What Decides a SIMODRIVE 611A and 1FT5 Motor Upgrade
Short answer
A SIMODRIVE 611A and 1FT5 upgrade is decided by four records you make before choosing hardware: the upstream controller's command interface and its scaling, where the position loop closes, the continuous torque the real motion cycle demands, and the cabinet's supply and braking-energy path. Siemens lists the 611A as a spare-part-only item, so select drive and motor as one matched package against those records.

On this page
- Record the designation before you order anything
- What the upstream controller decides
- Find where the position loop closes
- Size the motor on continuous torque from the real cycle
- Check feedback and commutation as part of the package
- Cover supply, braking energy and stopping in the cabinet
- The decision, case by case
- Questions asked
Order the drive and the motor as one package, and let the controller that commands the axis decide which package qualifies. For a SIMODRIVE 611A with a 1FT5 motor such as the reported 1FT5136OAC71-1, the nameplate tells you what you have, not what you can buy: Siemens pairs the 1FT5 family with the 611A control and lists that drive as a spare-part-only item for a limited time, so a modern upgrade passes through the upstream CNC or PLC. Four records decide the selection: the exact drive assembly and motor designation, the command interface and its scaling, where the position loop closes, and the continuous torque the real cycle demands. This article gives you the method, the arithmetic and the decision for each case.
Record the designation before you order anything #
Copy the motor designation character by character from the nameplate. The reported string 1FT5136OAC71-1 contains a character immediately after the frame-size digits that reads as either the letter O or the digit zero, and the two select different ordering variants and different motor data, so confirm it on the plate rather than trusting a parts list. Photograph the nameplate, the drive module labels and every connector before disconnecting anything.
The 611 family name covers several drive variants, and the variant suffix is part of the exact module designation, so read it from the module label rather than from conversation memory; a quote built on the family name alone can come back for the wrong hardware. In the cabinet, give each supply, power and control module its own reference designation so the migration drawing and the panel agree: the IEC 81346 letter codes for electrical components give you the standard notation for that.
What the upstream controller decides #
Identify the CNC or PLC that commands the axis before you shortlist any drive. Record the controller's hardware identification, its axis interface hardware, and three things about the axis: the command type (an analog speed or position setpoint, a pulse or step-direction command, or a message over a communication link), the scaling the control applies to that command, and the enable, ready and fault signals the control expects back.
A drive that fits the shaft but speaks none of those three correctly will not run the machine, and controller-side rework usually costs more than the drive itself. So the rule is simple: a drive stays on your list only when its documented command interface matches what the control already sends, whatever its generation.
Find where the position loop closes #
The position loop compares commanded position with measured position, and it closes either in the controller or in the drive; we walk through the three loop arrangements in our article on where servo control loops close. Trace the encoder wiring to find yours. If measured position travels to the CNC, the CNC closes the loop, and the replacement drive must deliver a measured-value signal the control accepts, or the loop must move into the drive with a position-command interface, which adds controller configuration work. If the drive closes the loop and the control sends position commands, the replacement must accept that command form.
The decision: keep the loop where it is unless you also budget the controller-side rework. Moving the loop to gain a modern drive is a legitimate migration, but it is a controls project, not a drive swap.
Size the motor on continuous torque from the real cycle #
Separate continuous torque, which is thermally limited sustained output, from peak torque, which covers brief acceleration events inside the motor and drive limits. A peak figure alone flatters a marginal selection, which is why peak servo torque ratings mislead a CNC mill retrofit; read both limits from the datasheet of the exact candidate motor. Record the machine's actual cycle, including acceleration, run, dwell and deceleration, and compute the RMS torque the cycle demands.
For a worked example cycle of 5.0 s:
| Phase | Torque | Duration |
|---|---|---|
| Acceleration | 18 N·m | 0.4 s |
| Cutting run | 6 N·m | 2.5 s |
| Deceleration | 12 N·m | 0.3 s |
| Dwell | 0 N·m | 1.8 s |
The RMS torque is the square root of the torque-squared-weighted time over the cycle: T_rms = sqrt((18² × 0.4 + 6² × 2.5 + 12² × 0.3 + 0² × 1.8) / 5.0) = sqrt((129.6 + 90 + 43.2) / 5.0) N·m = sqrt(52.56) N·m, about 7.3 N·m. These are example inputs, so recompute with your own measured cycle. Selecting a package about 9 N·m continuous covers the cycle with a 25 percent margin, a rule of thumb rather than a datasheet limit, and the 18 N·m acceleration transient must also sit inside the candidate's peak curve for 0.4 s at your actual cycle rate.
Mechanical fit is part of the same check: flange, shaft, length and mounting space, with an adaptation plate as a defined design step when the new motor drawing differs.
Check feedback and commutation as part of the package #
The drive needs rotor position to commutate the motor, which is the switching sequence that produces commanded torque. Take the feedback element type from the motor documentation and confirm the candidate drive lists that element in its documented motor data; an adapter does not fix an unsupported feedback device. The general compatibility questions are the same ones that decide old servo motor and new drive compatibility, and the encoder side has its own signal-name discipline covered in our piece on matching encoder signal names between motor and drive. Include feedback and motor cables in the package definition so nothing is discovered missing during commissioning.
Cover supply, braking energy and stopping in the cabinet #
Compare the replacement's infeed, protection, cooling and grounding requirements with the existing cabinet before procurement. Deceleration returns mechanical energy to the drive's DC link, and the replacement needs a defined path for it, usually a braking resistor or a regenerative unit. Size it from your cycle: for an axis with 0.02 kg·m² of total reflected inertia decelerating from 3000 rpm to standstill in 0.3 s, the speed is 3000 × 2π / 60 = 314 rad/s, so the energy per stop is ½ × 0.02 kg·m² × (314 rad/s)², about 986 J, an upper bound because friction removes part of it. Cabinets where several drives share one infeed follow the same logic at group level; the article on DC bus sharing between servo drives covers that arrangement.
Lock out the cabinet supply before tracing any of these connections, and treat the machine's stopping functions through its risk assessment and the applicable standard rather than by matching terminal labels between old and new drives. An enable signal and a safety function are different things.
The decision, case by case #
| What you record | Decision |
|---|---|
| Control closes the position loop and needs the drive's measured-value signal | Choose the drive-and-motor package the control vendor documents for that control; a loop move is controller work, budgeted as such |
| Control sends an analog setpoint | Any drive with a documented analog setpoint input, commutation support for the chosen feedback element, and a measured-value output the control accepts qualifies |
| Control communicates over a bus | Pick from the drive vendor's documented migration path for that bus and its version |
| Drive only, motor kept | Only when the candidate drive documents support for the 1FT5's feedback element |
| 611A must stay for now | Buy it as a spare part while Siemens still offers it, and schedule the full package upgrade before that window closes |
For the reported machine: confirm the letter-or-digit character on the nameplate, record the control interface and the loop location, size the continuous torque from the real cycle, and buy drive, motor, feedback and cables as one documented package whose every connection has a named home in the cabinet.
Questions asked
Is the character in our motor designation the letter O or a zero?
Read it from the nameplate itself, not from a parts list or an old email. Photograph the plate and enlarge the character that sits immediately after the frame-size digits; the letter and the digit select different ordering variants and different motor data. If the plate is unreadable, recover the motor data from the machine's original electrical drawings before you order anything.
Can we replace only the 611A drive and keep the 1FT5 motor?
Only if the new drive can read the motor's feedback element and use it for commutation, which you confirm from the candidate drive's documented motor list before purchase. Siemens states in its support documentation for 1FT5 motors with SINAMICS drives that the 611A is the matching control and is now offered only as a spare part, for a limited time, so a drive-only route depends on a third-party drive's documented support for that feedback.
How do I convert my duty cycle into a continuous torque requirement?
Square each phase torque, multiply by its duration, sum over the whole cycle, divide by the cycle time and take the square root. The 5 second example cycle in this article gives 7.25 N·m RMS, so the selected package needs about 9 N·m continuous with a 25 percent margin, which is a rule of thumb rather than a datasheet limit. Check separately that each transient torque stays inside the peak curve for its duration.
Does the replacement need a braking resistor?
Calculate the kinetic energy per stop from the reflected inertia and the top speed, then multiply by the stop rate. The worked case gives about 986 J per stop from 3000 rpm; at five stops a minute that is roughly 82 W of average power for the resistor to absorb, and it is an upper bound because friction and motor losses remove part of it. Size the resistor from the replacement drive's documented resistor data for that duty.