Replacing Drives on Old DC Servo Motors Without Sizing Errors
Short answer
Keep old permanent-magnet DC servo motors once the tag arithmetic and a meter agree: back EMF at top speed plus armature drop sets the terminal voltage, and one ambiguous resistance digit moves the required DC bus by tens of volts. Measure the winding four-wire and the supply with a voltmeter, then buy the drive those two readings name.

On this page
Keep the motors — after two meter readings, not before. Old permanent-magnet DC servo motors, even big NEMA 42 frames, run well on a modern PWM servo drive, but the drive is chosen by voltage and current arithmetic from the nameplate, never by frame size. On the motor in the worked example below, the terminal voltage at top speed comes out at 82.6 V on one reading of the armature resistance and 142 V on the other. That spread, together with the DC bus you actually have, decides which drive to buy. The sections below give the equation, the check that settles the ambiguous digit, and the decision for each case.
What the nameplate gives you #
Everything needed to size the drive is on the motor tag, provided you know what each line is for:
- Motor type — permanent-magnet DC servo motor. Brushed DC, mechanically commutated. It needs a DC servo drive, not an AC servo drive; the two families are not interchangeable.
- Max speed — 2000 rpm. The speed at which the back-EMF line matters, and the fastest this motor will ever legitimately turn.
- Torque — 565 in·oz. The rated torque, which pairs with the current line.
- Current — 11 A. Almost certainly the current that produces the rated torque; the cross-check below confirms that reading.
- Back EMF — 38 V per 1000 rpm. The voltage constant: the motor generates that much back EMF for every 1000 rpm of shaft speed.
- Armature resistance — tagged 6 ohms, with 0.6 ohm as the credible alternative. One ambiguous digit moves the required bus by tens of volts, so this line gets its own section below.
Treat the tag as claims to verify rather than gospel; one line of it is visibly ambiguous already. If your own tag is missing or half illegible, the same discipline applies as in identifying salvage robot servo motors before drive selection: establish what you have before buying anything for it.
The voltage equation that decides the drive #
For a permanent-magnet DC motor, the terminal voltage the drive must deliver is:
V = E + Ia × Ra
where V is terminal voltage, E is back EMF, Ia is armature current and Ra is armature resistance. Back EMF rises linearly with speed, so the worst case is top speed and the rated current at the same time; lighter load shrinks the resistive drop and lower speed shrinks E.
Worked example for the tag above — a calculated example for these inputs, not a measured result:
- Back EMF at top speed: 38 V/1000 rpm × (2000 rpm ÷ 1000) = 76 V.
- Resistive drop: the rated current through the winding resistance — 6.6 V on the low reading, 66 V on the high one.
- Terminal voltage: 76 V + 6.6 V = 82.6 V on the low reading; 76 V + 66 V = 142 V on the high one.
The DC bus must clear the terminal voltage plus the drive's own conduction drop, a few volts across a PWM bridge at this current. The table below turns the two readings into the bus class each one needs; a candidate drive whose documented bus window does not cover that class is the wrong drive, whatever its current rating says.
The two readings of one resistance #
On a tag like this the resistance line is the one that gets misread: a single decimal place separates the two candidate readings, and the consequences differ by a factor of ten in drop, heat and bus voltage. The tag's own numbers hint at which reading is right. Rated torque at rated speed is about 835 W of shaft power: 565 in·oz converts to 3.99 N·m, and 3.99 N·m × 209 rad/s ≈ 835 W. At the rated current the high reading burns 726 W of heat in the winding and the low reading burns 72.6 W, so the high reading would imply 835 ÷ (835 + 726) = 53 percent efficiency, while the low reading gives 835 ÷ (835 + 72.6) = 92 percent. As a class, permanent-magnet DC servos run well above 53 percent, so expect the low reading — then make a meter confirm it, four-wire, with the rotor stationary.
| Resistance reading | Armature drop at the rated current | Terminal voltage at top speed | Bus class for full speed |
|---|---|---|---|
| 0.6 ohm | 0.6 ohm × 11 A = 6.6 V | 76 V + 6.6 V = 82.6 V | about 90 VDC |
| 6 ohms | 6 ohms × 11 A = 66 V | 76 V + 66 V = 142 V | 150 VDC or more |
Both rows are calculated examples for the example tag, at top speed with the rated current flowing; they are arithmetic, not measurements.
The cross-check that settles the current #
For a permanent-magnet DC motor, the torque constant and the voltage constant are the same machine constant in different units: newton-metres per ampere equals volt-seconds per radian. So this tag can be checked against itself. Divide the torque line by the current line: 565 in·oz ÷ 11 A = 51.4 in·oz/A. Converted, that is 0.363 N·m/A, which is 0.363 V·s/rad, and 0.363 × 104.7 (the radians per second in 1000 rpm) gives 38.0 — matching the tag's 38 V/1000 rpm within rounding. The tag is self-consistent, and the current line behaves like the continuous rating that produces the rated torque, not a short-duration peak. Size the replacement drive's continuous current to meet that figure, and let its peak rating cover acceleration torque.
Feedback the new drive needs on the motor #
Drives of that vintage often closed the speed loop with an analog tachometer. A modern drive wants an incremental encoder on the motor, and the encoder input is part of the drive's compatibility list, so specify it before ordering:
- 5 VDC supply for the encoder electronics, with the drive able to source its current.
- Differential outputs — A, /A, B and /B, plus an index channel if the machine homes to one — for noise immunity along the motor cable; single-ended signals on a servo cable pick up counts from noise.
- An output circuit the drive input actually accepts, line driver versus open collector, and a line count that meets the positioning resolution the machine needs.
- A mount and a speed rating that survive the motor's top end: check the rear shaft diameter and stub length against the encoder kit's clamp.
Because the motor commutates mechanically, the encoder serves position and speed only; there is no commutation angle to set, unlike a brushless retrofit. Check frequency as well as resolution: 500 lines give 2000 counts per revolution in quadrature, and top speed is 33.3 rev/s, so 2000 × 33.3 ≈ 66,600 counts per second, about 67 kHz — a calculated example to compare against the drive's documented maximum encoder input frequency. Feedback type gates drive choice on AC servos too; the same discipline appears in selecting a replacement servo drive for resolver motors.
Measure the bus before you order #
'The old supply seems to work' is not data. Put a DC voltmeter on its output with the mains on and read the actual volts: a filtered supply sits near its rating, while a plain rectified supply reads lower on average and carries ripple. The replacement drive's documented bus window must cover the measured voltage with headroom above the terminal voltage the motor needs at the rated point. If the drive you choose makes its own bus from AC mains, this step disappears and the old supply is retired. Decelerating inertia also pushes energy back into the bus, so confirm the drive can absorb or dissipate regeneration on your axes.
One safety note: bus capacitors hold charge after the mains is off — treat the supply and drive as live until the machine is locked out and the terminals read zero volts on a meter.
The decision for each case #
- Winding measures 0.6 ohm and the bus reads in the 90 VDC class: keep the motors. Buy a four-quadrant PWM servo drive for permanent-magnet DC motors whose documented bus window covers the measured supply — 90 VDC clears the 82.6 V terminal requirement with a few volts of bridge drop to spare — whose continuous current rating meets the rated current, whose peak covers acceleration, and whose encoder input takes 5 VDC differential signals.
- Winding measures 6 ohms: the motor needs a 150 VDC-class bus or more to reach rated speed, because 142 V is committed before the bridge takes its share. If you can source that drive at the rated current, the motors stay. If the drives available to you top out below it, a 90 V class bus still delivers full torque but at about a third of rated speed; decide from the machine's cycle whether that is acceptable, or replace the motors. When the motors go, the keep-or-convert arithmetic, including when stepping down to steppers wins, is worked through for a brushed DC robot arm in keeping brushed DC servos or converting to steppers.
- Never decide from frame size. The NEMA 42 face means the mounting bolts line up; it says nothing about voltage, current or feedback.
Measure the winding, measure the bus, then buy the drive the arithmetic names — that order prevents every sizing error this motor can produce.
Questions asked
How do I get a trustworthy armature-resistance reading?
Lock out the machine, then measure four-wire between the armature terminals with the shaft held still. A two-wire handheld meter adds its own lead and contact resistance, often tenths of an ohm, which is the entire difference between the two candidate readings, and a spinning armature generates voltage that corrupts any ohm reading. Take the reading twice and compare.
Is the current line on the tag continuous or peak?
The tag cross-check says continuous: dividing the torque line by the current line gives a torque constant whose electrical twin matches the tag's voltage constant almost exactly, which is the signature of a steady rating. Choose a drive whose continuous current rating meets that figure and whose peak rating covers acceleration torque, and verify both numbers on the drive's own datasheet.
Can I keep the machine's original DC power supply?
Only if the new drive accepts a DC bus input and its documented bus window covers the measured output, checked both open-circuit and under load where you can load it. If the drive makes its own bus from AC mains, the old supply is retired and the check moves to the mains circuit. Either way, the drive's documented window is what the motor's terminal voltage has to fit inside.
What happens if the resistance really is 6 ohms and the bus is the 90 VDC class?
The motor runs, but not fast. At the rated current the winding consumes 66 V of the bus, leaving 24 V for back EMF, and 24 V at 38 V per 1000 rpm is about 630 rpm. You keep full torque at that speed; you lose roughly the top two-thirds of the speed range. Whether that matters depends on the machine's cycle, not on the motor.
Will an AC servo drive run a permanent-magnet DC motor?
No. An AC servo drive is built to commutate a three-phase machine: it synthesizes rotating currents and needs rotor-position feedback to do it. A brushed DC motor commutates mechanically, so it needs only a controlled armature voltage and current from a DC drive. The two drive families are not interchangeable, and no setting change converts one into the other.