Troubleshooting
Why a Servo Axis Runs Past the Limit Switch After a Drive Swap
Short answer
When a servo axis reaches the homing limit switch, changes speed slightly and keeps moving into an overload alarm, the switch input is confirmed good and the fault is downstream in the homing sequence. After a drive swap, check the replacement drive's input function assignment, then the homing method and direction, then firmware-dependent settings a parameter copy cannot carry — and clear the supply overvoltage before any retry.

On this page
- What the symptom proves and what it does not
- Check the replacement drive's input assignment first
- Then check the homing method and direction
- Firmware differences a parameter copy cannot close
- Clear the supply fault before the next attempt
- Worked example: 270 V measured on a machine rated for 240 V
- The fix order and the pass test
- Questions asked
When a servo axis reaches the homing limit switch, changes speed slightly and then keeps moving until it overloads and alarms, the switch and its wiring are not the fault. The control's maintenance page already shows the input changing state at the switch, which clears the switch, the wiring and the input channel in one check. What is broken is the step after that transition: the homing sequence never reversed off the switch, never finished setting the reference, and the axis crept until the drive's overload protection tripped. On a machine that just received a replacement drive with its parameters copied across, the likely causes run from the replacement drive's input function assignment, through the homing method and direction entries, to firmware-dependent settings a parameter copy cannot carry. The supply problem suspected of destroying the original drive is a separate fault, and it gates the retry: clear it first.
What the symptom proves and what it does not #
The observed symptom, in order: the drives enable, the axis travels to the switch, its speed changes slightly at the switch, travel continues in the same direction, and the drive trips on overload.
That sequence proves three things:
- The switch actuates and its transition reaches the control's I/O status, so the switch, its wiring and the input channel work.
- The homing sequence starts and reacts to the transition. The speed change is almost certainly the profile shifting from search speed to creep speed.
- The tail of the sequence never runs: reverse off the switch, find the encoder mark, set the reference.
It does not prove:
- that the replacement drive's input is assigned the homing function this machine's sequence expects;
- that the copied parameter set is complete on the replacement drive;
- that the fault which destroyed the original drive has cleared, because a clean enable proves only that enabling works.
If the input had never changed state at all, the fault would sit upstream in the switch circuit, and that case is covered in why servo homing cannot find a reference switch on PLC inputs. Your case is the harder one: a good input that the sequence ignores or misreads. The overload trip at the end is the drive protecting itself, not the fault; its own diagnosis path is in why a servo drive trips an overload alarm mid cycle.
Check the replacement drive's input assignment first #
A used drive arrives programmed for another machine builder's scheme: which input terminal carries the reference or overtravel function, whether that function is active when the circuit opens or when it closes, and whether the drive itself acts on the input or only reports it. Any of those can differ from what this machine expects, and the parameter screens still look normal because the values are self-consistent — for the machine the drive came from.
The confirming check takes minutes. With motion inhibited, actuate the switch by hand and watch two screens. The first, the control's maintenance page, is already confirmed. The second is the replacement drive's own I/O monitor in the drive maker's setup software: the input must change there too, and the function that changes must be the homing input the machine's documentation names. If the drive never sees the transition, or reports a different function, the assignment is the fault. Set the terminal assignment, the input function and its active level from this machine's documentation, not from whatever the donor machine left behind.
While you are in the software, stop treating the printed maintenance list as a completeness check. The screens show what the firmware exposes, and a drive from a different builder can hold assignments that list never mentions. Compare full parameter sets from inside the setup software instead.
Then check the homing method and direction #
The slight speed change at the switch tells you the profile shifted from search speed to creep speed, so the sequence saw something. In a healthy switch-based method, the axis then reverses off the switch at creep speed, searches for the encoder mark and sets the reference. An axis that keeps creeping in its original direction past the switch has a broken step in that tail, and the usual mismatches are the method and the direction.
Work through them in this order:
- Confirm the homing method entry matches the hardware. A switch used as the reference itself and a switch used as a coarse trip ahead of an encoder mark are different methods, and they behave differently after the transition.
- Confirm the approach direction and the direction the sequence expects to leave the switch. Jog the axis slowly toward the switch and note which side of it the reference position sits on; the sequence must approach from that side and reverse away from it.
- Compare the axis homing entries against the machine's own documentation. A method or direction entry read against the wrong machine's convention looks correct and is not.
Firmware differences a parameter copy cannot close #
The replacement drive runs a different firmware version than the original, and that alone can break a copied configuration in three ways:
- some settings exist in one firmware version only, and a transfer can drop them silently;
- some settings revert to defaults across a firmware change;
- the setup software itself is generation-specific. A software family that does not match the drive generation may connect with reduced function or not at all, and a parameter list that appears complete is not.
The confirming check: record both firmware version strings exactly, not just as "different", and take them to the drive maker's documentation or support channel to learn which homing-related settings are firmware-dependent. Then verify the copy itself. Read the full configuration back from the replacement drive and compare it against the file saved from the original: a write followed by a read-back compare is the only proof that the values stored, and identical screens across the other axes are not.
Clear the supply fault before the next attempt #
The original drive died destructively: the regenerative resistor on its heatsink melted, something popped, and the internal fuse opened while the machine sat powered, enabled and homed. A used replacement enabling cleanly does not tell you the initiating fault is gone.
The suspected contributor is the supply. The shop runs machines through phase converters, the machines that run without trouble all sit behind isolation transformers with voltage taps, and this machine has no tapped transformer while its input reads well above its rating. Install the tapped transformer that brings the machine input back to its rated value, re-measure afterwards, and do that work with the machine locked out. Inspect the regenerative resistor and its wiring on the replacement drive before any sustained enable: the cause that cooked the original resistor was never found, and a parameter copy does not remove causes. Phase-converter supplies fail in characteristic ways, and one common case is worked through in fixing a machine shutdown on a rotary phase converter third leg.
Worked example: 270 V measured on a machine rated for 240 V #
Inputs:
- Rated machine input: 240 V — the machine's stated supply target, from its electrical documentation.
- Measured supply at the machine input: about 270 V — measured during the failure investigation.
Rule: deviation in percent equals the measured supply minus the rated input, divided by the rated input, multiplied by 100%.
Arithmetic: (270 V - 240 V) ÷ 240 V × 100% = 30 V ÷ 240 V × 100% = 12.5%.
Result: the supply sits 30 V, or 12.5%, above the machine's rated input.
Decision: a supply 12.5% above the machine's rating is a fault to correct, not a tolerance to run in. Fit the tapped isolation transformer, re-measure at the machine input under load until it reads the rated value, and only then move to the controlled homing test. This deviation is a calculated example for those two inputs, not a measured drive limit; the acceptable band around the rating comes from the documentation for the exact drive model.
The fix order and the pass test #
Run the checks in this order, cheapest first:
- Correct the supply and inspect the regenerative resistor circuit. This is the precondition: no sustained enable before it is done.
- Actuate the switch with motion inhibited and confirm the drive's I/O monitor sees the transition and reports the homing function.
- Compare the homing method, the approach direction and the active level against the machine's documentation and the physical switch layout.
- Read back the full parameter set from the replacement drive, compare it against the saved original, and check both firmware versions against the drive maker's documentation.
- If the control rather than the drive runs the homing, check the control's axis configuration, where the hardware-limit enable and the homing method live.
Then the pass test: one controlled reference run, with a prepared way to stop the axis and the E-stop within reach. It passes when the drive and the control both register the switch transition, the axis shifts to creep speed, reverses off the switch, completes the mark search and sets the reference without continued travel or an overload alarm. If the switch-based sequence still will not complete after these checks, homing a servo axis to a hard stop with torque limit establishes a reference without trusting the switch at all.
Questions asked
Can I jog the axis to confirm the homing direction by hand?
Yes. With motion inhibited and the speed turned well down, jog toward the switch and note which side of it the reference position sits on. The homing sequence must approach the switch from that side and reverse away from it. A sequence set to approach from the wrong side runs past the switch instead of reversing, which is exactly the travel pattern described here.
Does writing parameters to a replacement drive prove the drive matches?
No. A write puts values in; only a read-back compare proves they stored. Firmware differences can also leave settings that exist in one version only, which the transfer drops without an error. Keep the file saved from the original drive as the comparison baseline, read the full configuration back from the replacement, and record both firmware version strings for the compatibility check.
How far above a machine's rated input can the supply sit?
In the case behind this article the measured supply read about 270 V against a 240 V rated input — 30 V, or 12.5%, high — and that is a supply fault to correct, not a tolerance to run in. The corrective move was the tapped isolation transformer the machine lacked. Re-measure at the machine input under load afterwards, because tap settings read differently once the machine draws current.
Why did the drive trip on overload instead of the axis just stopping?
Sustained creep against overtravel holds high current at low speed, which is precisely the condition overload protection exists to catch. The trip is the protection working, not the fault, and clearing it changes nothing. The fault sits upstream of the trip: a homing sequence that reached the switch and never completed, so the axis never stopped on its own.
Will a used drive from a different machine builder ever work?
Yes, once its input assignments, homing-related settings and firmware behavior are matched to this machine's documentation instead of the donor machine's. The failure mode after a swap is rarely the enable; it is a sequence detail the parameter copy could not carry. That is why the checks run on the drive's I/O monitor, the method and direction entries, and the firmware versions.