Why a Proportional Valve Driver Cannot Run an On/Off Valve
Short answer
A proportional driver such as the Atos E-ME-T controls valves that carry a spool-position transducer: it drives the solenoid, reads the spool position back, and corrects the current until the spool sits where the command says. An on/off directional valve has no transducer, so there is nothing for the driver's loop to close on. For a simple deceleration step, use a preset reduced-flow valve switched by a limit switch.

On this page
No wiring, setting or adapter makes a proportional driver such as the Atos E-ME-T modulate an on/off directional valve. The driver's whole job is to close a loop around spool position: it drives the solenoid, reads the spool's actual position from a transducer built into the valve, and corrects the current until the two agree. The on/off valve in question, the DHO-0611/8W-X24DC, has no spool transducer at all. Its spool is pulled to a seat by a coil or springs, and flow is whatever the fixed orifices and ports give. Connect the driver and you get full shift or no shift, never a position in between.
If what you actually need is a cylinder that slows down at one point of its stroke, you do not need proportional hardware at all: a preset reduced-flow valve switched by a limit switch does that job, and it is the fix to choose. This article explains why the pairing cannot work, how to tell an on/off valve from a proportional one on paper, and what to build instead.
What the E-ME-T driver actually does #
The E-ME-T family of analog drivers is documented for proportional valves with a position transducer. Atos's own literature states that E-ME-T drivers control the current to the solenoid of proportional valves with position transducer, regulating the spool position or the flow accordingly. In practice the driver takes a command input (the family accepts standard signals such as a 0-10 V DC or 4-20 mA reference), drives the valve solenoid, and reads the transducer signal that reports where the spool really is. Inside, it compares the two and adjusts the solenoid current continuously, so flow tracks the command despite supply-pressure changes, oil temperature and coil heating.
Take the transducer away and the loop has nothing to close on. The driver is then just pushing current into a solenoid with no knowledge of what the spool is doing, and no means of holding it at a mid-travel position. An on/off valve is not built to hold one anyway: its spool is designed to land on a seat, not to hover.
Why the on/off valve cannot follow #
A proportional or servo valve moves its spool through intermediate positions, directly or through a pilot stage, so the metering edges throttle flow in proportion to the command. An on/off directional valve has two stable states: shifted and not shifted. Its spool either clears the flow path completely or seats against it. There is no metering stroke to park on, and there is no sensor telling a driver where the spool is. The two architectures differ in the mechanics and in the feedback, and the feedback is the part a driver cannot add after the fact.
Supply tolerance does not classify a valve #
A datasheet line saying the coil supply tolerates plus or minus 10% says only that the valve works over that supply range. Both on/off and proportional valves carry similar tolerance figures. The DHO-0611/8W-X24DC literature states that tolerance; it also describes the valve as an on/off directional valve with no transducer connection, and that functional description, not the voltage figure, is the classification.
Worked example: what the tolerance actually means #
The inputs: a 24 V DC nominal coil supply (the valve's rated supply as shown by its X24DC suffix), and the plus or minus 10% tolerance stated in the valve's documentation.
The rule in words: the tolerance band is the nominal voltage multiplied and divided by 0.10, and the supply must stay inside that band for the coil to operate as documented.
The arithmetic: lower limit = 24 V x (1 - 0.10) = 24 V x 0.90 = 21.6 V. Upper limit = 24 V x (1 + 0.10) = 24 V x 1.10 = 26.4 V.
The result: the supply may sit anywhere from 21.6 V to 26.4 V DC.
The decision: this band tells you how to size the power supply and its wiring drop, and nothing about whether the valve modulates. At 24.0 V nominal the coil pulls in across that whole band whether the valve shifts fully (on/off) or the driver can position the spool (proportional). Read the function diagram and the transducer connections to classify the valve; read the tolerance to design the supply.
How to tell the two valve types apart on paper #
Before buying or wiring anything, open the valve datasheet and check three things in order.
- The function diagram. A proportional valve shows a metering spool with modulated positions; an on/off valve shows discrete boxes for shifted and centered states.
- The electrical connection. A transducer-equipped proportional valve has extra conductors for the spool-position signal, typically four or five pins beyond the solenoid supply. An on/off valve has only the coil connections.
- The driver documentation. The driver page lists the valve families it is built for. The E-ME-T literature names valves with transducer; there is no on/off family in its scope.
If the valve has no transducer wires, no proportional driver will ever control it proportionally, whatever its supply tolerance says.
What to build for a deceleration step #
For the two-speed motion the question is really after, the supported architecture is a discrete one. Fit a preset reduced-flow valve (a deceleration or metering valve set to one reduced flow) in the cylinder line, and trigger it with a limit switch or a digital output. At the trigger point the cylinder drops from full speed to the preset reduced speed, and it holds that speed for the rest of the stroke. The preset flow is set once at commissioning with a flow meter; the switch provides only a discrete event, never a continuous position signal.
If the machine later needs a continuously adjustable deceleration ramp, the parts change: a true proportional valve with an integral spool transducer, its matching driver, and a command source. Related reading on closed-loop hydraulic position control: the article on path control of a hydraulic cylinder with a 4-20 mA feedback signal article:path-control-of-a-hydraulic-cylinder-with-4-20-ma-feedback and the one on stopping a hydraulic ram repeatably with a servo valve article:can-a-plc-servo-valve-stop-a-hydraulic-ram-repeatably both show what the transducer-equipped chain looks like when it works.
One safety note: a limit switch triggering a flow change is a motion-control signal, not a stop function. Keep the machine's actual stop and guard interlocks on hardware rated for that duty, per the risk assessment your machine falls under.
The decision #
- You have an on/off valve and a proportional driver: do not connect them for variable flow. The driver cannot regulate spool position on a valve with no transducer.
- You need one reduced speed part-way down the stroke: use a preset reduced-flow valve switched by a limit switch. Set the flow once, trigger it discretely.
- You need continuously variable flow or a shaped deceleration ramp: specify a proportional valve with an integral position transducer and its matching driver, and budget for the command signal and transducer wiring from the start.
Questions asked
Can a proportional driver make an on/off valve flow part-way?
No. The driver regulates spool position by comparing a transducer signal with the command; an on/off valve has no transducer to feed back, so its spool snaps between seats and the flow goes to whatever the fixed orifices give. Connecting the driver changes nothing about the valve's mechanics.
Does a 24 V DC coil with a plus or minus 10% supply tolerance mean the valve is on/off?
No. That tolerance says only how far the supply may drift while the coil still pulls in reliably. Both on/off and proportional valves are sold with such tolerances. Classify a valve by its function diagram and transducer connections in the datasheet, never by the supply tolerance.
How do I get a two-step deceleration on a hydraulic cylinder?
Switch a preset reduced-flow valve with a discrete signal such as a limit switch or a digital output. The cylinder drops from full speed to that one reduced speed at the trigger point. For a continuously adjustable deceleration ramp, you need a genuine proportional valve with its matching transducer-equipped driver.
What does the transducer do in a proportional valve?
It is a position sensor, typically an LVDT built into the valve, that reports where the spool actually sits. The driver closes a current and position loop on that signal, so flow tracks the command despite pressure, temperature and coil changes. Without it the driver is regulating blind.