Brushless servo motor overheating with no load: commutation first
Short answer
At rest with the axis enabled and zero command, a correctly commutated brushless servo is silent, still and draws near-zero current, so it cannot heat itself. Rapid no-load heating is therefore a commutation problem first: read standing current on the drive monitor, map the three U, V and W signals through all six orders one de-energized change at a time, confirm the motor's voltage rating from its nameplate, and only then review tuning and the drive's switching frequency.

On this page
- What a healthy axis does at rest
- The causes, cheapest to check first
- Map the three commutation signals before anything else
- The voltage question: read the nameplate, not the guess
- Worked example: what standing current costs in watts
- If commutation is right: tuning and switching frequency
- The decision, case by case
- Questions asked
A brushless servo motor that reaches untouchable temperature within minutes, with the ball screw disconnected and no load commanded, has an electrical cause, not a mechanical one. At rest — axis enabled, zero command — a correctly commutated brushless servo is silent, its shaft is still, and the drive's current monitor reads zero or a fraction of an amp. Near-zero current cannot heat a motor, so rapid no-load heating points at commutation first: the three U, V and W signals are telling the drive to energize the wrong stator winding at the wrong shaft angle, and the drive sits there pushing current into the motor without turning it. Measure standing current, map the commutation order across all six permutations, verify the motor's voltage rating from its nameplate, and only then touch tuning and switching frequency.
What a healthy axis does at rest #
Disconnecting the ball screw takes mechanics off the suspect list, so use that state as the test bench. Enable the axis with a zero command and read three things: your ears, the shaft and the drive's current monitor, which every servo drive shows on its display or in its PC tool.
- Silent: no hum, no singing, no ticking from the motor.
- Still: no shaft vibration or twitch.
- Near-zero current: a standing reading of zero to a fraction of an amp on a motor whose nameplate continuous current is measured in whole amps.
Standing current means the drive is forcing winding current while producing no motion and no useful torque, and every watt of it lands in the windings as heat. A correctly commutated axis cannot do this, because zero torque command demands zero winding current.
One split narrows the fault before you touch a wire. Most drives offer a torque mode; command zero torque and watch the current. If the current disappears at zero torque command but returns when the position loop closes, the drive is fighting itself through the loop — wrong commutation or bad tuning. If current or heat persists even at zero torque command, suspect the drive's output stage or a short in the wiring. If instead the shaft creeps or steps at zero command, that is a different signature, described in Diagnosing a Servo Axis That Jogs in Steps With Fluctuating Current.
The causes, cheapest to check first #
Order the suspects by what each one costs to confirm:
- Wrong U/V/W-to-phase order at the connector. Confirm with the standing-current test above and the mapping procedure below; it costs nothing but time.
- Feedback device mismatch — the wrong commutation tracks used, or a pole-pair setting that does not match the motor. Confirm against the drive's documented motor and feedback combinations, then run the drive's commutation-alignment procedure.
- Current-loop tuning or a zero-offset error. Confirm with the zero-torque split: tuning faults only show current once a loop is closed.
- PWM switching frequency set below what the winding needs. Confirm by raising it within the range the drive manual documents and comparing temperature rise over the same short cycle.
- A shorted output transistor feeding one winding continuously. Confirm with the motor leads removed at the drive: a healthy idle drive shows no current, and de-energized resistance checks show whether a winding is shorted to the frame.
Map the three commutation signals before anything else #
Commutation has to switch each stator winding at the correct shaft angle. Three signals — U, V and W — placed against three phases give six possible orders: U-V-W, U-W-V, V-U-W, V-W-U, W-U-V, W-V-U. Five of the six are wrong, and a wrong order holds current, vibrates and heats the motor with zero external load, exactly the symptom in front of you.
Work the orders in a fixed sequence:
- Photograph and label the existing wiring at the motor connector and the drive before changing anything, and never map signals by wire color, because colors are not standardized between makers.
- Make every change de-energized: lock the drive out, wait the bus-capacitor discharge time the drive manual specifies and verify zero volts on the bus before touching terminals. If the axis holds a vertical or counterweighted mass, block it first so nothing falls.
- Swap one order at a time, re-enable and command a short, slow move.
- After each order, check the same three things — silence, a still shaft, standing current at zero command — and stop immediately if rapid heating returns.
- Mark the order that passes on the motor, the cable and the drawing.
Two cases change the procedure. Some drives announce a phase problem themselves as a communication fault followed by an overload trip, which points straight at the phase wiring; that pattern is covered in Servo drive shows COM fault then overload: check U V W phasing first. Other drive families take commutation from the main feedback device after an alignment step instead of separate U, V and W tracks, so there is nothing to swap at the connector: run the drive's alignment procedure, and if the feedback device is not the one the drive expects, check the pairing rules first — they are laid out in Swapping a Servo Resolver for an Encoder: Commutation Rules.
The voltage question: read the nameplate, not the guess #
The bus reading of 300 VDC is a measurement. The motor rating of 150 V was a belief; take the real value from the nameplate or the motor's documentation before it drives any decision. Then apply the physics: winding heat is current squared times resistance, and the drive's current loop regulates winding current whatever the bus sits at, because at rest there is no back-EMF to fight. A doubled bus voltage does not double the heat. What a voltage mismatch between motor and drive threatens is winding insulation and the validity of the pairing, not the minutes-scale heating you are chasing.
Decide it this way: if the nameplate shows the voltage class inside the motor range the drive's documentation lists, cross the voltage question off and stay on commutation. If the nameplate really shows a lower class than the drive's documented motor family, do not run that pair until it is matched. How to tell an AC machine from a DC one and match supply classes to an axis is covered in Servo Motor Voltage Selection: AC or DC for Your Axis.
Worked example: what standing current costs in watts #
Illustrative values only — take your own from the nameplate, a meter and the drive monitor:
- Nameplate continuous current: 5 A.
- Line-to-line winding resistance, measured cold across two phase wires: 2.0 Ω.
- Standing current, axis enabled at zero command: 4.8 A.
- Expected standing current with correct commutation: near zero; a working rule of thumb is under about two percent of the nameplate rating, 0.1 A here.
Winding heat at that standing current: P = I²R = 4.8² × 2.0 Ω ≈ 46 W, continuously, with the shaft stopped and nothing moving air. With correct commutation: P = 0.1² × 2.0 Ω = 0.02 W. The wrong order puts roughly two thousand times more heat into the housing — which is why the case goes untouchable in minutes, and why the bus voltage number never entered the calculation.
The decision this example encodes: a standing reading anywhere near the drive's torque-limit current is commutation or feedback, not tuning. A standing reading near zero, with heating only under motion, points to tuning or switching frequency instead.
If the machine carries identical axes, comparing standing current across all of their motors finds the odd one out in minutes; a separate page walks through diagnosing current imbalance across every motor on a service.
If commutation is right: tuning and switching frequency #
With the order confirmed and standing current near zero, any remaining heat appears while the axis moves or holds position, and the suspects are the loop and the switching stage.
Reset tuning before diagnosing it: load the drive's default or a conservative gain set, command gentle moves with low acceleration and climb from there. An axis that heats while hunting around a stationary target is a loop fighting its own noise. An axis that runs away while you tune it has a feedback-sign or commutation problem first; the pattern is described in Why a Servo Axis Runs Away During Tuning.
Then the switching stage. The drive chops the bus voltage into the windings at a set frequency, and every chop leaves triangular ripple on the winding current; ripple is heat in proportion to its square, stacked on the commanded current. Find the switching-frequency setting among the drive's parameters and set it where the drive manual recommends for your winding's measured inductance — low-inductance windings need the upper end of the documented range. Raising it within that range either removes the extra heat over the same cycle or clears the switching stage as a suspect.
The decision, case by case #
- Rapid heating at rest with standing current near the torque limit: stop running and map the commutation order; the sequence above fixes it.
- Order corrected, axis silent, still and cold at rest: mark the wiring and return the axis to service.
- Order confirmed correct, standing current near zero, heat only under motion: reset to conservative gains, raise the switching frequency to the documented value for your winding and re-test over the same cycle.
- Current or heat present at zero torque command with the motor leads removed: the fault is in the drive's output stage; the motor is the victim, not the cause.
- Nameplate voltage class outside the drive's documented motor range: do not run the pair until matched — and fix commutation first either way, because the heat follows winding current, not bus volts.
Questions asked
How do I tell whether a brushless servo motor is AC or DC?
You usually cannot tell from the case, because both types are permanent-magnet machines with three-phase windings; the difference is naming convention and the drive's commutation waveform, not something a meter reveals. Read the nameplate instead: rated voltage, continuous and peak current, and the feedback device type. Then check the drive's documentation for the motor families it is built to commutate. A drive and motor whose nameplate data and feedback type both fall inside the drive's documented range are a compatible pair on paper.
Why does the drive show no fault while the motor gets hot?
Because the drive protects itself, not the motor. The current loop happily regulates to whatever the torque limit allows, and most drives only trip on overcurrent spikes, feedback loss or their own heatsink temperature. A mis-commutated axis stays inside all of those limits while cooking the windings. If the motor carries a thermal contact in its connector, wire it to the drive and enable the motor-temperature trip; that is the protection this axis is missing.
Can a wrong commutation order damage the motor?
Yes, through heat rather than voltage. A mis-commutated axis at rest can hold current near the drive's torque limit continuously, and winding insulation ages faster with every sustained temperature rise; a common rule of thumb gives roughly half the insulation life for each additional 10 degrees Celsius. Minutes at that level are enough to make the case untouchable. Map the commutation order before running the axis again, and treat any return of rapid heating as a stop.
Does a 300 VDC bus explain the heating on a motor believed to be rated 150 V?
Only indirectly. The current loop holds winding current regardless of bus voltage, so the extra volts do not add heat at rest. They do matter twice: as insulation stress on a motor wound for a lower class, and as taller voltage steps at every chop when the switching frequency is low, which increases current ripple and its heat while current flows. Verify the nameplate against the drive's documented motor range, fix commutation first, and raise the switching frequency within its documented range.