Using a Resolver as Absolute Position Feedback After Power-Off

Sensors, encoders and machine vision on the machine Published 8 min read By AutomateDirectUSA engineering team

Short answer

Yes, conditionally. A resolver is absolute within one electrical cycle, so it recovers the shaft angle after power-off without a battery, but with R motor revolutions per table revolution the feedback repeats every 360/R degrees of table travel. A turntable whose stroke crosses that period must home at startup or add multiturn feedback.

On this page
  1. Is a resolver an absolute encoder?
  2. What does a resolver lose when power is removed?
  3. How far does the table move before resolver feedback repeats?
  4. Can a forward-and-reverse turntable recover its position at power-up?
  5. What else must be true for the recovered coordinate to be correct?
  6. Where do you configure the recovered machine coordinate?
  7. When should you add multiturn feedback to a resolver axis?
  8. Questions asked

Yes, conditionally, and the condition is arithmetic rather than configuration. A resolver is absolute within one electrical cycle: its sine and cosine signals encode the shaft angle with no battery and no stored count, so the drive measures the angle again the moment power returns. What it cannot tell you is how many cycles the axis completed before the outage. On a geared turntable the angle repeats at a fixed spacing of table travel set by the transmission ratio, and resolver-only recovery works exactly when the permitted stroke is shorter than that spacing. Below is the check, a worked example, and the decision for each case.

Is a resolver an absolute encoder? #

Yes, within one electrical cycle: the resolver is a rotating transformer whose sine and cosine voltages encode the shaft angle, so after a power-off the angle is measured again from the present signals, with no battery and no stored count to lose.

The drive's resolver interface drives an AC excitation into the reference winding, and two output windings spaced 90 electrical degrees apart return signals proportional to sin θ and cos θ of the shaft angle. Their ratio, sin θ / cos θ = tan θ, identifies the angle regardless of amplitude drift, and the interface converts that ratio into a digital value.

Because the angle comes from signals present at that instant, there is nothing to convert and nothing to add: within its cycle the resolver already works as an absolute encoder. The fine resolution is set by the angle converter in the interface, since the signals are continuous rather than a line count to divide. Multi-speed resolvers generate several electrical cycles per mechanical revolution; the rest of this article assumes the common single-speed type, one cycle per revolution.

What does a resolver lose when power is removed? #

It forgets the completed-turn count: a single-speed resolver repeats its electrical angle once per motor revolution, so at power-up you know the angle within that revolution but not how many revolutions the axis accumulated before the power went.

That is the difference between single-turn and multiturn absolute feedback. A multiturn absolute encoder counts completed revolutions on a gear train or a battery-backed counter, so it can report a full position such as turn 23 at 41 degrees after an outage. A plain resolver reports 41 degrees and says nothing about the 23.

Multiturn resolvers exist — a fine resolver combined with a coarse turn-counting stage in one housing — but that is a different sensor specified into the motor, not a mode of the standard unit already on your shaft. So the drive can always recover the within-cycle angle after power returns; whether that angle names a machine position is a question about the mechanics, which comes next.

How far does the table move before resolver feedback repeats? #

The feedback repeats every 360° / R degrees of table travel, where R is the number of motor revolutions per table revolution, assuming a single-speed resolver, a fixed transmission ratio and no slip.

One motor revolution is 360° of motor rotation, and it advances the table by 1/R of a revolution. On a single-speed resolver the electrical angle completes one full cycle in that same motor revolution, so the reading repeats after 360° / R of table travel. With a multi-speed resolver of n cycles per motor revolution the period shrinks to 360° / (R × n).

Take R from the mechanical documentation, counting every stage between motor and table: a 40:1 gearbox driving the table directly gives R = 40; add a 3:1 toothed-belt stage after the gearbox and R = 40 × 3 = 120. The fixed-ratio assumption is doing real work here — a slipping belt or a worn stage breaks the link between motor angle and table angle, and no startup routine can repair that.

Can a forward-and-reverse turntable recover its position at power-up? #

Yes, but only when the permitted stroke is shorter than one feedback period: a 90-degree stroke on a 60:1 table repeats its resolver angle 15 times, so that machine must home at startup or count turns with multiturn feedback.

A calculated example, not a measured result. Inputs: the motor reaches the table through a 60:1 ratio, so R = 60 motor revolutions per table revolution; the resolver is single-speed, one electrical cycle per motor revolution; the permitted stroke runs from home at 0° to a forward limit of 90° and back to home.

Step 1, the period: 360° / 60 = 6° of table travel.

Step 2, the periods inside the stroke: 90° / 6° = 15 periods. The angle read at power-up matches table positions at 0°, 6°, 12° and so on up to 90° — sixteen candidates for one reading.

Decision for that machine: the mapping is ambiguous, the coordinate cannot be reconstructed from the resolver alone, and the choice is a homing run at every startup or multiturn feedback.

Two neighboring builds show where the line sits. Limit the same table to a 4° stroke, inside one 6° period, and every permitted position has its own angle — recovery from the resolver alone works once offset and wrap are configured. Drive the table straight off the motor, R = 1, and the period is 360° / 1 = 360°, so the 90° stroke is unique with margin.

The forward-and-reverse pattern itself changes nothing: uniqueness is decided by the total angle the table may occupy, not by the path it takes between the ends.

What else must be true for the recovered coordinate to be correct? #

Four more things: the reference offset from home to resolver zero, the direction sign, the wrap at the angle boundary, and any table movement while the drive is off — each one wrong gives you a plausible but false coordinate.

  • Reference offset. Home is a physical stop or mark; the resolver angle read at that spot is the offset. Store it where it survives power cycles, or the recovered coordinate shifts by exactly that amount.
  • Direction. Increasing table angle must map to the sign the controller expects. Resolver signal pairs wired swapped or reversed mirror or shift the angle, and the symptom is motion that runs away from the target.
  • Wrap. A stroke inside one period can still cross the resolver's zero boundary during a continuous forward move, and a naive angle difference reads that crossing as a large reverse jump. Place the offset so the working stroke sits away from the boundary, or unwrap the angle explicitly when rebuilding the coordinate.
  • Movement while off. The resolver reports where the shaft actually is at power-up, which is its strength. If a holding brake or the load geometry guarantees the table cannot move unpowered, the startup angle equals the shutdown angle; if hands or gravity can move it, trust the fresh reading or a homing run, never a coordinate saved before the outage.

Where do you configure the recovered machine coordinate? #

The resolver interface supplies the raw angle; the machine coordinate — offset, scaling, direction and turn count — is built one layer up in the drive or motion controller, and that is the layer you configure.

The interface module that excites and decodes the resolver hands a raw angle upward. Scaling it into table degrees — dividing by R — and applying the direction sign, the home offset and the cycle count happens in the drive's position handling or in the motion controller; the commissioning manual for the installed drive states which referencing and restart functions it supports. No change to how the signals are interpreted creates a turn count the sensor never measured; that count has to come from a reference run or from a sensor that measures it.

Before touching anything, record the working baseline: feedback type, scaling, direction and the current homing behavior, so a restart regression has something to be compared against. Then control the startup sequence: keep automatic motion inhibited until the interface reports valid feedback and the recovered coordinate is checked against expectation, and where the mapping can be ambiguous the homing run comes before any powered move.

When should you add multiturn feedback to a resolver axis? #

Choose multiturn feedback when the stroke crosses one feedback period and a homing run at every power-up costs too much cycle time; below one period, keep the resolver and reference from its startup angle.

The decision for each case:

  • Stroke inside one feedback period: keep the resolver, configure startup referencing from the measured angle, handle the offset and the wrap, and skip the homing run.
  • Stroke crossing the period, homing acceptable: keep the resolver and home at every power-up — the 60:1 table from the example.
  • Stroke crossing the period, homing unacceptable: add multiturn feedback. A multiturn absolute encoder on the motor holds the turn count through the outage and deletes the homing run; the maintenance question there is whether servo motor absolute encoders are really battery-backed. If the swap puts an encoder on the existing motor, the commutation rules for swapping a servo resolver for an encoder decide whether the motor commutes correctly at all.

No case allows a saved coordinate to stand in for a measurement: the saved number is a claim about the table, the resolver angle is evidence.

Questions asked

Does the resolver interface measure anything while the drive is powered off?

No. The excitation and the angle conversion both live in the drive's resolver interface, so during the outage nothing is measured and nothing is kept. At power-up the interface re-excites the resolver and reads the shaft as it is at that moment, which is why a table that moved while off is measured at its true new angle rather than the remembered old one.

How do I confirm how many electrical cycles my resolver makes per revolution?

Read the motor datasheet for the resolver speed or pole-pair count, and the feedback type set in the drive, then verify on the machine. With the drive's power stage disabled, turn the motor shaft exactly one revolution by hand and watch the feedback angle in the drive's diagnostics: a single-speed resolver sweeps through 360 degrees once, a two-speed unit twice.

Can I store the turn count at shutdown and combine it with the resolver angle?

Yes, when the table cannot move more than one feedback period while powered off. Save the completed-cycle count at shutdown; at startup, combine it with the fresh angle, and if that angle shows the shaft crossed a period boundary, adjust the stored count by one. If the table can be pushed freely with the drive off, the stored count can be wrong by any number, and homing is the only honest recovery.

Does gearbox backlash corrupt the recovered table position?

It can. The resolver on the motor shaft recovers the motor angle exactly, but lost motion between motor and table — gearbox backlash, belt compliance — lets the real table angle differ from the reconstructed value by up to the total lost motion. If the table itself must hold position, reference on the table side, or approach every target from the same direction so the lost motion always lies the same way.

Keep reading

  • How-to

    How to Identify Geared Resolver and Encoder Feedback on Old Servos

    Treat the resolver plus its geared 1:4 and 1:80 channels as one integrated coarse-and-fine, multi-turn position package: the resolver reads absolute angle within one shaft revolution, and the geared channels count revolutions above it. Identify each channel by resistance checks, ratio counting and waveform capture before choosing a replacement drive, because the resolver model number alone establishes neither commutation nor multi-turn position recovery.

    Sensors, encoders and machine vision on the machine

  • Troubleshooting

    Absolute Encoder Error Persists After Battery and Encoder Replacement

    When an absolute-encoder alarm survives a new battery and a new encoder, stop buying parts and split the chain: verify 3.6 V at the encoder-side battery connector, continuity-check the cable and shield, confirm the controller interface, then run the documented mastering or initialization the axis needs after any encoder swap.

    Sensors, encoders and machine vision on the machine

  • Explainer

    Are Servo Motor Absolute Encoders Really Battery-Backed

    Most servo motors sold as absolute use incremental feedback whose multi-turn count lives in battery-backed memory. The battery feeds a microamp retention circuit, not the operating draw, which is why the hold runs about two years powered down. Change the battery with the control powered so the count survives.

    Sensors, encoders and machine vision on the machine