Why a stepper motor gets hot when enabled but not moving

Servo and stepper motion Published 8 min read By AutomateDirectUSA engineering team

Short answer

Heat with the shaft stopped is holding current at work: an enabled pulse-and-direction driver feeds both windings continuously, and copper loss P = I²R turns that current into heat before a single pulse arrives. Fix it at the driver with idle-current reduction and a datasheet temperature check before you change the PLC's ready and enable wiring.

On this page
  1. Why does an enabled stepper motor get hot without moving?
  2. How hot is too hot for a stepper motor?
  3. Do I have to wire the ready and enable signals in the axis configuration?
  4. Does MC_POWER itself heat the motor?
  5. How much heat does holding current actually make?
  6. What should I check, in what order?
  7. How do I cut the heat without losing position?
  8. When is it safe to de-energize the motor at standstill?
  9. Which fix fits my case?
  10. Questions asked

An enabled stepper driver is a heater by design: with the axis enabled and no move commanded, it still feeds both windings at the set phase current, and copper loss P = I²R turns that current into heat. The pulse train commands motion, not winding current, so an idle pulse output never means an idle motor. Work through the physics before you touch the PLC: measure the case temperature against the motor's datasheet, read the driver's current and idle-current settings, and wire the ready and enable signals only where the driver's terminals actually provide them. The sections below answer each question in the order you meet it and end with the fix that fits each case.

Why does an enabled stepper motor get hot without moving? #

The driver is doing its job: once the axis is enabled, the driver feeds both windings at the set phase current even with zero pulses, and winding copper loss P = I²R converts that current to heat continuously.

The chopper stage inside the driver regulates each winding to its configured current on its own; step pulses only advance the current vector, they do not gate it on. After MC_POWER enables the axis — or after the driver powers up with no external enable wired — both windings of a bipolar motor carry current at standstill, so the dissipation is roughly twice one winding's loss. Nothing in the pulse-and-direction interface interrupts that current: pulse and direction command movement, and only the enable path, wired or internal, commands energization. That is why a motor can scald after ten enabled minutes during which the PLC never issued a step.

How hot is too hot for a stepper motor? #

Touch cannot decide this: bare metal at about 60 °C burns skin in roughly five seconds, and a full-current stepper can legitimately run near that, so measure the case and compare it with the datasheet limit.

Mark one point on the motor body and measure there every few minutes with a contact probe or an infrared thermometer until the reading stops climbing. The winding temperature limit comes from the insulation class — 130 °C for class B, 155 °C for class F — and the permitted case temperature sits below that, at the value in the datasheet of your exact motor. A stable reading at or under that limit is normal operation for the design; a reading that keeps rising past it calls for a lower current setting or more cooling.

Do I have to wire the ready and enable signals in the axis configuration? #

No: in the S7-1200 axis technology object the ready input and the enable output are optional signal assignments, and a supported configuration can leave both unassigned — what matters is that any assignment matches the driver's terminals.

Ready is status feedback: a wire from the driver's status output to a PLC input, reporting that the driver meets its own readiness conditions — it is not proof of shaft position, motor temperature or available torque. Enable is a command: a wire from a PLC output to the driver's enable terminal, letting the controller de-energize the windings. Neither replaces pulse and direction, which remain the command interface and whose signal levels and polarity must match the driver's inputs, as covered in what a stepper driver control connector needs from a PC. Assign a ready input in the configuration and leave it unwired, and the axis may fail to become ready; leave the signals unassigned and the driver simply energizes on its own supply conditions. The S7-1200 Motion Control function manual documents the signal options for the technology object version you have installed.

Does MC_POWER itself heat the motor? #

No: MC_POWER enables the axis so that Motion Control commands can run, and Siemens documents it as an enable instruction rather than a move command — the heat comes from the holding current that flows once the driver is energized.

With no motion commanded, expect zero pulse activity at the pulse output. If pulses continue while the axis stands still, look for a motion instruction that is active in the program, not at the driver. And if the pulse output is quiet but the motor still heats, the driver is energized by its own power and enable conditions — exactly the state that a wired enable output would let you interrupt. That is why changing PLC logic alone rarely cools a motor whose driver has no enable terminal wired.

How much heat does holding current actually make? #

Compute it from your motor's own numbers: copper loss per winding is P = I²R with I the RMS phase current and R the winding resistance from the datasheet, and both windings carry current at standstill.

Worked example, with illustrative inputs — substitute the plate values of your own motor. Take a winding resistance of 1.0 Ω and a rated RMS phase current of 2.8 A:

  • Per winding: P = (2.8 A)² × 1.0 Ω = 7.84 W.
  • Both windings energized: 2 × 7.84 W = 15.7 W, dissipated continuously with the shaft stopped.
  • With idle-current reduction holding half the current: (1.4 A)² × 1.0 Ω = 1.96 W per winding, 3.9 W total — a quarter of the heat, because loss scales with the square of current.

These are calculated values for those inputs, not a measured result. Also check the setting convention: a driver that interprets its current setting as peak while the motor plate states RMS — or the reverse — changes the real winding loss by a factor of two.

What should I check, in what order? #

Start with the checks that cost nothing: a temperature measurement, a settings read, a wiring audit, then a settings change, and only last added cooling — each step either clears a suspect or names the next one.

  1. Measure the case at your marked point every few minutes until the reading stabilizes, and compare it with the datasheet limit.
  2. Read the driver's phase-current and idle-current settings, including the peak-versus-RMS convention and the situation described in when a stepper driver is rated below the motor current.
  3. Audit the ready and enable wiring against the axis configuration, so that no assigned input is left unwired.
  4. Confirm the pulse output stays quiet while no motion is commanded.
  5. Switch on the driver's idle-current reduction if the load can tolerate it.
  6. Add a heatsink or fan only when the load genuinely needs full holding current at standstill.

How do I cut the heat without losing position? #

Use the driver's own idle-current reduction rather than PLC logic: the drive drops to its reduced standstill current after the last step, which on the example winding takes the loss from 15.7 W to 3.9 W — a quarter of the heat.

The reduction level, the trigger and any delay live in the driver, set by its DIP switches, potentiometer or configuration tool, so take the values from the driver's documentation instead of building a timer in the PLC. Then verify the hold: apply the mechanism's real stationary load and confirm the shaft does not rotate. A stepper is open-loop here — a quiet pulse output is not proof that the shaft stayed put. If the shaft moves at reduced current, the reduction is too deep for that load: raise it or hold the mechanism mechanically. Note too that the winding resistance in the I²R equation depends on the series or parallel connection chosen, a second reason the same nameplate current can run hotter or cooler — the details are in why a stepper motor runs hot from winding connection and phase current.

When is it safe to de-energize the motor at standstill? #

Only when the mechanism holds itself: with a non-backdriving lead screw, a brake or a counterbalance, dropping the enable takes both windings to zero watts during long idles, while a gravity- or spring-loaded axis drifts the moment the current stops.

With the enable output wired to the driver's enable terminal and assigned in the technology object, the disable path removes winding current entirely and the shaft turns freely by hand — convenient for setup and for clearing jams between cycles. Keep that current on whenever the load needs holding torque; idle reduction plus a heatsink or fan is the fix there, not de-energizing. Before working near any axis that could fall or back-drive, secure it mechanically and follow the machine's risk assessment and lockout practice — this article is a diagnosis, not a safety validation.

Which fix fits my case? #

Match the symptom to the fix: a stable reading inside the datasheet limit with a self-holding load needs nothing, the same motor under a torque load gets idle-current reduction, and a reading over the limit gets lower current or cooling before anything else.

  • Stable at or under the datasheet case limit: normal for the design; enable idle-current reduction if the load allows, and leave the enable wiring as it is.
  • Over the limit or still climbing: correct the current setting and its convention first, then idle reduction, then heatsink or fan.
  • Load needs holding torque at standstill: idle reduction sized by test plus cooling, never a bare disable.
  • Load holds itself: wire the enable output and de-energize on long idles.
  • Full holding torque needed continuously and still too hot: the motor is undersized for the duty — move to a larger frame rather than nursing a hot one.

Questions asked

Does a stepper motor draw more current standing still than while turning?

Roughly the same: the driver's chopper regulates each winding to the set current whether the shaft turns or not, so copper loss is the baseline at any speed and motion adds iron and switching losses on top. With idle-current reduction active the standstill value drops below the running one; without it, standstill runs at the full setting.

What case temperature can a stepper motor tolerate?

Read the case-temperature limit from the datasheet of your exact motor; it sits below the winding limit set by the insulation class, commonly 130 °C for class B or 155 °C for class F windings. Measure the case at a marked spot with a probe or infrared thermometer, because touch alone cannot judge it.

Why does my motor get hot even though the pulse output sends no pulses?

Pulses command motion, not current. After MC_POWER enables the axis, the driver holds both windings at the set phase current on its own chopper control, so a completely quiet pulse output still leaves the motor dissipating full holding heat. Wrong pulse or direction wiring causes wrong or missing movement, not standstill heat.

Can I lower the driver's running current instead of using idle-current reduction?

Only if the moves still complete: running current sets motion torque, and a setting below what the load needs shows up as lost steps or stalls rather than cooler running during motion. Idle-current reduction lowers the current only after the last step, which is why it cools a stopped axis without touching move torque.

What happens to the axis position if I disable the motor and turn the shaft by hand?

The controller still counts the position it last commanded, so any manual rotation desynchronizes the open-loop count from the real shaft. Re-home or re-reference the axis before trusting its next move. Disabling itself is harmless to the drive; it is the untracked motion afterward that needs the reset.

Keep reading

  • Troubleshooting

    Why an EtherCAT CSP Stepper Axis Enables but Does Not Move

    Holding torque on Servo On proves only that the power stage energizes the windings. In cyclic synchronous position mode the axis moves only when the drive accepts each new 0x607A target and no internal limit refuses it, so check Statusword bit 11 first, then the drive's speed, current and software position limits, then the position unit scaling between controller and drive.

    Servo and stepper motion

  • Explainer

    Why a Stepper Motor Runs Hot: Winding Connection and Phase Current

    Copper loss sets stepper heat: current squared times winding resistance, summed over the energized sections. The driver's current setpoint and the winding connection decide it; the supply voltage mostly sets torque at speed. Wire the motor half-coil, bipolar parallel or bipolar series for the torque-speed curve the axis needs, set current to that connection's rating with the driver's documented setting equation, drop the current when the axis idles, and judge the result by stabilized case temperature and position retention.

    Servo and stepper motion

  • Troubleshooting

    Stepper pulse output enabled but motor not moving: jumper first

    An output-enabled bit proves permission, not current through the drive's optocoupler. On the H0-CTRIO2 one jumper sets both pulse outputs to sink or source, so a sinking loop landed on the wrong common passes nothing. Fix the control loop, scope the pulses at the drive terminals, then lower the start rate before touching the motor.

    Servo and stepper motion