Troubleshooting
Why the conveyor tracking scale factor ignores encoder PPR
Short answer
The tracking scale factor holds recorded counts per meter of conveyor travel, not the encoder's pulses-per-revolution rating. With 2000 PPR and 305 mm of travel per revolution, one count per pulse cycle gives 6557.38 counts per meter and a four-edge decode gives 26229.51 — thirteen times the 2000 wrongly entered. Measure raw counts over a marked distance and enter the measured density in the parameter's documented units.

On this page
- What is the tracking scale factor supposed to hold?
- Why does an encoder PPR rating fail as the scale factor?
- How many counts per meter does the belt actually produce?
- Why does the tracked position jump when the zone changes from 0 to fine?
- How do I measure the real counts per meter on the belt?
- What else can distort the measured density?
- What value goes into the scale factor, and how do you prove it?
- Questions asked
The scale factor in a conveyor tracking input holds the belt's count density — how many counts the interface records for every meter of conveyor travel. The ScalingFactor entry of 2000 in an installation like yours is the encoder's nameplate rating, not a density: with a four-edge quadrature decode the same encoder produces the 26160 counts per meter your installation works out to, thirteen times what the field holds. That mismatch is why tracking drifts as parts travel away from the reference and why tightening the point zone to fine makes the tracked position jump. Measure raw counts over a marked belt distance, confirm which edges the input decodes, enter the measured density in the parameter's documented units, and re-establish the tracking reference before judging the result.
What is the tracking scale factor supposed to hold? #
It holds the belt's count density — the number of counts your tracking input records for one meter of conveyor travel, in the unit the parameter's documentation names — and nothing about the encoder as such, because the nameplate only describes one revolution of its own disk.
Three quantities set that density: the pulses the encoder emits per revolution, the number of edges the counter decodes from each pulse cycle, and the meters of belt that pass per encoder revolution. The nameplate fixes only the first, so it can never be typed in as the finished value. The controller divides the raw count by this constant on every tracking update to place the belt's coordinate frame, so a wrong constant produces position error that grows with distance from the tracking reference — the match is exact at the reference and worst far from it.
Size the miss for this case: with the density thirteen times too small, a part one meter past the reference computes as 0.08 m of belt travel, so the tracked target sits about 0.92 m from where the part actually is. Scale is one of three settings a tracking input needs, alongside the zero reference and the direction sign, and the encoder supplies none of them on its own — which is the gap what a conveyor tracking retrofit needs beyond an encoder works through.
Why does an encoder PPR rating fail as the scale factor? #
Because the nameplate describes one revolution of the encoder disk while the field converts counts into meters of belt travel, so entering the rating there leaves the conversion short by a factor of 3.28 at one increment per cycle and 13.11 at a four-edge decode.
The density the field wants is a completed division: counts per encoder revolution divided by belt meters per encoder revolution, and the nameplate is only one ingredient of the numerator. Treat the entry as a unit question first — the deciding document is the tracking interface's own manual, which defines the field's unit and the input's counting mode. One honest branch exists: some interfaces document their input as encoder resolution plus a separate mechanical field and compute the density internally. If yours is that shape, the nameplate value belongs in the resolution field and the fault lives in the travel or decode field beside it, so check those before editing the resolution. What the symptom already proves is that the density reaching the motion planner is wrong by more than a factor of three, whichever field carries it.
How many counts per meter does the belt actually produce? #
At one increment per pulse cycle the belt produces 6557.38 counts per meter; at a four-edge quadrature decode it produces 26229.51 — and the 26160 in your installation's figures is the four-edge result taken with 305.8 mm of true travel per revolution instead of the nominal 305 mm.
That is a calculated example for the stated inputs — the nameplate rating and the nominal travel figure — not a measurement of your belt. The arithmetic, with units carried through:
- Belt travel per encoder revolution, nominal: 305 mm = 0.305 m
- One increment per cycle: 2000 PPR × 1 = 2000 counts per revolution, and 2000 ÷ 0.305 m = 6557.38 counts per meter
- Four edges per cycle: 2000 PPR × 4 = 8000 counts per revolution, and 8000 ÷ 0.305 m = 26229.51 counts per meter
- Cross-check against the installation figure: 8000 counts per revolution ÷ 26160 counts per meter = 0.3058 m = 305.8 mm of true travel per revolution, 0.8 mm more than nominal — a 0.265% gap that a rounded drawing figure or a loaded belt explains on its own
| Quantity | Value | Basis |
|---|---|---|
| Density, one increment per pulse cycle | 6557.38 counts/m | PPR × 1 ÷ travel per revolution |
| Density, four-edge quadrature decode | 26229.51 counts/m | PPR × 4 ÷ travel per revolution |
| Density in the installation figures | 26160 counts/m | four-edge result at 305.8 mm true travel |
| Current ScalingFactor entry | 2000 | the nameplate PPR — wrong basis for a density |
A figure that close to the four-edge calculation is strong evidence the input decodes all four quadrature edges — but it is not proof the field should hold it until the documented unit and your own measurement agree. Whatever density you settle on, the input has to deliver it cleanly; what limits counts per meter in robot conveyor tracking is its own subject and decides whether a high density is even usable.
Why does the tracked position jump when the zone changes from 0 to fine? #
The zone decides where the robot's path terminates relative to the tracked target, not how counts become meters: zone 0 drives to the computed target exactly, a fine zone blends the approach, and tightening it turns a scale error the blend was absorbing into a visible position change.
The error from a wrong density grows with the part's distance from the reference. A blended approach spreads the endpoint across a short path segment and hides part of the offset; zone 0 puts the endpoint hard on the target and re-aims the whole error into the stop position. The jump is therefore diagnostic evidence, not a motion-setting fault: no zone or blend adjustment can correct a count-conversion error. Confirming check: once the density is corrected, command the same approach from standstill with zone 0 and then with fine — the robot should settle within a millimeter or two of the same position, and a residual shift at that point points to the tracking frame or a stale reference rather than the scale.
How do I measure the real counts per meter on the belt? #
Read the raw tracking-encoder count at two fixed marks, run the belt between them over a distance you have measured with a tape, and divide the count change by that distance in meters — one test settles both the density and the decode question.
- Record the current scale entry, its documented unit, the input's counting mode, the direction setting, and any gear or pulley ratios between encoder and belt before changing anything, so the working configuration can be restored.
- Open the tracking interface's monitor or diagnostics view and find the raw conveyor encoder count; that value, after the input's decode, is the number the density converts.
- Mark the belt and a fixed point on the frame and set the tracking reference there, so count and position are matched at the mark.
- Run the belt in its normal direction until the mark has traveled the longest distance you can measure accurately, then read the raw count again; a longer run divides your marking error by more meters.
- Compute the density: count change divided by measured distance, in counts per meter. Repeat three times, approaching the end mark from the same direction every run.
- Repeat the run in reverse. Matching values in both directions say the number is real; differing values point to slip or lost edges, covered below.
- Compare the result with the two calculated candidates above: near the single-cycle figure means the input takes one increment per pulse cycle; near the four-edge figure means it decodes all four edges; anything else means fix the travel figure or the count integrity before trusting either candidate.
What else can distort the measured density? #
Four things corrupt the value or the measurement — an assumed decode multiplier, a rounded or slipping travel figure, lost edges, and speed-dependent delay — and each has a confirming check that separates it from a true density.
- An assumed decode multiplier. The multiplier belongs to the counter input, not to the encoder label: read the input's documented counting mode, or let the marked-distance test decide — a result four times the single-cycle calculation is a four-edge decode, the same arithmetic that turns a 750 PPR encoder into an effective 3000 PPR signal in building an x4 encoder multiplier.
- A rounded travel figure. Roller diameter tolerance, belt seating and load shift the true meters per revolution by a fraction of a percent, and your own figures show it: a 0.8 mm gap per revolution. The marked-distance test measures travel and counts together, so the measured density absorbs this automatically — enter the measured value, not a recalculation from the drawing.
- Slip or lost edges. A tracking encoder needs both quadrature phases as clean square waves so reverse travel registers and vibration does not fabricate counts; a marginal A or B signal loses edges anyway. Confirming check: a density that differs between directions or between runs is not a scale value — the pattern matches missing counts after a cut cycle on any incremental encoder.
- Delay, not scale. An error that grows with belt speed at a fixed distance is synchronization latency, not a wrong density, and burying it in the scale factor corrupts a good value. Confirming check: log the tracked error at two speeds over the same marked distance — distance-proportional error is scale, speed-proportional error is timing, which lives where the conveyor tracking timestamp keeps counting up.
What value goes into the scale factor, and how do you prove it? #
Enter the density you measured, in the parameter's documented unit — counts per meter if the field converts counts into meters, the reciprocal in the documented distance unit if it converts the other way — and on the figures above that means the four-edge density, never the nameplate rating.
- Field documented in counts per meter: enter measured counts ÷ measured meters.
- Field documented as a distance per count: enter measured meters ÷ measured counts, in the documented distance unit.
- Field documented as encoder resolution beside a separate travel field: the nameplate value stays in the resolution field; put the measured travel in the mechanical field and let the controller compute the density.
- Direction: set the sign so a positive count means the belt's normal travel; magnitude and sign are separate settings, and a sign error makes tracking fight the belt even with a perfect density.
Apply the value with the belt stationary, follow the interface's required activation or restart step, and re-establish the tracking reference before judging anything — a stale reference leaves a constant offset that mimics a scale error. Then mark a part, run several meters at reduced speed, and watch the tracked target hold station: the error should stay flat along the whole run, and the zone 0 and fine approaches should settle at the same standstill position. Until the density is proven, keep the tests at reduced speed with no product in the tooling, because a density off by a factor of thirteen steers the target meters from where the part really is.
The decision, case by case: a counts-per-meter field takes the measured density; a distance-per-count field takes its reciprocal in the documented distance unit; a resolution-plus-travel pair takes the nameplate value in the resolution field and the measured travel beside it — and in no case does the nameplate rating go into a field documented as counts per meter.
Questions asked
How accurate does the marked-distance measurement need to be?
Distance error passes straight into the density. Over a 2.000 meter run, a tape good to 2 mm contributes 0.1%, well inside what tracking needs; chalk marks good to 20 mm on the same run contribute 1%, and you will feel that at the far end of the belt. Use the longest run you can mark, measure it with a tape or the machine's own calibrated axis, and approach the end mark from the same direction every run.
What if the scale parameter is documented in distance per count instead?
Enter the reciprocal in the documented distance unit. For example, a measured 20000 counts per meter converts to 1000 divided by 20000, or 0.05 mm per count. The wrong basis is easy to recognize: with a density entered where a distance is expected, the tracked target runs away from the part instead of following it, and the error grows with distance just as an undersized density does.
Does the direction setting change the density I measured?
No. The density is a magnitude and stays positive; a separate direction setting decides which count direction the controller treats as positive belt travel. With the sign backwards, tracking fights the belt on forward motion and drifts on reverse while distances still compute correctly. Confirm the sign with a short manual run before judging the density: the tracked position must move the same way the part moves.
Why did tracking work at all with the entry so far off?
Because the count-to-position match is exact at the tracking reference by definition, so parts near that point track almost correctly and the installation reads as working. The error grows in proportion to how far the part travels from the reference, so reliability falls steadily down the belt. Anything that retightens the path, such as changing the approach point's zone, exposes the accumulated offset in one move, which is the jump you saw.