DC Servo Motor Transfer Function Depends on the Output

Servo and stepper motion Published 7 min read By AutomateDirectUSA engineering team

Short answer

For an armature-controlled DC servo motor, voltage to speed is Kt/[(Ls+R)(Js+b)+KtKe], second order, and voltage to position is the same with an extra 1/s. Keep L unless the electrical time constant L/R is a tenth of the mechanical one or less; the worked example keeps the second-order model at a ratio of eight and accepts first order at eighty.

On this page
  1. Two balance equations fix the model
  2. Speed, position and drive command are three plants
  3. The time-constant ratio decides the order
  4. Worked example: one motor, two inductances
  5. Identify the plant with one voltage step
  6. The decision for each case
  7. Questions asked

A DC servo motor does not have one transfer function to look up. For a motor driven by armature voltage, the answer depends on which output you name: shaft speed gives a second-order function, shaft position gives the same function with an extra pole at the origin, and the familiar first-order speed model is a reduction that holds only while the electrical time constant stays far below the mechanical one. Below are the two equations the model comes from, the ratio that decides when the inductance can be dropped, a worked example with the arithmetic shown for one motor at two inductances, and the bench step test that supplies the constants a datasheet leaves out.

Two balance equations fix the model #

For an armature-controlled DC motor — permanent magnet, or separately excited at constant field — two equations carry the whole linear model. Around the armature loop, the applied voltage pays the resistive drop, the inductive drop and the back EMF. On the rotor, motor torque accelerates the inertia and pays the viscous friction:

V = L·di/dt + R·i + Ke·ω
J·dω/dt = Kt·i − b·ω

With zero initial conditions and no external load torque, the Laplace forms are V(s) = (Ls + R)·I(s) + Ke·Ω(s) and (Js + b)·Ω(s) = Kt·I(s). Eliminating the current gives both transfer functions:

Ω(s)/V(s) = Kt / [(Ls + R)·(Js + b) + Kt·Ke]
Θ(s)/V(s) = Kt / [s·((Ls + R)·(Js + b) + Kt·Ke)]

R is the armature resistance in ohms, L the armature inductance in henries, Kt the torque constant in N·m per ampere, Ke the back-EMF constant in V·s per radian, J the total inertia at the shaft in kg·m² (rotor plus everything rigidly coupled) and b the total viscous friction in N·m·s per radian. Ω is shaft speed and Θ shaft angle.

The model assumes a rigid coupling, no saturation and no deadband; a gearbox enters through reflected inertia and friction. No standard prescribes these expressions, and none is needed: Kirchhoff's voltage law plus Newton's second law leave nothing to choose once the input and the output are named. In SI units Kt and Ke are the same number, and a datasheet that makes them look different is quoting two unit systems.

Speed, position and drive command are three plants #

Quoting "the second-order motor model" without naming what goes in and what comes out quotes half a model. The candidates:

Input Output Transfer function Order
Armature voltage Shaft speed Kt / [(Ls + R)(Js + b) + Kt·Ke] Second
Armature voltage Shaft angle Kt / [s·((Ls + R)(Js + b) + Kt·Ke)] Third, pole at the origin
Armature voltage, L neglected Shaft speed Kt / [R·(Js + b) + Kt·Ke] First
Drive command, torque or speed Measured motion No fixed formula: the drive's closed loops Identified by test

Position is the integral of speed, which is where the extra 1/s comes from — and why a servo axis needs position control to stop at the same position rather than a speed command alone (why a servo axis needs position control to stop at the same position). If the controller talks to a servo drive instead of to armature terminals, the plant behind the command is that drive's closed-loop response, because a servo system is defined by closed-loop control, not by one motor construction (what a servo motor is: closed-loop control, not one construction). Model command to measured motion, in the mode the machine will run.

The time-constant ratio decides the order #

The full speed model stores energy in two places, armature inductance and rotor inertia, so it has two poles. The electrical time constant is L/R. The mechanical time constant is R·J divided by (R·b + Kt·Ke): the rise time the speed would show if the current could change instantly. For any first-order step, one time constant is the time to reach about 63% of the final value, which is how both constants are read off a trace.

Rule of thumb, and the one to use: drop L when the mechanical constant is at least ten times the electrical one, and keep it below that. The basis is arithmetic — neglecting L shifts the slow pole by roughly the reciprocal of that ratio. At the threshold the shift is about 10%, inside normal controller-design margin; at eight the miss is already about 15%, as the example shows. The steady-state gain, Kt divided by (R·b + Kt·Ke), is untouched either way, because dropping L changes the transient, not the final speed. Position keeps its 1/s regardless, so a position model is always one order higher than the speed model it is built from.

Worked example: one motor, two inductances #

Example values, calculated rather than measured: R = 1.0 Ω, Kt = 0.05 N·m/A, Ke = 0.05 V·s/rad, J = 1.0×10⁻⁵ kg·m² for rotor plus beam drive, b = 1.0×10⁻⁵ N·m·s/rad. First pass with L = 0.5 mH:

tau_e = L/R = 0.5 mH / 1.0 Ω = 0.5 ms
Kt·Ke = 0.05 × 0.05 = 2.5×10⁻³
R·b + Kt·Ke = 1.0×10⁻⁵ + 2.5×10⁻³ = 2.51×10⁻³
tau_m = R·J/(R·b + Kt·Ke) = 1.0×10⁻⁵ / 2.51×10⁻³ = 3.98 ms
tau_m/tau_e = 3.98 ms / 0.5 ms ≈ 8

That is short of a decade of separation, so the rule says keep L. The exact poles agree. Expanded, the denominator is L·J·s² + (L·b + R·J)·s + (R·b + Kt·Ke), and the quadratic formula on the numbers above gives:

s = [-(L·b + R·J) ± √((L·b + R·J)² - 4·L·J·(R·b + Kt·Ke))] / (2·L·J)
  = [-1.000005×10⁻⁵ ± √(1.00001×10⁻¹⁰ - 5.02×10⁻¹¹)] / (1.0×10⁻⁸)
  = [-1.000005×10⁻⁵ ± 7.06×10⁻⁶] / (1.0×10⁻⁸)
slow pole ≈ -294 rad/s, fast pole ≈ -1706 rad/s

The first-order reduction places its only pole at -(R·b + Kt·Ke)/(R·J) = -251 rad/s, which misses the true slow pole by about 15%, close to the 1/8 ≈ 13% the ratio predicts. A controller designed on the reduced model compensates a pole that far from the real one.

Second pass, same motor with L = 0.05 mH:

tau_e = 0.05 mH / 1.0 Ω = 50 µs
tau_m/tau_e = 3.98 ms / 50 µs ≈ 80
2·L·J = 1.0×10⁻⁹, square-root term = 9.75×10⁻⁶
slow pole ≈ -254 rad/s, fast pole ≈ -19750 rad/s

The reduced pole at -251 rad/s now lands within about 1.3% of the true slow pole, again near the predicted 1/80. Decision: this version is a first-order speed plant.

Steady-state check for both: the gain at s = 0 is Kt/(R·b + Kt·Ke) = 0.05 / 2.51×10⁻³ ≈ 19.9 (rad/s)/V, so 12 V holds about 239 rad/s, roughly 2280 rpm. A step test that settles far from that speed points at wrong friction or wrong constants before any dynamics are worth discussing.

Identify the plant with one voltage step #

When the datasheet is incomplete, the constants come off the bench. A Texas Instruments application note on simplified DC motor modeling obtains the mechanical time constant by driving the motor from a constant-voltage source and timing the speed's rise; the same test settles the order question.

  • Take the drive out of the loop, or set it to plain voltage or torque output with its speed and position loops off — otherwise you identify its closed loop, not the motor.
  • Clamp the motor, guard the coupling and stay inside rated voltage and current: the test spins the shaft.
  • Step the voltage and log input and speed from before the edge until the speed is steady, sampling at least ten times per electrical time constant; slower sampling cannot resolve the electrical pole, so accept a first-order fit at that point.
  • Read the mechanical time constant where the speed reaches 63% of its final value. A trace that leaves the corner at full slope and follows one lag supports the first-order model; an initial flat toe before the rise is the inductance — keep L.
  • Check the fit against a second step of a different size, and re-identify whenever the coupled load changes — on a beam rig, identify with the beam attached, because J and b belong to the combination, not to the motor alone.

If you low-pass the speed feedback before the controller sees it, the same one-pole-or-two choice returns as filter design, and a write-up of first and second order filter implementations in a PLC covers that trade-off for ladder logic.

The decision for each case #

  • Speed output, time-constant ratio of ten or more: first order, Kt / [R·(Js + b) + Kt·Ke].
  • Speed output, ratio under ten: second order, Kt / [(Ls + R)(Js + b) + Kt·Ke] — the example at eight misses the pole by 15%.
  • Position output: add 1/s in both cases, so a first-order speed plant becomes a second-order position plant and a second-order one becomes third.
  • Commands going into a servo drive: the armature model is the wrong plant for the outer controller; identify command to motion in the drive mode the machine uses.
  • Constants missing: one voltage step, the mechanical time constant read at 63% of final speed, the order decided by the ratio.

On a ball-and-beam rig the motor block ends at beam angle; the ball's dynamics follow after it, so identify the motor with the beam coupled and hand the validated block to the outer loop design. State the input, the output and the ratio next to whatever model you publish, and nobody has to guess which plant it describes.

Questions asked

How do I measure R, L and Ke if the datasheet does not list them?

Hold the shaft still and read an ohmmeter across the terminals at four or five rotor positions, then average, because brush contact varies with position. An LCR meter at a fixed frequency gives L the same way. For Ke, spin the shaft at a measured speed with a second motor and read the generated terminal voltage: that voltage divided by that speed is Ke in V·s per radian.

Does a gearbox change the transfer function?

The form survives; only the constants move. Reflect the load to the motor shaft: inertia and viscous friction divide by the square of the ratio, so a 10:1 reducer makes the load feel a hundredth of its inertia. Add the rotor and gearbox inertia to that reflected value, then use the same two balance equations. Gear efficiency scales the torque reaching the load, which changes the gain, not the order.

Does the same model apply to a brushless servo motor?

In the rotor's synchronous reference frame, the q-axis voltage, current and back EMF obey the same two equations, so voltage to speed keeps the second-order form. In practice a drive commutates the motor and closes its own current, speed and position loops, so an outer controller never sees that raw plant: identify command to measured motion as one block, in the drive mode the machine will use.

Why do Kt and Ke have the same numerical value?

They are one physical constant. Power balance for an ideal motor says Ke times speed times current equals Kt times current times speed, so the two match in consistent units, and N·m/A and V·s/rad reduce to the same dimensions. Datasheets that list different numbers are mixing unit systems: a Ke in V/krpm becomes V·s per radian when divided by about 105, since 1000 rpm is 104.7 rad/s, and that quotient is Kt in N·m per ampere.

Keep reading

  • Comparison

    Absolute Position at N20 Size: Which Tiny Servo Gives It

    Absolute position in an N20-size package comes from where the position sensor sits, not the motor diameter. A micro RC servo with feedback on its output shaft reads its angle the instant power arrives, with no homing move. An N20 gear motor with a motor-shaft quadrature encoder is incremental: its counts die at power-off and every start needs a homing routine, so the micro servo wins this brief.

    Servo and stepper motion

  • Explainer

    Replacing Drives on Old DC Servo Motors Without Sizing Errors

    Keep old permanent-magnet DC servo motors once the tag arithmetic and a meter agree: back EMF at top speed plus armature drop sets the terminal voltage, and one ambiguous resistance digit moves the required DC bus by tens of volts. Measure the winding four-wire and the supply with a voltmeter, then buy the drive those two readings name.

    Servo and stepper motion

  • Selection guide

    Second encoder on a servo motor: output before NDE shaft extension

    For a spare motor-position channel on a DRIVE-CLiQ servo motor such as a 1FT7, use a drive-side module that emits an incremental TTL signal: an encoder splitter has no pulses to split, and no NDE second encoder appears among the documented 1FT7 options. Fit a second physical encoder only when the second system must measure independently or see the load.

    Servo and stepper motion