Running a Permanent Magnet DC Servo Motor on a DC Drive
Short answer
Yes: a permanent magnet DC servo motor runs on a conventional armature-controlled DC drive, but only with the drive's internal field function switched off (P82 = 0 on the 6RA70 family), the shaft mechanically locked before armature current-controller optimization (P51 = 25), and speed-controller optimization (P51 = 26) run afterward. A PM motor keeps its field, so an unsecured shaft can run away during tuning.

On this page
- Can a conventional DC drive run a permanent magnet DC servo motor at all?
- Why does the drive's field section have to be switched off?
- Why must the shaft be locked before current-controller optimization?
- Which optimization runs do you use, and in what order?
- Does the drive's rating fit a PM servo motor, and how do you check it?
- What else changes when an analog DC drive is replaced on a servo axis?
- How do you confirm the axis is safe to release to production?
- Questions asked
A permanent magnet DC servo motor runs on a conventional armature-controlled DC drive such as the 6RA70 family, and plants do this routinely when replacing old analog DC drives without changing the motors. Two settings and one physical precaution decide whether the commissioning goes cleanly: the drive's internal field function is switched off with P82 = 0, the motor shaft is mechanically locked before the armature current-controller optimization (P51 = 25), and the speed-controller optimization (P51 = 26) runs afterward. Skip the shaft lock and a permanent magnet motor can run away during tuning, because unlike a wound-field spindle motor its field is always present.
Can a conventional DC drive run a permanent magnet DC servo motor at all? #
Yes, provided the drive is configured for armature control only and the field section is taken out of the application. A permanent magnet servo motor is, from the armature's point of view, an ordinary DC motor: controlled armature voltage gives controlled speed and torque. The difference sits in the field. A conventional DC drive assumes a wound field it excites and monitors itself; a PM servo motor has no field winding to excite, because the flux comes from magnets. So the drive works fine as an armature controller and must simply be told that its field circuit is unused. This is the same compatibility logic as matching any old DC motor to a new drive: voltage class, current rating and feedback arrangement decide the fit, as covered in old servo motor and new drive compatibility.
Why does the drive's field section have to be switched off? #
Because a permanent magnet motor has no field winding to control, and leaving the field function active produces faults and wrong optimization behavior. On the 6RA70 family the setting is P82 = 0, which configures the application for permanent-field motors with the internal field function not used. With the field section active, the drive would try to establish and monitor a field current that cannot exist, and optimization runs that depend on a measured field would not complete meaningfully. Set P82 = 0 before you run any optimization. Note what this setting does not do: it configures the field function, it does not verify the armature circuit wiring, the motor ratings or the direction of rotation, and those checks stay on your commissioning list.
Why must the shaft be locked before current-controller optimization? #
Because a PM motor has full field during that run, and every armature current step the optimization injects produces real torque. During the current-controller optimization the drive measures the armature circuit by stepping armature current. On a separately excited spindle motor, the field current is held near zero during this run, so there is almost no torque and the motor sits still. A permanent magnet motor has no field current to reduce; the magnets supply full flux at all times. Any armature current therefore makes torque, and with an unsecured shaft the motor accelerates the moment the optimization starts. Mechanically lock or block the shaft before you start P51 = 25. This is the physical version of the tuning-runaway mechanism described in a servo axis running away during tuning: the loop drives current into a motor that is free to move.
Which optimization runs do you use, and in what order? #
Two runs, in a fixed order: armature current-controller optimization with the shaft locked, then speed-controller optimization with the machine coupled. On the 6RA70 family these are selected through the commissioning parameter P51:
- Confirm P82 = 0 and physically lock the motor shaft.
- Run P51 = 25, the optimization of precontrol and the armature current controller. This sets up armature current control only; it does nothing to a field loop, which is correct for a PM motor.
- After it completes, release the shaft lock, couple the machine, and run P51 = 26, the speed-controller optimization.
The manufacturer's documentation for this drive family states that the current-controller run can execute without a motor or load, while the speed-controller run and the remaining optimization runs require a load coupled to the drive. The field-weakening run and the other field-related runs have no role in a permanent magnet application. Two runs, nothing else needed.
Does the drive's rating fit a PM servo motor, and how do you check it? #
The drive's rated armature DC output voltage must exceed the motor's rated armature voltage, and its continuous armature current must exceed the motor's rated current. The check uses the drive's line voltage, because an armature converter fed from a line of RMS voltage U produces a maximum mean DC output of about 1.35 × U at full firing.
Worked example with illustrative nameplate values (make the check with the real values from your motor's plate and your drive's rating plate): a PM servo motor rated 220 V armature, 15 A continuous, on a 6RA70-style drive fed from a 400 V line gives a maximum mean DC output of 1.35 × 400 V = 540 V, comfortably above the motor's 220 V rating, and a drive with a continuous armature current rating of 30 A covers the 15 A motor with roughly two to one margin.
The same drive on a 230 V line would reach only about 1.35 × 230 V = 311 V, still above 220 V but with far less headroom for the armature voltage drop across the converter, so a low-line installation deserves the arithmetic before you order. Take every actual figure from the nameplate of the exact motor and the rating plate of the exact drive; the numbers here are an example of the method, not a rating.
What else changes when an analog DC drive is replaced on a servo axis? #
Three things deserve attention beyond the two optimization runs. First, speed feedback: analog DC drives often used a tachometer, and the new drive must be configured for whatever feedback the motor carries, with signal names matched between motor and drive the way encoder interface compatibility describes.
Second, zero-speed behavior: a PM servo holding a load, such as the rope-tensioning duty in a threading application, needs a working drive-disable path so the axis does not drift when operation enable drops; the drive manufacturer's guidance on avoiding speed drift addresses disabling through the operation enable input and the corresponding bit in control word 1. Third, direction and reference polarity: reversing armature polarity conventions between the old and new drive flips the axis, so prove direction at low speed with the machine able to stop. For the broader four-point fit check between a motor and a drive, matching a servo drive to a motor walks through it.
How do you confirm the axis is safe to release to production? #
Confirm three conditions with the guards closed and nobody in the machine envelope: the field function still reads as disabled, the motor does not rotate when operation enable is removed, and the axis holds position under the machine's normal load. Run the speed-controller optimization only with the mechanism coupled and the area clear, and treat the shaft-lock rule as absolute: no current-controller optimization run on a permanent magnet motor with a free shaft. Then jog the axis through its full travel at reduced speed, verify direction, and only after that hand the drive over. This commissioning proof is your verification of the application; it is not a substitute for the machine's own risk assessment and applicable safety standards.
Questions asked
What does P82 = 0 actually change inside the drive?
It tells the drive the motor has no separately excited field winding, so the drive's field converter output and field-current monitoring are taken out of the application. The drive then controls armature voltage and armature current only, which is exactly what a permanent magnet motor needs, because its field comes from the magnets on the rotor.
Why can the motor run away during current-controller optimization if I forget to lock the shaft?
The current-controller optimization injects armature current steps to measure the armature circuit. On a spindle motor with a wound field, the field current is held near zero during that run, so there is almost no torque. A permanent magnet motor always has full field, so every current step produces real torque and the shaft accelerates the moment current flows.
Do I need any optimization run other than current controller and speed controller?
For a permanent magnet motor on a 6RA70-style drive, no. Field-weakening optimization applies only to motors with a wound field, and EMF-dependent runs assume a measurable field. The current-controller run with the shaft locked, followed by the speed-controller run with the machine coupled, covers the tuning this application needs.
Can I commission with the motor uncoupled from the machine?
For the current-controller run the shaft must be physically blocked regardless of coupling. For the speed-controller run the manufacturer's documentation states that the drive needs a load coupled to it, so commission that step with the motor connected to the mechanism it drives, or with an equivalent mechanical load.