Setting a stepper drive to 200 steps per revolution

Servo and stepper motion Published 8 min read By AutomateDirectUSA engineering team

Short answer

Yes. 200 steps per revolution is the drive's full-step point: set it in the drive's resolution setting, power-cycle, then divide the controller's pulse scaling constant by 100, because 20,000 divided by 200 equals 100. Skip that division and the axis travels a hundred times the commanded distance; full step buys pulse-rate headroom and gives up microstep smoothness and command resolution.

On this page
  1. Can a drive set for 20,000 steps per revolution be changed to 200?
  2. Where does the steps-per-revolution setting live on the drive?
  3. How do you change the drive to 200 steps per revolution?
  4. What happens to the controller's scaling when the drive resolution changes?
  5. How much pulse rate does full-step resolution give back?
  6. What does full-step operation cost in smoothness and accuracy?
  7. How do you verify the axis after the resolution change?
  8. Questions asked

A drive that reports 20,000 steps per revolution can be set to 200: that value is the motor's full-step point, the resolution every microstep setting subdivides, and it heads the switch-selected resolution tables published for the SureStep family. On the STP-DRV-80100 in this setup the resolution is software-set — Motion Pro reads and writes the drive's steps-per-revolution value — so the change happens where you are already looking, followed by one division in the controller: 20,000 / 200 = 100, and the controller's pulse scaling constant must be divided by 100. Skip that division and the axis travels a hundred times the commanded distance. This article shows where the setting lives, the change procedure, the rescaling arithmetic worked through for a 5 mm lead screw, the pulse rate you get back, and what full step costs.

Can a drive set for 20,000 steps per revolution be changed to 200? #

Yes — 200 steps per revolution is the drive's full-step point, the native 360° ÷ 200 = 1.8° step, and on the SureStep STP-DRV-80100 you select it in Motion Pro in place of the 20,000 steps per revolution the software reports now.

Every microstep setting is an electronic subdivision of that same physical step, so the full-step point exists on every stepper drive whatever its ceiling; the previous setting cuts the same 1.8° into 0.018° pieces. The switch-selected resolution tables in the SureStep user manual list full step and half step as the base entries, with higher ceilings elsewhere in the family — take the table for your exact part number from that manual rather than borrowing a sibling model's ceiling.

Where does the steps-per-revolution setting live on the drive? #

It lives in one of two places: a DIP switch bank on switch-configured drives — on the EM542S the microstep selection is switches SW5 through SW8, per that drive's manual — or a resolution setting in configuration software such as Motion Pro on the STP-DRV-80100.

If a model offers both sources, find in its manual which one the drive honors before editing anything; a switch bank left at an old position can override or be overridden depending on the design. Drives of this class read the switch bank at power-up, so a switch change takes effect only after a power cycle. Software settings must be downloaded to the drive and survive in non-volatile memory — power-cycle and re-upload to prove the value stuck rather than living only in the editor.

How do you change the drive to 200 steps per revolution? #

Record the working configuration, set the resolution entry to 200 steps per revolution — the drive's full-step point — power-cycle, re-upload to prove the value persisted, and apply the matching division to the controller's pulse scaling constant before the first powered move.

  1. Record the working configuration. Upload from the drive and save the current Motion Pro configuration file before editing anything; note the running current, the idle-current reduction and any anti-resonance or damping value so they can be restored.
  2. Set the resolution. In software, change the drive's steps-per-revolution setting to the full-step value and download it to the drive. With a switch bank, remove control power, set the switches to the full-step combination printed for the model in its manual, and restore power.
  3. Power-cycle and prove persistence. Re-upload and confirm the drive now reports the full-step resolution. Drives of this class latch the switch bank at power-up, so cycle power even after a switch change; the re-upload is what proves a software setting reached non-volatile memory.
  4. Re-check the motor current. Resolution and current are independent settings — set the resolution as needed and the current to the motor's rated value — but a stale configuration file can overwrite both, so confirm running and idle current after any download.
  5. Rescale the controller. Apply the division worked out in the next section to the controller's pulse scaling constant before any powered move.
  6. Confirm pulse timing once. Changing resolution does not relax the drive's minimum step pulse width or its direction setup-and-hold times; check the controller's output pulse width against the timing values in the drive manual.

What happens to the controller's scaling when the drive resolution changes? #

Every pulse becomes 100 times larger in angle, so the controller's pulses-per-revolution constant must drop by the same factor of 100: leave it alone and a commanded 100 mm move travels 10,000 mm instead.

The constant is pulses per millimeter of load travel, and setting it from scratch is the same arithmetic as calculating step and direction servo pulse scaling.

Worked example — calculated values for these inputs, not a measured result: 5 mm lead ball screw, direct-coupled, commanded move of 100 mm, drive changed from 20,000 steps per revolution to full step.

  • Previous constant: 20,000 steps per revolution ÷ 5 mm per revolution = 4,000 pulses per mm. The move sends 100 mm × 4,000 pulses per mm = 400,000 pulses.
  • New constant: 200 steps per revolution ÷ 5 mm per revolution = 40 pulses per mm. The same move sends 100 mm × 40 pulses per mm = 4,000 pulses.
  • Correction: 20,000 ÷ 200 = 100, and 4,000 pulses per mm ÷ 100 = 40 pulses per mm — divide the old constant by the resolution ratio.
  • Left alone, those 400,000 pulses produce 400,000 ÷ 40 pulses per mm = 10,000 mm of travel, and at the same pulse rate the shaft spins 100 times faster than the profile intends.

With a belt or gearbox between motor and screw, the reduction multiplies into the numerator: constant = (steps per revolution × motor-to-load reduction) ÷ millimeters of load travel per revolution. Behind a 3:1 reduction, (200 × 3) ÷ 5 = 120 pulses per mm. The same travel-per-revolution bookkeeping governs a pulley retrofit — see servo pulley ratio and travel per revolution in a retrofit.

An uncorrected constant is the classic cause of an axis that lands a fixed multiple away from the target — the failure documented step by step in why a stepper axis travels 1.25 times the commanded distance.

How much pulse rate does full-step resolution give back? #

Pulse rate falls by the same ratio as the resolution itself: holding 300 RPM needs 100 kHz at the previous setting but only 1 kHz at full step, because pulse rate in hertz equals steps per revolution times RPM divided by 60.

Shaft speed Pulse rate at the previous resolution Pulse rate at full step
60 RPM 20 kHz 200 Hz
300 RPM 100 kHz 1 kHz
600 RPM 200 kHz 2 kHz

To see what that buys, take an illustrative controller output ceiling of 10 kHz — an example number used to show the method, not a rating of any module. At the previous resolution that output turns the shaft at 10,000 × 60 ÷ 20,000 = 30 RPM. At full step the same output covers 10,000 × 60 ÷ 200 = 3,000 RPM, a ceiling the motor's speed-torque curve will cut far below: the pulse generator is never the true speed limit, the curve and the load are. A controller-side ceiling like that behaves exactly as described in why a closed loop stepper will not move above 200 kHz — past the maximum step rate the hardware can clock, the axis simply will not run the commanded speed.

What does full-step operation cost in smoothness and accuracy? #

Full step costs resolution, not torque: each pulse jumps 1.8° instead of 0.018°, low-speed motion gets rougher and louder, mid-speed resonance becomes more likely, and holding torque stays exactly what the drive current provides.

On the example screw, one pulse at full step moves the table 5 mm ÷ 200 = 0.025 mm, against 5 mm ÷ 20,000 = 0.00025 mm before — a machine commanding increments smaller than 0.025 mm loses the ability to land on them. Microstepping exists precisely to smooth the stepping response — the SureStep documentation describes the drives' advanced microstepping as smoothing motor motion and stepping response — and full step hands that smoothing back. Keep acceleration ramps in the profile, avoid steady operation in the speed band where the axis rings, and restore any anti-resonance setting recorded before the change.

Accuracy is a separate point: microstepping buys command resolution and smoothness, not better mechanical step accuracy — the rotor's placement error does not shrink because the command got finer. Torque does not move either: it is set by the drive current and the speed-torque curve, so expect no gain from full step.

Decision: choose the coarsest resolution that still resolves the machine's smallest commanded increment inside the pulse budget. If 0.025 mm per pulse is too coarse on the example screw, 2,000 steps per revolution is the first compromise — 360° ÷ 2,000 = 0.18° per pulse, 5 mm ÷ 2,000 = 0.0025 mm per pulse, and 2,000 × 300 ÷ 60 = 10 kHz at 300 RPM: ten times finer than full step while asking a tenth of the pulse rate the previous setting demanded.

How do you verify the axis after the resolution change? #

Uncouple the load, mark the shaft, command one revolution at low speed and count: the shaft must stop at exactly one marked turn, and a commanded 100 mm must measure 100 mm on the scale or dial indicator.

Run these checks with the load uncoupled or the axis disabled — until the scaling is proven, the machine can move a hundred times the commanded distance at full pulse rate, which is an unexpected-motion hazard.

  • Command one revolution at low speed: the marked shaft must stop at one turn, which proves the drive side.
  • Command the same move in the opposite direction and confirm direction is unchanged.
  • Command the reference move against a dial indicator or scale: measured travel must equal the command, and the output must send the corrected pulse count from the worked example, which proves the controller's constant.
  • Sweep the speed range under load, watching for stalls or ringing in the resonant band, then restore the recorded anti-resonance and idle-current settings.

If the measured distance is off by a consistent multiple, the constant is wrong, not the drive — recheck the division before touching anything else.

Questions asked

Which resolution ceilings do the SureStep switch-selected models publish?

The switch-selected resolution tables for the SureStep family list 200 (full step) and 400 (half step) as the base entries, up to 20,000 steps per revolution on the -4845 and -6575 drives, and up to 25,600 steps per revolution on the -4830. Those ceilings belong to those models; take the table for your own part number from the SureStep user manual.

Can two drives on the same motor run different resolutions?

Yes. Resolution is a setting stored in the drive, not a property of the motor: the motor supplies the same 200-full-step circle and each drive subdivides it electronically. Two identical machines can therefore run different resolutions side by side, provided each controller's pulse scaling constant matches its own drive.

Why does the motor still stall near the same speeds at full step?

Because the speed-torque curve does not move with the resolution setting — available torque at a given speed comes from the winding current and the motor's characteristics. What changes is the resonance picture: full-step excitation makes mid-speed resonance dropout more likely, so a stall can appear earlier in the resonant band even though the torque available is unchanged.

Does an encoder on the motor need rescaling after the change?

No. Encoder feedback and the step command are two separate scales: the encoder defines actual position in counts per revolution, while the drive's resolution defines command pulses per revolution. Rescale the command side of the controller only and leave the encoder scale alone; otherwise the position display reads correctly while commanded motion is off by the same factor as the resolution change.

Keep reading

  • Comparison

    A step and direction servo drive versus an open-loop stepper

    A step and direction servo drive takes the same pulse train as an open-loop stepper drive but closes the position loop inside the drive on the motor's encoder counts, so lost steps become a following-error fault instead of silent drift. The deciding arithmetic is the pulse budget: steps per inch times feed gives the steps per second your controller must supply, and a high-count encoder can exhaust that budget before the motor runs out of torque.

    Servo and stepper motion

  • Explainer

    Servo Positioning Resolution Versus Stepper Step Angle Explained

    A 0.018° move needs 360 ÷ 0.018 = 20,000 usable feedback counts per revolution, which come from the encoder and the drive's decoding and scaling, not from the servo label. Matching 3,000 command pulses per revolution on a stepper and a servo only matches command scaling; short-time overload capacity and high-speed performance still differ.

    Servo and stepper motion

  • Troubleshooting

    Why a Closed Loop Stepper Will Not Move Above 200 kHz

    The axis sits dead because the kernel exceeds the drive's documented step input limit, making each high or low state narrower than the input can latch. Set the kernel to half the ceiling, derive steps per mm from the drive's command resolution divided by the screw's travel per revolution, and verify the encoder A-channel polarity at the drive terminals.