How-to
How to release a stepper motor after a move
Short answer
Yes: stop the step pulses, confirm the move-complete condition, then release the drive's ENABLE circuit. Holding torque disappears and the load settles mechanically, exactly as if the drive were powered down. Do not power-cycle the drive or open motor leads, and re-home the axis before its next absolute move if the released shaft can move.

On this page
- How do you release a stepper motor at the end of a move?
- Why does the motor stay locked after the last step pulse?
- Why not switch the drive power off instead?
- Which drive input actually removes the holding torque?
- When can you drop ENABLE relative to the pulse train?
- How do you wire the PLC output to the drive's ENABLE input?
- What happens to the axis position while the motor is released?
- How do you verify the release before running production?
- Should you release the motor or reduce the hold current instead?
- Questions asked
Yes — the function exists on the drive itself, and it is wired through the ENABLE input, not through the power supply. Stop the step pulses, wait for the pulse-output instruction in the DL-05DD to report the move complete, then release the ENABLE circuit to the STP-DRV-4035: the driver stage switches off, holding torque disappears, and the moved components settle freely, just as they would with the drive powered down — but without a supply restart. This article walks the sequence in the order you build and prove it: why the motor stays locked after the last pulse, which input removes the torque, when to drop that input relative to the pulse train, how to match the PLC output to the drive input, what happens to position while the load is free, and how to verify the release before production runs.
How do you release a stepper motor at the end of a move? #
Stop the step pulses, wait for the pulse output's move-complete condition, then open the drive's ENABLE circuit: holding torque disappears and the load settles on its own. In the setup in question — a DL-05DD driving a STP-DRV-4035 from a STP-PWR-3204 — the ENABLE terminals on the drive are the control point. A basic setup diagram can show them unused, because a continuously enabled drive runs simple moves fine; unused in a diagram is not unavailable, and those terminals are built for exactly this. A released motor behaves like a powered-down one as far as the load is concerned, while the supply, the logic and any other axes keep running, and re-enabling becomes a logic event instead of a restart.
Why does the motor stay locked after the last step pulse? #
An enabled stepper drive keeps both windings energized at standstill, and that current is holding torque, not a motion command — so the last pulse stops motion but leaves the shaft locked where the move ended. Holding torque is a property of the drive's enabled state, not of motion: the STP-DRV-4035 keeps its output stage energized between moves, and the rotor locks to the standstill current pattern until that state changes. Keep three states distinct in your sequence: enabled and moving, enabled and holding, disabled and released — only the third lets the load settle.
That enabled-and-holding state is also the one that heats an idle axis. It is the same standstill current that leaves a stepper motor hot while enabled and not moving, and it draws continuous power for every second of every dwell.
Worked example, calculated for illustrative inputs — take winding current and resistance from the motor datasheet; these are example values, not STP-MTR-34066 ratings. A bipolar drive energizing two windings at 2.0 A with 1.0 Ω per winding dissipates (2.0 A × 2.0 A) × 1.0 Ω = 4.0 W in each winding, 8.0 W at the motor. An axis that dwells 30 s each cycle for 240 cycles each shift, two shifts a day, spends 240 × 30 s = 7,200 s = 2.0 h of dwell each shift, so that motor burns 8.0 W × 2.0 h × 2 shifts = 32 Wh each day — roughly 8 kWh over 250 working days, produced purely to hold position.
Why not switch the drive power off instead? #
Switching the STP-PWR-3204 off and back on does remove torque, but it does it uncontrolled: every axis releases at once, the next move waits for the supply and the drive to restart, and startup behavior is not something your sequence commands. Power cycling also carries a start-up risk no release logic should absorb: a stepper axis can run at drive power-up before software loads, which is the opposite of a controlled release. The ENABLE input exists so that release is a commanded, repeatable event — application documentation for step/dir drives describes ENABLE as switching the driver stage completely off or on, used for energy saving when no holding torque is needed. Same end state as removing supply power, reached through logic you sequence.
Which drive input actually removes the holding torque? #
The ENABLE input on the STP-DRV-4035 is the documented release point: it switches the driver stage completely off, which removes holding torque exactly as power-off would, without touching the supply or the motor leads. The polarity is the trap: whether torque is present with ENABLE energized or de-energized is a documented property of the input circuit, and assuming energized-equals-enabled is how drives end up permanently released or permanently locked. Read the terminal-function and input-wiring sections of the drive manual and wire to what they state. Some driver boards also expose Sleep and Reset inputs that drop the output stage; those are separate functions with their own polarity and timing rules, so use the input your drive documents for release. On this drive that input is ENABLE, and it doubles as the release command for an otherwise continuously enabled system.
When can you drop ENABLE relative to the pulse train? #
Drop ENABLE only after the move instruction reports complete and the pulse output is confirmed inactive: releasing while the last pulses are still being generated truncates the move and leaves an undefined final position. Run the release as its own step in the cycle sequence:
- Assert ENABLE and let the drive's enabled state establish before the first step pulse; if the manual states an enable-to-step interval, use that value — do not add an undocumented arbitrary delay.
- Command the move and keep ENABLE asserted for the entire pulse train.
- Wait for the completion flag of the DL-05DD pulse-output instruction and confirm that no further pulses are being generated.
- Release ENABLE.
- Let the mechanism settle without treating the result as a controlled position.
- Re-assert ENABLE before the next move, and home or reference the axis first if the shaft could have moved while released.
Interlock the release against the active-move condition: drive it from the same completion bit that ends the step sequence, not from a parallel timer, so a one-scan race between pulse generation, completion and enable removal cannot truncate the move.
One safety rule belongs here: a released motor cannot restrain a vertical, spring-loaded or stored-energy load, so give such a mechanism a mechanical restraint that does not depend on motor torque before ENABLE is ever dropped.
How do you wire the PLC output to the drive's ENABLE input? #
Match the PLC output to the drive's input circuit before wiring: confirm from the STP-DRV-4035 documentation which terminals are ENABLE, whether the input is active high or active low, and whether the DL-05DD output type can drive that circuit directly. A release input switches a few times each cycle at most, so speed does not drive the choice — circuit match does. A relay output is acceptable for a function this slow provided its contact rating covers the drive input's voltage and current; a transistor output must match the drive's input common and current direction. Confirm four things before the first wire goes in: the ENABLE terminal pair, the active state, the required common and current direction, and whether an interposing relay is needed between output and input. Then set the fail state deliberately: with the output de-energized — controller off, wire broken, control power lost — decide whether the load should release or stay held, and choose the polarity that gives this machine the safe answer.
What happens to the axis position while the motor is released? #
Once torque is removed, gravity, springs and process forces — not the controller — decide where the mechanism settles, and a stepper has no encoder to report the change, so the commanded position and the physical position separate the moment the shaft moves. End every release with a decision. If the released shaft can move — anything vertical, off-balance or spring-driven — home or reference the axis before the next position-dependent move; it is the same recovery problem as retaining stepper axis position after power loss. If the axis provably cannot move while released — a horizontal slide held by friction and detent torque under a settled load — the DL-05DD's commanded coordinates stay valid and no homing step is needed. What you must not do is assume: the controller's position register does not follow the shaft.
How do you verify the release before running production? #
Prove the sequence in four bench checks — enabled and locked, released and free, re-enabled and locked again, next move from a fresh reference — with the mechanism physically supported so a first release cannot drop, pinch or crash anything. Check in this order:
- Enabled at rest: the shaft resists turning by hand — holding torque is present.
- Move commanded: the axis completes the programmed move with ENABLE asserted.
- ENABLE released: torque disappears and the load settles. If it does not, measure the ENABLE input state at the drive terminal and compare it with the manual's inactive state — a correct output bit in the DL-05DD does not prove the drive input changed.
- Re-enabled: torque returns with no unintended motion; a shaft that jumps on re-enable points to residual step pulses still being driven.
- Next cycle: the axis starts from a fresh reference wherever the release could have moved it.
Judge each check by watching the load, not only the logic.
Should you release the motor or reduce the hold current instead? #
Release through ENABLE when the load must settle freely; use the drive's hold-current setting when it must stay held but run cooler; keep it fully enabled when the next cycle must start from the current position without homing. The situation decides:
| Situation | Control action | Why |
|---|---|---|
| Load must settle into a natural position after the move | Release ENABLE after move-complete; re-home if the shaft can move | Zero active torque is the only state in which process forces settle the mechanism |
| Load must stay held between moves but runs hot at standstill | Hold current, where the drive provides it | Reduced standstill current keeps torque with less heat and no position loss |
| Vertical, spring-loaded or stored-energy load | Fail-held wiring plus a mechanical restraint; release only under command with the restraint engaged | Motor torque is the only thing restraining the load |
| Next cycle must resume the exact current position without homing | Keep ENABLE asserted; do not release | In an open-loop stepper, holding torque is the position memory |
On a DL-05DD driving a STP-DRV-4035, the whole decision compresses to one line of sequence: completion flag on, ENABLE off, let the load settle, ENABLE on, home if it moved.
Questions asked
Can I drop ENABLE in the middle of a move?
You can, but it is an uncontrolled stop: torque vanishes instantly and the mechanism coasts or falls wherever forces take it, with the axis position unknown afterward. Reserve it for a jam or an emergency, then home the axis before the next position-dependent cycle. For normal cycles, finish the move and release only after the completion flag.
Why does a released stepper still resist turning by hand?
Because detent torque remains: the rotor's permanent magnet coggs against the stator teeth even with the windings de-energized. It is a small fraction of the rated holding torque and specific to the motor, so take the value from the STP-MTR-34066 datasheet rather than assuming zero. Detent torque is passive and cannot hold a load against gravity or a spring.
What is hold current, and when is it better than releasing the motor?
Hold current is a drive setting that reduces the standstill winding current instead of removing torque, so the axis keeps its exact position with less heat — the middle state between enabled-and-holding and released. Choose it when the load must stay held between cycles but the motor runs too hot; choose full release only when the load must settle freely.
Is releasing a servo axis the same operation?
Similar input, different fail behavior. A servo drive exposes an enable or disable input much like a stepper drive, but many servo axes pair it with a motor brake: on a vertical axis the brake must be engaged and holding before drive torque is removed. Sequence brake first, then disable, and let the servo controller's own stop logic finish the motion.