Second encoder on a servo motor: output before NDE shaft extension
Short answer
For a spare motor-position channel on a DRIVE-CLiQ servo motor such as a 1FT7, use a drive-side module that emits an incremental TTL signal: an encoder splitter has no pulses to split, and no NDE second encoder appears among the documented 1FT7 options. Fit a second physical encoder only when the second system must measure independently or see the load.

On this page
- Does the second system need a copy of motor motion or an independent measurement?
- Why can't an encoder splitter feed a second system on a DRIVE-CLiQ motor?
- Which module supplies an incremental TTL signal to a third-party system?
- What pulse frequency must the receiver accept at your speed and resolution?
- Does the second system need motor position or load position?
- Does a spare output count as a safety channel?
- When is a second physical encoder justified, and what must the documentation show?
- Questions asked
For a Siemens 1FT7 servo motor — take 1FT7108-5SF70-1BG0 as the example — a spare motor-position channel for a second system is an electrical output derived from the drive, not a second encoder on a shaft extension at the non-drive end. A DRIVE-CLiQ motor sends no encoder pulses down its cable, so an encoder splitter has nothing to fan out; the documented route is a TM41 module that outputs an incremental TTL signal for the third-party system. A second physical encoder earns its place only when the second system must keep measuring after the first encoder fails, or must see the load instead of the motor. Below is the decision order, the frequency arithmetic and the mechanical checks, ending with the choice for each case.
Does the second system need a copy of motor motion or an independent measurement? #
A copy of motor motion needs only a derived electrical output, while a measurement that must survive failure of the motor's own encoder needs a separate sensor — this one question decides the whole selection.
An encoder converts shaft movement into position information. A second encoder is a second measuring device; a second output derived from the encoder already inside the motor is another interface to the same measurement. Both deliver position while everything is healthy, but they fail differently: anything upstream of a derived output — the encoder itself, its processing inside the drive, the drive's operating state — takes the derived output down with it.
So write down two things before touching hardware. First, the receiving equipment's input specification: the electrical interface it accepts, the position content it needs, its input frequency limit and its supply. Second, the functional requirement in one sentence, as information sharing or as independent measurement. "Another system must see this axis moving" is sharing. "Another system must hold a usable position after this motor's feedback fails" is independence, and only a separate sensor meets it.
The three candidates and the reading that decides each:
| Candidate | The reading that decides it | Decision |
|---|---|---|
| TM41 output module | Module compatibility in the installed drive configuration; the receiver's accepted interface and frequency limit | Choose for a copy of motor motion on a DRIVE-CLiQ motor |
| Encoder splitter | The motor's actual encoder interface and the splitter's input and output specifications | Valid only on conventional incremental interfaces; reject on DRIVE-CLiQ |
| Separate physical encoder | Required independence or a load-side measurement point; a documented motor option with a dimensional drawing | Choose only for independent measurement or load position, against documented options |
Why can't an encoder splitter feed a second system on a DRIVE-CLiQ motor? #
Because a splitter can only fan out pulses, and a DRIVE-CLiQ motor never puts pulses on its cable: the encoder communicates with the drive as digital data, so there is no signal to split.
On a conventional incremental interface — TTL, HTL or a 1 Vpp sinusoidal signal — a splitter or signal distribution module can serve a second reader. Even there it needs care: every added receiver loads the lines and can degrade amplitude, edge quality and noise immunity, so use a purpose-designed distribution device that preserves the drive's own feedback path and matches each receiver. A Y-cable is not a splitter.
Before assuming which case you are in, identify the actual feedback interface from the motor nameplate, the order code and the drive's encoder configuration — the same discipline as matching encoder signal names between motor and servo drive. On a DRIVE-CLiQ motor that reading ends the splitter branch: the encoder data is serialized for the drive, the same property that lets you swap an identical DRIVE-CLiQ servo motor without reconfiguration, and it leaves nothing on the cable for a splitter to fan out.
Which module supplies an incremental TTL signal to a third-party system? #
The TM41: the SINAMICS S120 Function Manual, Drive Functions, documents that it outputs incremental encoder signals in TTL, and the S7-1500T axis functions describe its output as an emulated axis position that behaves like an incremental encoder.
TTL names the electrical signal class — transistor-transistor logic levels — not a complete position interface. Confirm the channel arrangement, direction convention and supply against the receiver's input specification, and take resolution and frequency behavior from the module documentation, never from the motor model. The signal source is chosen with parameter p4400; the function manual documents that with p4400 = 0 the signals are generated from a speed value supplied in a process data word, and it lists the remaining source settings.
Two readings decide this branch:
- Hardware compatibility for the module in your installed drive configuration, stated explicitly in the drive documentation. Absent that, this branch is dead.
- Output against receiver, figure by figure from both documents: signal levels, channel functions, direction convention, resolution and frequency range. The frequency comparison is arithmetic — the next section does it.
Also read the documented behavior at initialization and on loss of the upstream feedback. The emulated output lives inside the drive's processing and inherits that state machine, and a receiver that needs absolute position cannot substitute incremental movement without a reference strategy.
What pulse frequency must the receiver accept at your speed and resolution? #
The line frequency equals resolution times speed: at 2048 increments per revolution and 3000 rpm the output runs at 102.4 kHz, so the receiver's documented input frequency limit must sit above that figure.
A calculated example with illustrative inputs — not values from any datasheet:
- Inputs: emulated resolution 2048 increments per revolution; axis peak speed 3000 rpm.
- Convert the speed: 3000 rpm ÷ 60 = 50 revolutions per second.
- Line frequency: 2048 × 50 rev/s = 102,400 Hz = 102.4 kHz.
- Granularity: one increment spans 360° ÷ 2048 ≈ 0.176° of motor rotation.
The decision: the receiver's datasheet limit must exceed 102.4 kHz at the top speed, and the increment size above must satisfy the second system's granularity requirement. If either fails, lower the emulated resolution — each increment coarsens in proportion — or restrict the speed at which the second system must track. One caution when comparing: check whether the receiver states its limit as a line frequency or as a decoded count rate, because quadrature decoding multiplies transitions; compare like with like. All figures here are calculated for the example inputs, not measured results.
Does the second system need motor position or load position? #
A motor-side encoder — the internal one or a second one on the NDE — sees only the motor shaft: belt stretch, gearbox backlash and coupling wind-up between motor and load are invisible to it, so load position needs a load-side sensor.
The TM41 output is that same shaft seen again: the axis position as the drive knows it. That is exactly right when the second system monitors or mirrors axis motion — a display, a tracking calculation, another axis synchronized to this motor. It is wrong when the second system measures a process result such as cut length, print registration or end-effector position, because everything between motor and tool sits outside the measurement. Put the measurement point after the last compliance element the process cares about: motor position takes the TM41 path; load position takes an encoder on the load, wired to the second system directly, which removes the motor from the question entirely.
Does a spare output count as a safety channel? #
No: the internal encoder and the TM41 output share one measuring device and one processing path, so for functional safety they are a single channel, and no architecture credit arises from having two readers.
Safety functions — safe position behind a guard, safe speed at an interlocked gate — get their architecture from ISO 13849-1 or IEC 62061 together with the machine's risk assessment per ISO 12100, built from validated components. A spare monitoring output is none of those, and this article is a selection guide, not a safety validation.
When is a second physical encoder justified, and what must the documentation show? #
Only for independent measurement or a different measurement point, and only against a factory-documented option: 1FT7 options are selected in the order number, and an arrangement missing from the option list cannot be added to a motor you already own.
The 1FT7 operating instructions show the pattern: for connection with the M17 round connector, one of the options Q17, N16 or N40 must be selected in the motor's order number. A factory second encoder or an NDE shaft extension would have to appear the same way — as an option against the complete order code, with a dimensional drawing. The SIMOTICS S-1FT7 configuration manual is the authority for that list; the documentation available for this article lists no such option, so treat the NDE route as unavailable for the example motor unless the manufacturer confirms it in writing for the complete order code — and for a spare channel you should not be asking at all.
If a documented arrangement exists for your motor, clear four checks before ordering:
- Shaft geometry and mounting face against the encoder's mounting requirements, taken from the dimensional drawing.
- Clearance and cable routing that maintain the motor's degree of protection — an added connector or gland must not downgrade the enclosure.
- Mounting discipline: the operating instructions require parts on a shaft extension to run without runout and thrust, and an added encoder coupling gets the same treatment, because misalignment loads the encoder bearings and coupling movement shows up directly as measurement error. Connect the encoder through a flexible shaft coupling specified for encoder service.
- Nothing undocumented: reject any arrangement that needs changes to the motor housing or shaft.
The decision for each case:
- Spare channel, a copy of motor motion, DRIVE-CLiQ motor: the TM41 TTL output. Splitter rejected, NDE encoder unnecessary.
- Independent measurement that must survive encoder or drive failure: a separate sensor — NDE only where the option list documents it, otherwise load-side or a different approved motor configuration.
- Load position: an encoder on the load, wired to the second system.
Questions asked
What happens to the emulated output after a power cycle?
The output behaves like an incremental encoder signal, so it reports changes of position, not an absolute angle. After a drive restart the third-party system must re-establish its reference, with a homing move or a set command, before it can trust absolute positions. Read the documented startup behavior of the output module and give the receiver a defined reference strategy; any incremental encoder imposes the same limitation.
How long can the TTL cable from the output module to the receiver be?
TTL is a single-ended, noise-sensitive signal class, and neither document quoted here gives a cable-length rating, so take the limit from the module and receiver datasheets. As a rule of thumb, not a rating, keep single-ended TTL runs to a few meters, use shielded twisted pairs, and ground the shield at the end the receiver's documentation names. Longer runs belong on a differential connection or a fieldbus.
Which resolution should the emulated output use?
The coarsest one that still meets the receiver's needs, because resolution sets granularity and frequency together. One increment spans 360 degrees divided by the increments per revolution: about 0.35 degree at 1024 and 0.088 degree at 4096. Doubling the resolution doubles the frequency the receiver must accept, so a fine resolution only works at lower speed or on a faster input.
Can the third-party system read the DRIVE-CLiQ signal directly?
No. DRIVE-CLiQ is the digital interface between the motor's encoder and its drive, and no third-party system has a documented way to join that link. It takes its position from the drive side instead: the emulated encoder output described in this article, or a fieldbus connection if the system supports one. Tapping the motor cable is not an option, because there are no pulses on it to read.