Why a Servo Faults When Acceleration Ramps Increase
Short answer
Leave the inertia ratio alone: it is a sizing input, not a tuning fix. The axis runs clean at 700–800 mm/s with ramps at 1000 and faults above 1500, so capture the exact fault code plus current, speed and lag-error traces at the first failing ramp, and let the trace choose between torque saturation, a following-error limit and a parameter violation.
On this page
An axis that runs clean at 700–800 mm/s with acceleration and deceleration at 1000, then faults the moment the ramps go above 1500, has already told you the failure is acceleration-dependent — and that makes it measurable, not mysterious. Leave the inertia ratio alone: it is a sizing number computed once from the mechanics, not a tuning knob, and a guessed entry there makes the tuning worse. Get the exact fault code, trace motor current, commanded and actual speed, and following (lag) error through the first failing ramp, and read which wall you hit: torque saturation, a following-error limit, or a parameter violation. Each of those three has a different fix, and the trace, not the symptom, picks it.
What the fault pattern already proves #
| Test already run | Result | What it establishes |
|---|---|---|
| 700–800 mm/s, acceleration and deceleration at 1000 | Completes clean | Scaling, tuning and drive finish a profile at these ramps |
| Same speeds, ramps above 1500 | Faults | The usable ramp limit sits between 1000 and 1500 on this mechanics |
| 1000 mm/s, ramps at 2000 and above | Faults | Speed and ramp together raise the demand further |
| Jerk set to 0.02 | Faults | No conclusion until the jerk unit is known |
| Any command above the 1500 mm/s speed limit | Faults | Rejection of an out-of-range command — administrative, not mechanical |
Two cross-checks sharpen the picture. Ramp time is speed divided by ramp: 800 mm/s at 1000 mm/s² takes 0.8 s of ramp, while 1000 mm/s at 2000 mm/s² takes 0.5 s — the failing points differ in how fast torque must build, not in distance travelled. And check units on both sides of the link: the axis limit is 1500 mm/s, and any field that reads 1500 m/s (5400 km/h) is a thousand-fold slip that faults on ramps long before it faults on speed. Confirm the controller and the drive scale the same units before trusting any ramp number.
The proven envelope is 700–800 mm/s at ramps of 1000. Treat 1500 and above as unproven, not impossible — the traces decide.
Get the exact fault code first #
"Servo failure" is not a diagnosis; the code is. The standards that govern here are the ones configured in the drive — the speed limit, the current limit and the following-error window — and the fault code tells you which one was enforced. It sorts into five buckets:
- Parameter or motion-range error. The command violates a configured limit, such as speed above the axis maximum, or a dynamic value out of range. This fault appears before the axis moves, so it is administrative: change the command or the limit, not the machine. Motion function blocks of this type document the same pattern of constraints: the acceleration input must be greater than zero, and a deceleration of zero is accepted only when the block also has an acceleration input to fall back on.
- Following-error (lag) exceeded. Commanded position ran ahead of actual position by more than the allowed window. The cause lives downstream: loop tuning, mechanical drag, or torque saturation.
- Overcurrent or peak-current limit. The drive hit its current ceiling trying to make the ramp.
- Overvoltage during deceleration. The DC bus climbs while the drive absorbs braking energy. Check the braking resistor's value and its wiring before touching any motion parameter.
- Feedback or direction-change fault. A fault that lands exactly at reversal points to a load-ratio or scaling entry in the axis configuration rather than to the mechanics; one documented drive case was cleared by correcting that single entry, with no mechanical change.
Order the work by cost: reading the code is free, scaling checks take minutes, one instrumented run buys the trace, and the inertia arithmetic comes last.
Five trace signatures and their fixes #
| Trace signature at the trip | Likely cause | Confirming check | Decision |
|---|---|---|---|
| Current flat at the drive ceiling, actual speed below command, lag error climbing through the ramp | Torque saturation | Compare peak current with the configured current limit, then compute the demand as in the example below | Run at the proven ramps, add reduction, or upsize the motor |
| Current well below its limit, lag error still climbs to its threshold | Loop bandwidth | Re-tune the velocity loop at the failing ramp; lag error should shrink on the next run | Fix the tuning — auto-tune performed at gentle ramps does not cover this profile |
| Current modest, speeds track, fault at constant speed — or a field shows m/s where you mean mm/s | Scaling mismatch | Command a short known move and measure the actual travel; compare the controller and drive scaling pages | Correct the scaling; never tune around it |
| Bus voltage climbing through deceleration, then an overvoltage fault | Regen limit | Inspect the braking resistor value and its wiring | Repair the regen path and retest; only then consider a gentler decel |
| Fault at the instant of command, axis never moves, current flat at zero | Parameter violation | Read the code and compare the command against every configured limit | Change the command or the limit |
Amps alone will not separate a bound-up axis from a badly tuned loop, so be clear about what current-only motor protection can and cannot detect before you judge by current.
The inertia ratio is a sizing input, not the fix #
The ratio of reflected load inertia to rotor inertia is decided when the machine is sized, and at the machine you compute it from the mechanics, enter it once, and tune — tuning a servo axis with a 6:1 ballscrew inertia ratio shows it doing that job. Entering a smaller inertia than the truth to help auto-tune raises the gains the tuner computes and can leave the axis unstable precisely on aggressive ramps.
A conveyor-style load with little attached mass reflects a small inertia at the motor anyway; the example below lands at 0.6:1. If the trace proved torque saturation, the honest fix is mechanical: add a speed reducer, trading speed for torque the way sizing servo reduction for belt-driven plasma table axes works through, or upsize the motor. If the trace proved tuning or scaling, changing inertia entries fixes nothing.
What a 1000 ramp demands versus a 2000 ramp #
Illustrative inputs for a belt-driven axis — substitute your own before deciding anything:
- Moving mass m = 25 kg, carriage plus payload
- Mechanics advance p = 10 mm per motor revolution
- Motor rotor inertia J_m = 1.1 × 10⁻⁴ kg·m² — in practice, from the datasheet of the exact motor
- Constant friction torque at the motor T_f = 0.05 N·m
Reflected load inertia: J_L = m (p ÷ 2π)² = 25 kg × (0.010 m ÷ 6.283)² = 25 kg × (1.592 × 10⁻³ m)² = 6.3 × 10⁻⁵ kg·m².
Inertia ratio: 6.3 × 10⁻⁵ ÷ 1.1 × 10⁻⁴ = 0.57, call it 0.6:1. The common rule of thumb keeps reflected inertia under roughly 5:1 to 10:1 for crisp response, depending on drive bandwidth, so this axis is nowhere near a ratio problem.
Angular acceleration at a 1000 mm/s² ramp: α = a ÷ (p ÷ 2π) = 1.000 m/s² ÷ 1.592 × 10⁻³ m = 628 rad/s².
Torque: T = (J_m + J_L) × α + T_f = (1.73 × 10⁻⁴ kg·m² × 628 rad/s²) + 0.05 N·m = 0.109 N·m + 0.05 N·m = 0.16 N·m.
At a 2000 mm/s² ramp the same arithmetic gives α = 1257 rad/s² and T = 0.218 N·m + 0.05 N·m = 0.27 N·m. Doubling the ramp doubled the inertia torque, which is all the formula claims.
Decision for these inputs: if the motor's datasheet peak torque is several times 0.27 N·m yet the current trace still pins at its ceiling, the wall is not steady torque — look at jerk, loop tuning, or a current limit configured below the drive's real capability. If the datasheet peak sits near 0.27 N·m, the axis is undersized for 2000 ramps and 1000 is the correct setting. This is a calculated example for these inputs, not a measured result.
Find the jerk unit before turning the number #
A jerk entry of 0.02 means nothing until you know whether the platform expects a jerk rate (mm/s³) or a jerk time (s), because the two move in opposite directions: a larger rate makes the profile harsher, a longer time makes it smoother. If 0.02 is a jerk time, acceleration rises almost as a step, and that step — not the ramp value — is what spikes current and following error on a machine that was happy at gentler settings. As a rate it is absurd on its face: 1000 mm/s² ÷ 0.02 mm/s³ = 50,000 s just to build the ramp.
The confirming check is the unit printed beside the field in the commissioning tool or in the function block documentation. The decision if it is a time: start at about one tenth of the ramp time — 0.05 s for the 0.5 s ramp that 1000 mm/s at 2000 mm/s² produces — and shorten it only as far as the fault-free margin allows. That tenth-of-ramp start is a rule of thumb, not a documented optimum.
One test pass that brackets the limit #
- Run the known-good point from the table above with traces recording current, commanded and actual speed, commanded and actual position, and lag error; save it as the reference run.
- Hold speed constant and raise the ramps in steps of about 200, logging each run, until the first fault brackets the limit.
- Stop at the first fault: save the exact code — the ErrorID on platforms that name it that — and export the trace window from two seconds before the trip.
- Read that trace against the five signatures and change exactly one thing: a ramp, a gain, a scaling entry or a jerk time, never two at once.
- Re-run the same move and check three margins: it completes, peak current stays below the limit with headroom, and peak lag error stays well inside its window.
- Sweep the speed range at the new ramps, stay under the configured speed limit, then write the final values into the machine's motion parameters.
Before you deliberately repeat faults, know how this drive stops one: some brake on a controlled ramp — Rockwell's Kinetix documentation, for example, describes a Ramped Decel response that decelerates the motor using the Axis Properties>Planner>Maximum Deceleration value — while others disable power instantly, and on a vertical axis an instant disable drops the load onto the brake, so prove the brake holds before the first intentional trip.
When the code, the trace and the margins agree, the ramps you land on are proven on the machine — a far stronger answer than any inertia entry you could type in.
Questions asked
Why does the axis jog fast but fault on a programmed move?
Jog usually runs its own fixed, gentle ramps and a wide speed window, while a programmed move applies the acceleration, deceleration, jerk and following-error limits you configured. A clean jog proves the motor, drive and feedback work — not that the profile is achievable. Capture the fault code and traces from the failed programmed move, never from jog.
What ramp value is proven on an axis like this?
Acceleration and deceleration at 1000 completed clean at 700–800 mm/s; values above 1500 faulted at those speeds, and 2000 faulted at 1000 mm/s. That is the tested envelope of this one axis, not a universal limit — bracket your own axis with the stepped test in this article before trusting any number.
How do I tell torque saturation from a tuning problem on the trace?
Saturation shows current pinned flat at the drive's ceiling while actual speed falls below command and lag error climbs. A tuning problem shows lag error climbing to its threshold while current stays well under its limit. The fault code confirms which limit the drive enforced. Fix saturation with ramps or mechanics, and tuning with gains.
Should I widen the following-error window to stop the fault?
No, not as a first move. A wider window only lets the axis fall further behind before tripping, which hides a torque or tuning problem and lengthens the uncontrolled travel when the trip finally comes. Set the window from the accuracy the process needs and the distance the axis can stop over, then fix the cause the trace shows.
What should I check first when the fault is overvoltage during deceleration?
The braking circuit. A bus that climbs through deceleration means the drive is absorbing more energy than the regen path can dump; inspect the braking resistor's value and its wiring before changing any motion parameter. If both check out, lower the deceleration ramp until the bus stays inside its band.