What the 5000 Hz and 7 V resolver markings on a spindle mean
Short answer
The 5000 Hz and 7 V printed on the spindle are its resolver's excitation carrier frequency and RMS excitation voltage: the drive feeds that carrier to one winding and decodes sine and cosine envelopes into shaft angle. The '2 poles' marking means one electrical cycle per revolution, and '4 poles Electrospindle AC' sets the motor's field speed at 30 rpm per hertz of motor frequency.

On this page
The 5000 Hz and 7 V printed on an AC electrospindle beside the word resolver are the excitation carrier frequency and excitation voltage of the spindle's feedback resolver. The drive's resolver interface generates that carrier, feeds it to one winding and decodes two amplitude-modulated signals back into shaft angle; the markings say nothing about the spindle's power supply or the mains wiring. On the same nameplate, '2 poles' is the resolver's pole count and '4 poles Electrospindle AC' is the spindle motor's — magnetic counts, not supply phases. Below is what each marking means physically, the arithmetic behind the carrier at a real spindle speed, and the checks that keep the circuit decoding cleanly.
A resolver is a rotating transformer, not a power input #
A resolver is an angle transducer built like a small transformer with a moving joint. One winding — commonly on the rotor, fed through slip rings or a rotary transformer — receives the excitation carrier. Two more windings, spaced 90 electrical degrees apart on the stator, pick the carrier up by induction. As the shaft turns, the coupling to each stator winding changes: one carries an amplitude proportional to the sine of the shaft's electrical angle, the other to its cosine. The receiving electronics demodulate both signals, compute the angle from their ratio, and derive speed from the angle's rate of change.
Because the angle comes from amplitudes rather than counted edges, a resolver reports an absolute angle within each electrical cycle: at power-up the decoder reads position inside that cycle without a homing move, which is one reason servo spindles use it for commutation. There are no optics to foul, so the construction tolerates coolant mist, oil and vibration. Construction varies — which winding is excited and how the rotor is fed differs between types — so wire from the unit's own connection diagram, not from a general description.
The markings name the excitation, not the supply #
The carrier frequency and voltage on the nameplate are instructions to the drive's feedback interface, not a supply the resolver can be wired to. The drive generates the carrier itself and must be set, or chosen, to match: excitation at the wrong frequency shifts the amplitudes and phase the decoder expects, and the drive faults or reads a wrong angle. Never connect any resolver winding to mains; the marking describes a low-voltage measurement signal, and 220 V across those windings destroys them.
The voltage convention matters when you configure an excitation source. Resolver practice rates this excitation in RMS: a typical application note describes standard rotor excitation up to 20 V peak-to-peak, which equals 7.1 V RMS, so the voltage marking on the spindle is an RMS figure. Converter and drive data sheets state the range they accept; one precision resolver-to-digital converter family's data sheet, for example, recommends 50 to 20,000 Hz applied to the resolver primary winding R1–R2, with a transformation ratio of 0.2 to 1.0 V/V between signal and excitation amplitude. The marked carrier sits comfortably inside such a window, which is why drives built for these spindles decode it without trouble.
Decoding the 5000 Hz, 7 V marking on a 2-pole spindle resolver #
Inputs, with units and where each comes from:
- Excitation carrier frequency: 5000 Hz — from the spindle nameplate.
- Excitation voltage: 7 V RMS — from the same nameplate, read as RMS per the convention above.
- Resolver poles: 2 — from the nameplate; a single pole pair.
- Shaft speed for the sanity check: 1000 rpm — an illustrative spindle speed for this class of machine.
The rule, in words: the carrier's period is the reciprocal of its frequency; a sine's peak-to-peak value is 2 times the square root of 2 times its RMS value; and the angle the shaft turns during one carrier cycle equals its rotational speed multiplied by the period.
Arithmetic, a calculated example for these inputs and not a measurement:
- Period: T = 1/f = 1/(5000 Hz) = 0.0002 s, which is 200 µs per carrier cycle.
- Peak-to-peak excitation: V_pp = 2 x 1.414 x 7 V = 19.8 V, rounding to the 20 V peak-to-peak standard excitation — which confirms the RMS reading of the marking.
- Shaft angle per carrier cycle: 1000 rpm = 1000/60 = 16.7 rev/s; 16.7 rev/s x 360 degrees/rev x 0.0002 s = 1.2 degrees. The resolver therefore delivers 360/1.2 = 300 complete carrier cycles per revolution, each one a fresh absolute angle sample.
Result: the drive's resolver interface must generate the marked carrier at the marked RMS voltage, and its decoder must accept that frequency; with a single pole pair, one electrical cycle equals one full turn, so the drive's feedback scaling is 1:1.
Decision: set the drive's excitation output to the nameplate carrier and voltage, or use a converter whose documented input window covers it — the 50 to 20,000 Hz family above does. If the only available excitation is fixed at another frequency, do not connect it; fit an interface with a programmable carrier instead, because a mismatched carrier does not degrade gracefully: the decoder loses tracking and the drive faults or commutates on a wrong angle.
Two poles and four poles are magnetic counts, not supply phases #
'2 poles' on the resolver does not mean it works on single-phase mains, and '4 poles Electrospindle AC' does not mean three phases plus neutral. Both are counts of magnetic poles; the protective earth and the cable shield are separate conductors with their own jobs.
For the resolver, the pole count sets how many electrical cycles it delivers per revolution. A resolver with 2p poles has p pole pairs and delivers p cycles per turn, so this unit gives exactly one cycle per revolution: electrical angle equals mechanical angle. Multipole resolvers with more pole pairs deliver several cycles per turn for finer interpolation, and a drive set for the wrong count will commutate and scale position incorrectly — take the count from the resolver type and enter it in the drive's motor configuration.
For the spindle motor, four poles means its rotating field has four magnetic poles, and the field's synchronous speed follows n_s = 120 f / P, with n_s in rpm, f the motor electrical frequency in Hz and P the pole count. For the marked four poles this reduces to n_s = 30 f: the field turns at 30 rpm per hertz of motor frequency. An induction spindle runs slightly below that field speed, with slip; a synchronous one follows it exactly — the nameplate's AC alone does not say which, so read the motor connection diagram and the drive's motor configuration. Keep the two frequencies apart: the resolver carrier is a measurement signal and must never be substituted for motor frequency in that equation.
Checking the circuit and finding the encoder #
Work from the drive's feedback connector outward. Identify the excitation pair and the sine and cosine pairs from the unit's connection diagram; they run as twisted pairs inside a shielded cable, with the shield grounded at the drive end as the drive's instructions specify. With the drive powered and its power stage disabled under the machine's lockout procedure — the carrier itself is harmless, but the same cabinet carries mains and the DC bus — measure the excitation at the drive end with a true-RMS meter or scope: it should sit at the nameplate carrier and voltage. Then turn the shaft by hand with excitation applied and watch the two signal windings: equal peak amplitudes, envelopes 90 electrical degrees apart. A dead or unbalanced envelope points to a broken wire, a shorted winding or a bad connector, in that order of likelihood.
Alignment is the other silent fault: the resolver's electrical angle relative to the motor poles is what the drive commutates against, and a resolver remounted a few degrees off its original angle faults the drive at power-up or runs the motor rough; that failure is walked through in why resolver mounting angle faults an induction motor drive.
As for the encoder the machine is known to carry: on many industrial motors it sits inside the housing on the rear shaft, so nothing shows until the motor comes apart, and a spindle can carry both sensors — the resolver for commutation and an encoder for tool position. Trace each feedback cable from its drive connector, and if an older axis leaves the feedback type unclear, how to identify geared resolver and encoder feedback on old servos gives the steps that tell them apart.
Questions asked
Where is the encoder on a machine whose spindle already has a resolver?
Many industrial motors build the encoder inside the housing, on the shaft behind the rear bearing, so nothing is visible until the motor comes apart. A spindle can carry both sensors: the resolver for commutation and a separate encoder for tool position. Trace each feedback cable from its drive connector back to the machine, and read the feedback type configured in each drive; that tells you which sensor serves which axis.
Can I test the resolver on the bench with a signal generator?
Yes, if the source can drive the winding's impedance; a plain generator usually needs a small amplifier, or you can use the drive's own excitation. Apply the nameplate carrier and voltage, then watch both signal windings on an oscilloscope while turning the shaft by hand: each shows the carrier under a rising and falling envelope, and the two envelopes stay 90 electrical degrees apart with equal peaks.
Does the excitation frequency limit how fast the spindle can spin?
No. The carrier is far faster than the shaft; one cycle covers only a small fraction of a revolution even at high spindle speed. The real limits are the decoder's tracking rate and the resolver's maximum rated speed, both given in their data sheets. Lowering the carrier would slow the decoder's angle updates and weaken its noise margin, which is why it stays at the nameplate value.
Why does the spindle stop with a controlled ramp instead of coasting?
Because the drive stays in command down to zero speed. It commutates the motor to apply braking torque, and the energy taken out of the spinning spindle is burned in a braking resistor or returned toward the supply through the drive's DC bus. Simply removing the output voltage would leave the spindle to coast on bearing friction alone. A feed axis holds position the same way: the position loop keeps correcting instead of switching the motor off.
Why must the drive know the resolver's pole count?
The decoder returns electrical angle, and the drive converts it to mechanical angle using the pole-pair count. On a resolver with one pole pair the two angles are identical, so the drive expects a single electrical cycle per turn. A multipole resolver returns several cycles per turn, and a drive configured for the wrong count commutates and scales position incorrectly. Take the count from the resolver type on the nameplate and enter it in the drive's motor configuration.