Troubleshooting
Why CNC servos won't power up after a battery alarm
Short answer
A control that stays black after the second power press has failed to start, and a battery alarm alone does not stop servos while control power is on. Measure the control supply and startup permissives first, then check whether memory survived the shutdown: eight months of battery warning plus a weekend unpowered can leave lost or corrupt parameters that block startup until they are reloaded from a verified backup.

On this page
- Why does the screen stay black while the hydraulics run?
- Can a battery alarm alone keep the servos off?
- Did a dead battery wipe the NC parameters?
- Which checks come first on a dark control?
- How do you read the cabinet LEDs without the manual?
- How do you replace the battery without losing memory?
- When do you reload the parameters, and what is the decision?
- Questions asked
A Mori Seiki SL-1 with a Yasnac 2000G starts in two stages: the first power press runs the hydraulic unit, the second brings up the NC and servo power. When that second press leaves the screen black except for a battery lamp, the NC has not finished starting, and the lamp is a clue, not the verdict. This article gives the checks in the order that decides the fault fastest: control power and startup permissives first, memory integrity second, plus the one piece of arithmetic that explains how an eight-month-old battery warning turns into a dead start after a weekend off. If the control's identity is in doubt, a side-by-side comparison of the two controls fitted to this lathe settles which one is in the cabinet.
Why does the screen stay black while the hydraulics run? #
The screen stays black because the second press never completed the NC start: the first button energizes only the hydraulic power circuit, so a running hydraulic unit proves that circuit works but says nothing about the control electronics or the servo enable chain. The lit battery lamp shows the display assembly itself has power. The black field means the NC behind it never got far enough to draw anything, which is a control-startup fault, not a monitor fault.
A servo system needs two things: an energy path to the motors and permission to use it. The hydraulic motor running proves incoming power and the first contactor close. It does not prove the control transformer, the NC power supply, the e-stop chain feeding the second-stage permissive, or the retained memory are good. Leave axis tuning, motor loads and encoder checks alone until the control starts and displays something.
Can a battery alarm alone keep the servos off? #
No: while control power is on, the memory circuit runs from the normal supply and the battery is essentially out of the retention path, which is exactly why the machine ran normally for eight months with the lamp lit. The low-battery alarm on this class of control is a maintenance warning, not a startup interlock. It does not gate the servo power circuit. The evidence is on the machine in front of you: the same lamp, the same servos, months of normal production.
What the alarm does mean is that retention is no longer guaranteed the next time control power goes away. Also keep the batteries straight: the one behind this lamp backs the NC's parameters and programs, not axis position. The encoder-side battery is a separate component with its own failure mode, covered in whether servo absolute encoders are really battery-backed. The black screen after a shutdown points at the memory battery, not the encoders.
Did a dead battery wipe the NC parameters? #
Very possibly: a machine that sat unpowered with an exhausted backup battery can lose part or all of its memory, and a control that finds missing or corrupt parameters at power-up refuses to complete its startup rather than run on bad data. Controls from other makers show the same pattern: a battery too weak to hold memory produces partial loss, which is worse than total loss because some parameter pages still look populated.
Here is the arithmetic that connects the alarm to the failure. Take example values, not this control's actual figures: a backup battery rated 1.5 Ah feeding a memory circuit drawing 2 mA.
- Retention time = capacity / current = 1.5 Ah / 0.002 A = 750 hours.
- 750 hours / 24 hours per day is about 31 days of retention from a fresh battery.
A weekend is far inside 31 days with a healthy battery, so a normal shutdown is safe. After eight months of low-battery warning, the remaining capacity is unknown and can be near zero, and the same weekend shutdown finishes it. That is a calculated example for those inputs, not a measurement of the battery in your cabinet; the real capacity and draw come from the fitted control's documentation. The decision: treat the parameters as suspect and find the machine's backup before anything else, because a reload may be the actual repair.
Which checks come first on a dark control? #
Check control power and the startup permissives before anything else: measure the incoming control supply during the failed start, then the supply outputs under load, then walk the enable chain to its first unsatisfied condition. Work cheapest first, and confirm each cause with its own check instead of assigning it from the symptom.
- Startup permissives. An open e-stop chain, a door interlock or an overtravel limit can hold the second stage off while hydraulics run. Confirm on the electrical drawing and at the e-stop relays; this is a two-minute check and the most common cause.
- Incoming control supply. A contactor or breaker feeding only the control transformer can be open while hydraulic power is healthy. Measure at the supply terminals named on the machine drawing during the start attempt, not after it.
- Control power-supply outputs. A supply that collapses when the NC draws current reads correctly only unloaded. Measure at the documented test points with the start commanded, under load.
- Start and enable relays. A relay with an open coil, or a coil missing its control voltage, keeps the servo power circuit dead. Measure coil voltage against the voltage printed on the fitted relay, when commanded.
- The enable chain, if the NC starts. Once a display appears with a servo alarm, walk the chain to the first unsatisfied permissive. The alarm names the failed condition, not the failed component.
Record every measurement. If all four power checks pass and the screen still stays black, the power input unit or the NC rack itself is the suspect, and those readings are what a service engineer will ask for first.
How do you read the cabinet LEDs without the manual? #
Match the LED designation to the maintenance manual for that exact board before condemning anything, because a red indicator can be a normal power-on state on one assembly and a fault on another. A lit red LED is also a different state from an unlit one at the same position, and manuals commonly test for "not lit" as the failure criterion. Good fuses and correct voltages elsewhere in the cabinet do not clear a module, but they do not convict it either. The decision: get the manual for the fitted control from the maker or its distributor, find the board's indicator table, and buy nothing on LED color alone.
How do you replace the battery without losing memory? #
Replace it with control power on, by the documented procedure for the fitted control, and only after a fresh memory backup exists — if the screen is black, treat the memory as probably already lost and stop improvising energized work to save it. The order matters:
- If the NC is running: back up parameters, programs, pitch-error data and offsets first, by the control's documented method.
- Replace the battery hot, control power on, exactly as the maintenance procedure specifies; pulling it powered-down erases what the battery was holding.
- If the NC will not start: the data is likely gone anyway, so replace the battery and plan a reload instead of a rescue.
- Take the battery type, count and cabinet location from the fitted control's manual; the arrangement quoted for another machine does not transfer.
One safety note: the energized battery swap is the only cabinet work done with power on, and only as the documented procedure prescribes. Everything else — measurements, relay checks, module swaps — goes through normal lockout, with the stored-energy sources identified on the machine's risk assessment.
When do you reload the parameters, and what is the decision? #
Reload only when the control starts and the retained parameters fail comparison against the verified machine backup, because visible values on a parameter page prove presence, not correctness. Data that survived half-lost is the most dangerous state: the machine may power up and behave wrongly. This is the same lesson as an absolute encoder error that persists after battery replacement — a new battery restores retention, not lost content.
The decision for each case:
- Control still black after all power checks pass: suspect the power input unit or NC rack. Do not initialize or reload anything; escalate with your recorded measurements.
- Control starts but shows alarms or behaves oddly: compare against the verified backup, reload parameters first, then programs, then verify before making chips.
- Control starts clean: replace the battery, take a fresh backup, keep a printed copy in the cabinet, and return the machine to production.
Find the backup before you need the reload: the machine's parameter printout, punched tape, or the copy from commissioning. A machine that has run eight months on a low-battery warning is a machine whose backup was never checked — fix both at once.
Questions asked
Should you leave control power on while waiting for service?
Yes, if the NC starts at all. With control power on, the memory runs from the normal supply and the battery is out of the retention path, so an aging battery cannot take more data with it. Keep the control energized until a fresh backup exists. If the screen stays black, there is likely nothing left to preserve and normal lockout practice applies to all cabinet work.
How often should a CNC memory battery be changed?
The maker states the replacement interval in the maintenance manual for the control, and that interval is the only number to schedule against. The low-battery alarm means the interval was overrun and retention is no longer guaranteed. On a machine with unknown maintenance history, replace the battery at commissioning, back up the memory first, and write the replacement date inside the cabinet door.
Can you test the servos by jogging before the memory is fixed?
No. With the NC not initialized, no motion command exists to execute, so a jog test proves nothing and forcing servo power with the control dark risks an uncontrolled state. Motion tests belong after the control starts, the parameters match the verified backup, and the enable chain closes. Until then, every measurement belongs on the power and permissive side of the start sequence.
Where is the memory battery located in the cabinet?
On the NC rack or power unit of the control, at the position shown in the maintenance manual or electrical drawing for the fitted control. Battery count and location differ even between machines from the same builder, so another machine's layout is not a guide. Identify the holder on the drawing before opening the cabinet, and have the replacement battery type confirmed against the manual.