position feedback after power-off shows what that takes. If the motor's feedback is later exchanged for an encoder, both the type selection and the two scaling entries change with it; the commutation rules for swapping a servo resolver for an encoder cover what carries over.

Worked example: counts per revolution for a 3-pole-pair resolver with 11 bits #

Inputs for this motor's configuration:

  • Pole pairs: 3 pole pairs — the multipole resolver fitted to the motor, three coarse cycles per mechanical shaft revolution.
  • Fine-resolution bits: 11 bits — the value set in STARTER P418 for this resolver.

Rule: increments per motor revolution = pole pairs × 2^fine-resolution bits. Each pole pair delivers one coarse cycle, and the fine resolution divides every cycle into 2^n equal counting steps.

Arithmetic:

  • 2^11 bits = 2048 counting steps per coarse cycle
  • 3 pole pairs × 2048 counting steps = 6144 increments per mechanical motor-shaft revolution

Result: the configured incremental actual value advances 6144 increments for every full turn of the motor shaft.

Decision: the coarse field takes the pole-pair count and the fine-resolution field takes the STARTER bit depth — never the combined count. Entering the combined count in the coarse field while the fine resolution stays set applies the subdivision a second time: one revolution then counts as 12,582,912 increments and every commanded distance runs 2048 times too far. The per-revolution count is scaling arithmetic for these two inputs — the unit system the axis counts in, not a statement of the resolver's measurement accuracy.

Set the fine resolution and telegram on the drive side #

The fine resolution of the incremental actual value is set in STARTER with parameter P418. It subdivides each coarse cycle inside the digital position value; it is not the width of the position words in the telegram, so a wider or narrower telegram field does not change it.

The second entry is the layout: standard telegram 3 runs at both interfaces, the drive side and the controller side, so the technology object decodes the position words exactly as the drive packs them. A telegram mismatch announces itself as a layout or feedback-validity fault rather than as a proportional position error, which keeps it out of the scaling checks below.

Enter the configuration in TIA Portal V13 #

With the feedback confirmed and the worked example's numbers fixed, the configuration runs in this order:

  1. Read the complete order number from the motor nameplate and confirm it orders the three-pole-pair multipole resolver.
  2. In STARTER, set parameter P418 for the fitted resolver's fine resolution to the worked example's value.
  3. Select standard telegram 3 on the drive interface and the same telegram on the controller interface.
  4. In the technology object's encoder settings, select Rotary incremental.
  5. Enter 3 in the steps-per-revolution field and 11 bits in the fine-resolution field.
  6. Enter the mechanical conversion — gearbox ratio, screw lead, pulley ratio — in the technology object's load-side settings, separate from these encoder fields.
  7. Download and activate the project, then read back the active values on both sides before any test motion.

Verify the scaling before production #

Decouple the load or set narrow travel limits before the first powered move: every entry above scales commanded distance, so a scaling fault turns a short jog into fast, oversized motion.

Three checks confirm the configuration. The interface check: drive and controller diagnostics should both report the telegram chosen above and a valid feedback value — a fault here is interface configuration, not scaling. The readback check: the fine-resolution entry in STARTER and the one in the technology object must show the same value, and the coarse entry must match the worked example's input.

The one-revolution check: with the drive enabled only for a controlled jog, turn the shaft exactly one mechanical revolution and read the change in the incremental actual value — it should advance by the worked example's result, 6144 increments per revolution. A change 2048 times that figure is the double-subdivision signature described above; a clean proportional miss with a simple ratio means one entry does not match the other side's configuration. Correct the entry, download and activate again, and repeat the check before the axis runs production parts.

Questions asked

Why does my axis travel 2048 times the commanded distance?

That ratio is the double-subdivision signature: the coarse steps-per-revolution field holds the combined increment count while the fine-resolution field applies its bit depth on top. Correct the coarse entry to the pole-pair count, leave the fine resolution as configured, download and activate again, then repeat the one-revolution check. Direction and torque look normal in this state, which is why it survives commissioning.

Does the increment count tell me the resolver's measurement accuracy?

No. The count is controller scaling: coarse cycles multiplied by a binary subdivision. Resolver accuracy depends on signal quality, wiring and the drive's interpolation, and the drive and motor documentation state what the feedback actually resolves. Treat the increment count as the unit system the axis counts in, and judge measurement quality from the feedback specification, not from the scaling entry.

Why does the axis lose its position after every power-off?

The configured path is incremental, and an incremental actual value restarts from an arbitrary state at power-up, so the technology object's position is valid only after referencing. Build a homing or referencing step into every start-up. If the machine must keep position across power-off, the feedback interface itself has to change, not the two scaling entries.

Where does the gearbox or ball-screw ratio go?

In the technology object's mechanical or load-side scaling, never in the encoder fields. The encoder entries describe the motor shaft only: one coarse cycle per pole pair, subdivided by the fine resolution. The conversion between motor revolutions and load travel multiplies on top of that, so run the one-revolution check on shaft rotation first and add the load-side scaling afterwards.

Keep reading

  • Selection guide

    Choosing Encoder Resolution to Match a Stepper Step Response

    A 50 ppr encoder read in x4 gives 200 counts/rev — one count per 1.8° full step, so the loop sees only before and after each step and ±1 count is ±1.8°. Size the encoder by counts per full step: 10 counts per step, which is 500 ppr in x4 at 2000 counts/rev and 0.18° per count, is the working minimum to reproduce a stepper's damped step response.

    Sensors, encoders and machine vision on the machine

  • Troubleshooting

    Fix Servo Travel Error After Swapping Resolver and Encoder

    Travel that does not match the position display after a resolver-to-encoder swap is a scaling fault: the drive or the technology axis is still converting counts with the other feedback's increments per revolution. Measure one commanded move and divide actual by displayed travel; a constant ratio equal to the resolution ratio names the encoder data. Fix both layers, re-home, then re-tune.

    Servo and stepper motion

  • How-to

    How to Identify Geared Resolver and Encoder Feedback on Old Servos

    Treat the resolver plus its geared 1:4 and 1:80 channels as one integrated coarse-and-fine, multi-turn position package: the resolver reads absolute angle within one shaft revolution, and the geared channels count revolutions above it. Identify each channel by resistance checks, ratio counting and waveform capture before choosing a replacement drive, because the resolver model number alone establishes neither commutation nor multi-turn position recovery.

    Sensors, encoders and machine vision on the machine