Load Sharing Between Two VFD Motors on One Common Load
Short answer
Two induction motors pulling one common load cannot be synchronized by giving both drives the same frequency reference: slip makes each shaft speed depend on its own share of the load. Put the master drive in speed control and the slave in torque-follower mode, with the slave's speed reference set a documented margin above the master and its speed limit verified. Independent loads each need their own closed speed loop, and the PLC hands out run, direction, reference and the coordinated stop.

On this page
Two motors pulling one common load will not stay matched just because both drives receive the same frequency reference. An induction motor's shaft speed depends on its own load through slip, so two motors carrying different shares of one load turn at different speeds on identical commands. The working architecture for a common load is a master drive in speed control and a slave in torque-follower mode, with the slave's speed reference set a documented margin above the master and its speed limit verified before first run. For independent loads, give each drive its own closed speed loop and let the PLC hand out run, direction, reference and the coordinated stop instead of trimming speed in a scan-based loop.
Why the same frequency command does not give the same shaft speed #
An induction motor's rotor follows a rotating field that turns at synchronous speed, and the rotor falls behind it by the slip. Below the breakdown point, slip rises roughly in proportion to shaft torque: a lightly loaded motor runs close to synchronous speed and a fully loaded one runs measurably slower, on exactly the same frequency reference. Two drives fed an identical reference therefore settle at different shaft speeds whenever their loads differ, and the split of one common load between two motors is not fixed by the wiring. It settles wherever each motor's slip curve meets the shared speed of the load.
Two closed speed loops on one rigid load make this worse, not better. Each loop tries to impose its own speed, the loops fight each other, and the losing drive pushes current without moving the load. That competition, not the PLC's scan time, is why the architecture has to be chosen at the drive level before any logic is written.
Decide the mechanical case first #
| Mechanical arrangement | What must stay equal | Architecture that works |
|---|---|---|
| Both motors act on one rigid load (load sharing) | Torque split, by design | Master in speed control, slave in torque-follower mode |
| Independent loads that must run at the same speed | Shaft speed, measured under load | Each drive in its own closed speed loop on a common reference |
| Independent loads whose travel must stay aligned | Accumulated position | Position-level control or registration correction; speed matching alone accumulates error |
Trace the mechanics before configuring anything. If pulley diameters or gear ratios differ between the two paths, equal shaft rpm does not give equal cable travel, so the variable to control is not speed at all. Decide the fault response first as well: if one drive stops while the other keeps pulling, the machine needs a coordinated stop owned by the controller, not a speed correction.
Two 4 kW motors at 50 Hz: what slip costs at half load #
The inputs for this worked example:
- 4-pole motors on a 50 Hz supply, so synchronous speed is 120 × 50 / 4 = 1500 rpm (calculated).
- An illustrative nameplate full-load speed of 1440 rpm, typical for this motor class; take the real figure from each motor's own nameplate.
- Full-load slip is therefore 1500 − 1440 = 60 rpm.
Motor A carries its rated torque, so it slips the full 60 rpm and turns at 1440 rpm. Motor B carries half of rated torque, and below the breakdown point slip follows torque, so it slips about 30 rpm and turns at 1470 rpm.
The result: identical 50 Hz references on both drives, and a 30 rpm standing speed difference, about 2% of synchronous speed, driven purely by the uneven load split. If you verify shaft speeds with a 360 PPR encoder, motor A's pulses arrive at 360 × 1440 / 60 = 8640 pulses per second, which must sit below the PLC input's rated counting rate for the selected mode, taken from that PLC's hardware manual.
The decision from these numbers: frequency matching, or a controller that compares two measured speeds and trims references, carries at least this order of standing error for as long as the load split is uneven. For one rigid common load that is not acceptable, and the fix is architectural, not a tuning exercise.
Master and torque follower for one common load #
Put the master drive in speed control and let it own the load's speed. Configure the slave in torque mode and feed it the master's torque reference, scaled so each motor contributes its intended share; the signal travels over an analog line or a drive-to-drive link, and the settings live in the drive's torque-control documentation under torque following or master-slave operation. Before designing around this, confirm that both installed drives actually offer a torque mode with a torque-reference input: the guide to what decides motor and drive compatibility works through that check.
The slave still needs a speed reference, set above the master's. Drive documentation for this architecture commonly quotes about 10% above the master's speed reference; treat that as architecture-specific and take the figure from the drive's own manual rather than a forum. The margin exists so the slave pulls into the load instead of coasting behind it while it delivers the commanded torque. One check belongs before the first run: verify the slave's active speed limit, because a torque-follower that loses its load accelerates until that limit stops it.
The master alone accelerates the common load, so its sizing has to cover the whole inertia and the breakaway torque, not half of them. The page on how to calculate motor starting time from torque margin and inertia shows how much margin a start consumes and how long the motor spends at elevated current.
Independent loads need their own speed loops #
Two independent loads that must run at the same speed get no help from torque following. Each drive closes its own speed loop, both receive the same speed reference, and acceptance comes from measured shaft speeds under load, not from identical parameter settings. Give the PLC the jobs it is good at: run, direction, reference selection and the coordinated stop that takes both drives down when one faults. If travel must stay aligned, a slow supervisory mismatch check in the PLC is reasonable, but the tight matching belongs in the drives, because a scan-based compare-and-trim only corrects between scans and will hunt against the drive loops.
The decision for each case #
| Case | Decision |
|---|---|
| One rigid common load | Master in speed control, slave in torque-follower mode with its speed reference about 10% above the master and its speed limit verified; the PLC issues run, direction, the master's reference and the coordinated stop |
| Independent loads, speed must match | Each drive on its own closed speed loop with a common reference; accept on measured speeds under load |
| Independent loads, travel must stay aligned | Position-level control or registration correction; speed matching alone leaves a growing offset |
A slow PLC supervisory check on the accumulated encoder counts is still worth keeping in every case: it catches a drive that has dropped out of torque mode or an encoder that has stopped counting, and it hands the fault to the coordinated stop rather than to a trim that cannot fix it.
Questions asked
Can one drive run both 4 kW motors instead of two drives?
Yes, for straightforward speed duty. Size the drive for the sum of both motor currents, start them together, and give each motor its own overload protection, because the drive's electronic overload sees only the total current and cannot protect an individual motor. This suits two motors running at one speed on one load; it does not provide load sharing control, and each motor still needs its own mechanical disconnect for service.
Why not let the PLC compare the two encoder readings and trim the speed references?
A scan-based trim can only correct between PLC scans, so it adds lag after every load step and can hunt against the drive's own speed loop. It also reacts to speed, while a travel-alignment requirement needs the accumulated count difference, which a speed trim never fully removes. Keep any PLC correction slow and supervisory, and leave the fast matching to the drives.
What speed reference does the torque-follower slave need?
Common drive-manual practice for this architecture sets the slave's speed reference about 10% above the master's, so the slave pulls into the load instead of coasting off it while it delivers the master's torque. Treat that figure as architecture-specific, not a universal setting: take the value from your drive's torque-control documentation and verify the slave's speed limit before the first run.