Why a Servo Drive Trips an Overload Alarm Mid Cycle

Servo and stepper motion Published 7 min read By AutomateDirectUSA engineering team

Short answer

An overload alarm mid cycle is accumulated thermal overload: torque above the drive's continuous rating for too long, not an instantaneous short. Read the torque monitor through the failing cycle, then clear causes cheapest-first: mechanical drag or a collision, a brake that never releases, acceleration times, gain and inertia ratio, then power and encoder wiring. Wait out the drive's overload timer before any reset, and prove the fix by rerunning while watching torque.

On this page
  1. What the overload alarm actually measures
  2. Read the torque monitor before touching anything
  3. Work the mechanical and brake checks first
  4. Fix the profile and the tuning before swapping hardware
  5. Then check power and encoder wiring
  6. Reset after the timer, and only from a safe state
  7. Example: RMS torque on a 3.6 s pick-and-place cycle
  8. The decision for each case
  9. Questions asked

An overload alarm that stops an axis partway through its cycle is the drive's thermal model calling time: the torque command has sat above the motor's continuous rating for longer than the drive's overload curve allows. It is not an instantaneous overcurrent trip, and no wiring fault needs to exist for it to fire. Start with data, not parts. Run the failing cycle with the torque monitor open, and the trace tells you which of five causes you are chasing: mechanical drag or a collision, a brake that never fully releases, an over-aggressive motion profile, unstable tuning, or a motor one size too small. Work them in that order, cheapest check first. Wait out the drive's overload timer before any reset, and prove the fix by rerunning under the torque monitor — a clean reset proves nothing on its own.

What the overload alarm actually measures #

A servo drive watches the torque command continuously and integrates it against a thermal model of the motor. Torque above the continuous rating fills the model; torque below it drains it. When the accumulation crosses the limit, the drive trips the overload alarm to stop the heating before winding insulation or magnets take damage. Because the trigger is accumulated heat, the trip can land mid cycle, mid shift, or at a different point on every occurrence, even while every individual move sits inside the peak torque rating.

Overcurrent protection is the different animal: it trips in milliseconds on current far beyond the peak rating, and it points at a short, a ground fault, a miswired power cable or a violent mechanical jam. The same thermal-versus-instantaneous split organizes plant motor circuits, where thermal elements sized from the nameplate ride ahead of instantaneous trips — the pairing laid out in setting overload relays from a motor's nameplate full-load current.

Codes and thresholds are drive-specific. One widely used AC servo family codes this condition as Err16.0 and holds the threshold in an overload-protection parameter, Pr5.12; your drive's manual lists its own code and the equivalent parameter, usually in the protection group of its parameter table. The time allowed at each level of overload comes from that drive's documented overload characteristic, not from a rule of thumb.

Read the torque monitor before touching anything #

Nearly every servo drive exposes live and trended torque as a percentage of its continuous rating, and current-generation drives store a fault history with the current, voltage and temperature recorded leading up to the trip. Pull that history first; it is the cheapest evidence you will get. Then command the cycle that actually fails and watch the trace phase by phase, with everyone clear of the machine.

Each trace pattern convicts a different cause:

  • High through the whole cycle: a continuous overload — mechanical drag or an undersized motor. The worked example below decides between them.
  • Spikes only during acceleration and deceleration: the motion profile demands more torque, held longer, than the overload curve allows.
  • High torque together with vibration, buzz or hunting: the tuning, not the load.
  • Normal torque until one specific spot in the stroke: a collision, obstruction or hard stop at that spot.
  • Elevated torque on a brake-equipped axis, worst when holding or moving a vertical load: suspect the brake before the machine.

Work the mechanical and brake checks first #

Inspect the cheap causes first: binding guides or ways, a missed lubrication point, a jammed part, a changed product or fixture weight, a slipping or misaligned coupling. The confirming test is the uncoupled run — take the load off the motor shaft and jog the axis. Torque that collapses to near zero convicts the mechanism. Torque that stays high with nothing attached shifts suspicion to the brake, the wiring, or the motor-and-drive pair.

On an axis with an electromagnetic brake, measure the voltage across the brake terminals during a commanded move and compare it with the rated brake voltage in the motor's documentation. A spring-applied brake releases only when fed its full rated voltage, so a sagging supply or a sluggish release means the motor drags brake friction through every move, and the trace shows it as load with no visible mechanical cause. Block or support any vertical load before forcing a brake release test.

Fix the profile and the tuning before swapping hardware #

Accelerating a reflected inertia J (kg·m²) at angular acceleration α (rad/s²) takes torque T = J·α (N·m), so a longer ramp on the same move cuts that torque term in direct proportion. If the trace spikes only on acceleration and deceleration, lengthen the ramps and retest — the same over-aggressive ramping behind why a servo faults when acceleration ramps increase. If the move time genuinely cannot be extended, the profile is telling you the motor is too small for the move.

If torque runs high together with oscillation or audible hunting, suspect the gains and the inertia ratio setting. An underestimated inertia ratio under high gain hunts around the commanded position, and the drive integrates that wasted torque straight into the overload. Stabilize the tuning and verify the inertia ratio against the actual reflected load before concluding the motor is undersized.

Then check power and encoder wiring #

Wiring comes late in the order because it is a rarer cause of this specific alarm. A damaged, disconnected or miswired motor power cable usually shows up as high current at modest torque, or as an overcurrent trip instead. The classic silent wiring fault is an encoder cable crossed between two axes: the drive commutates the wrong motor, torque climbs as the axis fights its own feedback, and the thermal model fills with no mechanical explanation. Confirm each power and encoder cable lands on its own axis, and inspect at the connectors and drag chains where damage concentrates. If the axis instead faults mid move with a clean torque trace and a position error, that is the following-error path covered in Troubleshooting a Servo Axis That Faults Mid Move, not the thermal one.

Reset after the timer, and only from a safe state #

Manufacturer manuals for these drives state it plainly: confirm the run signal is off before resetting, because the axis can restart the instant the alarm clears — keep hands and tools out of the machine until you have. The reset is also time-gated. The overload protection keeps its accumulated thermal memory after the trip and refuses a reset until the timer recovers; the drive family behind the Err16.0 code documents a minimum wait of 10 seconds after the fault before the alarm will clear. A reset that still fails after a full wait means the condition is present — go back to the trace instead of cycling power.

Example: RMS torque on a 3.6 s pick-and-place cycle #

This is a calculated example for the stated inputs, not a measured result. An axis runs a motor whose datasheet gives a 1.2 N·m continuous rating, on this cycle:

  • Accelerate: 3.6 N·m for 0.30 s
  • Move at speed: 0.96 N·m for 1.50 s
  • Decelerate: 2.4 N·m for 0.30 s
  • Dwell: 1.50 s at zero torque
  • Cycle time: 3.60 s

With torque in N·m and times in seconds, the RMS torque over the cycle is:

Trms = sqrt((3.6² × 0.30 + 0.96² × 1.50 + 2.4² × 0.30) / 3.60)

Trms = sqrt((3.888 + 1.3824 + 1.728) / 3.60)

Trms = sqrt(6.9984 / 3.60) = sqrt(1.944) = 1.39 N·m

That result is 116 percent of the continuous rating. Every single move sits inside the peak rating, yet the RMS figure means the motor runs hot on every cycle, the torque monitor sits above 100 percent for most of the shift, and the thermal model trips mid shift at a point that drifts with ambient temperature and duty. Stretching the dwell from 1.50 s to 2.50 s lowers the result only to about 103 percent — a longer pause is not a fix. The decision for this case: cut the move torque with longer ramps or a lighter load, or fit the next motor size whose continuous rating clears 1.39 N·m with margin. No gain adjustment will do it.

The decision for each case #

  • Torque high through the whole cycle, alarm after minutes of running: continuous overload. Run the RMS calculation; above 100 percent of the continuous rating, reduce the load, slow the rate or resize the motor — tuning and resets will not fix it.
  • Spikes only on acceleration and deceleration: lengthen the ramps. If the move time is fixed, the motor is too small for the move.
  • High torque with hunting or buzz: stabilize the gains and verify the inertia ratio before touching hardware.
  • Normal torque until one spot in the stroke: find and clear the obstruction at that spot.
  • Torque still high with the load uncoupled: brake, wiring, or the motor-and-drive pair. Measure brake voltage first, then confirm each cable is on its own axis.
  • Brake-equipped axis, elevated torque, no visible cause: restore full rated voltage at the brake and confirm release before any other change.
  • Alarm back within minutes of every clean reset: the load still exceeds the continuous rating. Stop resetting — unload or resize.

Questions asked

Can I raise the overload protection parameter to stop the alarms?

No. The overload level is the drive's model of what the motor can dissipate as heat, not an arbitrary trip point. Raising it silences the alarm while the winding insulation and magnets keep taking the heat, and the failure moves from a controlled stop to a burned motor. Treat the alarm as the sizing signal it is: cut the load, lengthen the ramps, or fit a motor with more continuous torque.

Why does the alarm come back hours after a clean reset?

A reset clears the alarm latch, not the cause. If the cycle's RMS torque sits above the motor's continuous rating, the thermal accumulation simply rebuilds over the next shift and the drive trips again at roughly the same point in the duty cycle. A fix that survives only one reset is not a fix: rerun the cycle with the torque monitor open and confirm the RMS figure lands below 100 percent of the continuous rating before calling the machine done.

How is an overload alarm different from an overcurrent alarm?

The causes differ: an overcurrent trip points at a short, a ground fault, crossed power wiring or a violent jam, and it usually resets straight into the same fault if the cause is still there. An overload trip points at sustained load, and the drive refuses to reset until its thermal timer recovers. On a machine that trips, the reset behavior is the fastest first clue: refused reset means thermal accumulation; instant re-trip means look for a wiring or jam fault.

The axis only overloads on a vertical axis that holds position. Is holding the problem?

Yes, holding counts. A servo holding a suspended load draws torque the whole time it stands still, and that holding torque feeds the same thermal integration as the moves do. Check whether the drive's brake control actually engages the motor brake during normal stops and dwell, rather than only catching the load after a fault. If the brake carries the static hold, the motor's torque budget is freed for the moves, and alarms that only ever appeared on the vertical axis usually stop.

Keep reading

  • Troubleshooting

    Servo Drive Over-Speed Alarm: Causes and Checks

    An over-speed alarm means the drive measured motor speed above the limit configured in its speed-limit parameter, not that the motor is broken. Confirm whether the limit, the command, the ramps, false encoder feedback, unstable tuning or a load that back-drives the motor put it there, cheapest first, and never raise the limit to silence a trip whose cause you have not confirmed.

    Servo and stepper motion

  • Troubleshooting

    Servo Motor Rear Noise: Brake or Bearing, Not Gears

    Rear servo noise under the resolver cover is the spring-applied 24 V brake or the rear bearing, and the motor holds bearings, not gears. Verify brake release under electrical load first: brake drag shows up as current rise, heat and noise tied to release events, while bearing noise tracks shaft speed and survives a brake proven healthy.

    Servo and stepper motion

  • Troubleshooting

    Troubleshooting a Servo Axis That Faults Mid Move

    An axis that runs a short distance under a held rapid and then stops has tripped the drive's following-error fault. When only the lightly loaded axis of an identical pair fails, and a clean reinstall of the control PC changes nothing, the cause is encoder noise coupled from the motor leads: separate the wiring, ground each shield at one end, and set a 3 µs step pulse before touching tuning.

    Servo and stepper motion

Servo External Scale Error Alarm: Fix the Feedback Path