Selection guide
Choosing VFD or gearbox to slow a linear actuator motor
Short answer
Choose the mechanical reduction first: a gearbox multiplies the motor's rated torque by the ratio (times roughly 90-95% efficiency), while a VFD only holds rated torque and loses shaft-fan cooling below about half speed. Gear a 1/8 HP motor so it runs at rated speed at maximum travel speed; add a VFD only when travel speed must vary.

On this page
Use the gearbox. A reducer multiplies the motor's rated torque by the ratio, while a VFD holds the motor at about rated torque and nothing more — and at reduced speed the shaft-mounted fan no longer cools a machine that still draws full-load current. For a 1/8 HP three-phase motor driving a linear actuator, size the reduction so the motor turns at rated speed when the actuator moves at its maximum travel speed, and add a VFD only if that speed must be adjustable. One speed, no drive.
Why a gearbox multiplies torque and a VFD does not #
A reducer trades speed for torque through its teeth. For a ratio i, defined as motor speed divided by output speed, and gearbox efficiency ηg:
n output = n motor ÷ i
T output = T motor × i × ηg
A 10:1 reducer at 90% efficiency delivers nine times the motor's rated torque at one tenth of the speed. Single-stage planetary and spur reducers typically run 90 to 95% efficient; take the exact figure, and the continuous and peak torque ratings, from the datasheet of the gearbox you buy — that range is a rule of thumb, not a rating.
A VFD lowers frequency and voltage together so the motor slows while its magnetic flux holds, which means it can produce roughly rated torque anywhere in its speed range — but never more than that. Mechanical power is P = T × ω, so as the motor slows, shaft power falls in proportion to speed while the current that produces the torque stays close to full-load value. The cooling fan rides on the shaft, so airflow falls roughly in proportion to speed while the winding heat does not. The working rule of thumb: a standard totally-enclosed fan-cooled motor on a drive holds full torque continuously only down to about half of rated speed; below that you need a blower-cooled (TEBC) or non-ventilated (TENV) motor, chosen against the maker's torque-versus-speed curve for that frame.
NEMA MG-1 Part 31 defines the definite-purpose inverter-fed motor class, whose insulation withstands the voltage spikes a drive puts on the winding; IEC 60034-25 is its IEC counterpart. Neither standard turns a standard motor into a low-speed machine: how much continuous torque the motor may deliver at reduced speed is a cooling limit the manufacturer publishes, not a capability the drive grants.
So the ratio is the primary decision. Gear the motor to run at rated speed at the machine's maximum travel speed, and let any VFD only slow the machine down from that maximum.
Worked example: 1/8 HP motor, 900 N at 25 mm/s #
A calculated example for the stated inputs, not a measured result — re-run it with your own nameplate and load values.
Inputs:
- Motor output 1/8 HP. At 746 W per horsepower: 746 ÷ 8 = 93.25 W.
- Nameplate rated speed taken as 1700 rpm, typical of a 4-pole 60 Hz motor at this size; read the real figure off your motor.
- Rated torque: T = 9549 × P(kW) ÷ n(rpm) = 9549 × 0.09325 ÷ 1700 = 0.52 N·m.
- Ball screw with 10 mm lead (0.010 m per revolution); screw efficiency assumed 0.90 for this example — take your screw's value from its datasheet.
- Required thrust 900 N at travel speed 25 mm/s (0.025 m/s).
Torque the screw demands:
T = F × L ÷ (2π × ηs) = 900 × 0.010 ÷ (2π × 0.90) = 9.0 ÷ 5.65 = 1.6 N·m
Screw speed needed:
n = 60 × v ÷ L = 60 × 0.025 ÷ 0.010 = 150 rpm
The ratio from rated motor speed is 1700 ÷ 150 = 11.3, so take the nearest standard 10:1. Checking it: output speed 1700 ÷ 10 = 170 rpm, so travel speed is 170 × 0.010 ÷ 60 = 0.0283 m/s = 28 mm/s, above the 25 mm/s required. Output torque is 0.52 × 10 × 0.90 = 4.7 N·m against the 1.6 N·m the screw needs — a 2.9× margin that absorbs breakaway friction and acceleration. Verify the gearbox's continuous and peak ratings, and join its output to the screw with a flexible shaft coupling rated for the torque it will see, peaks included.
The VFD-only route fails twice. Direct drive would need the motor at 150 rpm, which is 150 ÷ 1700 = 9% of rated speed, with only 0.52 N·m available — under a third of the 1.6 N·m required — so it stalls on torque before cooling is even discussed; and 9% speed at full-load current sits far below the half-speed floor from the rule of thumb. Driven at full speed instead, the same screw would travel 1700 × 0.010 ÷ 60 = 0.283 m/s, over eleven times the requirement. Decision: 10:1 reducer, no drive.
Gearbox, VFD, or both #
| Approach | Speed | Torque | Choose it when |
|---|---|---|---|
| Gearbox only | Fixed: output = motor speed ÷ ratio | T motor × ratio × efficiency | One travel speed covers the job — the default here |
| VFD only | Adjustable, rated speed downward | About rated torque, never more | Load torque already fits inside rated torque and the motor is cleared for full torque at the lowest speed |
| Gearbox plus VFD | Ratio sets the maximum, drive adjusts below it | T motor × ratio × efficiency, down to the motor's thermal floor | Travel speed must vary while peak thrust is fixed by the ratio |
| PM DC motor and controller | Adjustable | Per the motor's ratings, no multiplication | A small variable-speed rebuild where the DC package costs less; low-speed heating limits it too |
When speed genuinely must vary — a feed-to-force profile, jog and setup speeds, staged travel — pick the ratio from the maximum travel speed exactly as above, then confirm the motor's permitted continuous torque at the minimum speed from its published curve. If that minimum falls below the motor's low-speed torque floor, the motor needs a separate blower or a TENV rating. At 1/8 HP a permanent-magnet DC motor with a simple controller is often the cheaper adjustable-speed package, but its continuous torque at crawl speed is thermally limited the same way: the motor data decides, not the controller's headline capability.
Sizing sequence: ratio first, drive second #
- Convert the actuator duty into shaft torque and speed across the whole cycle: breakaway, steady thrust, acceleration and any hold. The thrust-and-speed-to-motor arithmetic is the same as in sizing a long-stroke actuator for a 500 N push.
- Divide rated motor speed by the maximum required output speed to get the ratio, round to a standard value, then re-check speed and torque with the gearbox's actual efficiency. The same ratio-first logic, worked for servo motors, is in choosing servo gearing for a ballscrew router axis.
- Check the gearbox's continuous torque, peak torque and service factor for your duty against its datasheet, and check the screw, bearings and coupling downstream of it against the same loads.
- Fixed speed: stop here. A single-speed axis gains nothing from a drive except commissioning work.
- Variable speed: verify the motor's continuous torque at the lowest speed against the manufacturer's curve; if the lowest speed falls below the rule-of-thumb floor, specify a blower-cooled or TENV motor.
- If a drive is used, size it by the motor's nameplate voltage and full-load current, not horsepower: its continuous output current must meet the motor's full-load current, and its overload rating must cover acceleration. Isolate the supply before wiring, then enter the nameplate data and run the drive's prescribed motor setup from its manual. Where the only supply at the machine is single-phase, check the drive's input rating — sizing a drive for a three-phase motor on single-phase input covers the derating.
- On a vertical axis, a drive commanded to zero speed is not a brake: if the actuator can back-drive, fit a holding brake rated for the load.
Questions asked
Can I just run the motor slowly on a VFD and skip the gearbox?
Not for a load like this. A VFD holds the motor near rated torque; it does not multiply it. If the screw needs 1.6 N·m and the motor is rated 0.52 N·m, no frequency will close that gap, and running at 9% of rated speed at full current would overheat a shaft-fan-cooled motor anyway. The gearbox does the work; the drive only adjusts speed.
What does an inverter-duty motor actually change?
NEMA MG-1 Part 31, with IEC 60034-25 as its European counterpart, defines the definite-purpose inverter-fed motor class: insulation that withstands the voltage spikes a drive puts on the winding, and a basis for the maker to state how much continuous torque the motor may deliver at reduced speed. It does not by itself extend the low-speed torque of a fan-cooled motor — that still comes from the published torque-versus-speed curve and, usually, a separate blower.
Is a DC motor cheaper than a VFD at 1/8 HP?
Often, yes. A permanent-magnet DC motor and a simple controller usually cost less than a small drive plus the same reduction, and speed adjusts with armature voltage. But a brushed DC motor obeys the same physics at low speed: torque costs current, current heats the windings, and self-cooling falls with speed. Its continuous torque at crawl speed still has to come from the motor data, not the controller's headline capability.
How do I size the VFD if the speed really must vary?
By the motor's nameplate voltage and full-load current, not horsepower. The drive's continuous output current must meet or exceed the motor's full-load current, its overload rating must cover your acceleration current, and its acceptable motor-current range must include a motor this small. Also confirm what supply the drive accepts: several compact drives take single-phase input with derating, which matters when that is all the machine has.