Fixing a pneumatic air spring circuit that spikes on retraction
Short answer
The spike is trapped air being compressed: retraction shrinks the volume at port A and the relief valve is plumbed where it cannot relieve it. Tee the relief valve in parallel with the regulated supply at the cylinder port, set it about 10 psi above the regulator, and prove it exhausts through the full retract. Add a volume chamber only when the force must stay flat over the stroke.

On this page
Re-plumb the relief valve in parallel with the regulated supply, teed at the cylinder port, and the spike stops. What you have now is a relief path that loses its connection to port A exactly when the cam compresses the trapped air, so the pressure multiplies until a seal or a gauge gives out. The regulator fills the cylinder for extension; the relief valve alone limits pressure during retraction. No gate or switching valve is needed, because the relief is normally closed and consumes no air below its setting. Set it about 10 psi above the regulator, prove it exhausts through the full retract, and work the two-case diagnosis below before buying anything.
Why retraction multiplies the pressure #
With port B open to atmosphere and regulated air on port A, the extension force is supply pressure times piston area, less seal friction. The trouble is the return stroke: the cam does work on the air trapped at port A, and a gas volume with no exit answers with pressure. For a slow, near-isothermal compression, absolute pressure times volume stays constant — halve the trapped volume and you double the absolute pressure. A fast retract behaves closer to adiabatic, where pressure rises as volume to the power of minus 1.4 for air, and goes higher still. The spike is therefore not a defect in the cylinder. It is the predictable result of a closed volume, and the whole design question is whether the relief path can pass the displaced air at the set pressure.
Where the relief valve belongs #
Tee the relief valve into the port A line as close to the cylinder as the layout allows. The regulator supplies extension pressure from upstream; the relief opens only when retraction pushes pressure past its setting. The two never contend, so nothing has to switch between them. Three placement rules do the real work:
- Nothing that can close or resist may sit between the tee and port A: no check valve, no one-way flow control, no shut-off, no manifold with an internal check.
- Extension speed controls belong on the regulator side of the tee, so they meter supply air without throttling relief flow; retract-side speed, if you need it, is set at port B.
- The relief exhaust needs a clear, unthrottled path — no metered vent, and a silencer only if it is sized for the flow.
Do not count on a relieving-type regulator to do this job. Its integral vent protects the regulator's own downstream side, and its capacity is not the displacement flow of a retracting cylinder. A dedicated relief valve, with a flow coefficient taken from its datasheet against your displacement rate, carries the duty.
Two failure cases behind the spike #
Every version of this fault falls into one of two cases, and the exhaust tells you which. A relief that never cracks is case 1; one that blows continuously while the gauge still climbs is case 2. Work the causes in order of cost.
Case 1: the relief never exhausts during retraction. Port A has no open path to the relief inlet, or the valve cannot open.
- Setpoint above the pressure the circuit reaches. Back the adjustment out slowly while a gauge teed at port A rises on a retract; if exhaust begins as the reading falls through the new setting, the setting was the fault.
- Isolated inlet — the fault you drew. Trace the line from port A to the relief inlet and name every component in it; any check element, closed valve or one-way fitting is the culprit. Confirm with a second gauge teed at the relief inlet: it must track the port A gauge during retraction, and a reading that stays at supply pressure while port A climbs proves isolation.
- Blocked exhaust. A clogged silencer or a closed meter-out on the vent holds the valve shut. Confirm by removing the exhaust fitting and repeating the retract.
Case 2: the relief exhausts and pressure still climbs. The path is open but cannot flow enough.
- Undersized valve. Air streams out while the port A gauge keeps rising: the valve's flow coefficient, read from its datasheet, is too small for the displaced flow at your cycle speed. The fix is a larger valve and a short, full-bore line to the tee.
- Restriction between port A and the valve. Compare the port A gauge with the gauge at the relief inlet during a retract at cycle speed; a large, sustained difference is line loss through narrow tube, elbows or a partly closed flow control. Opening the flow controls fully and retesting removes it.
- Speed controls in the wrong place. Any throttling element between the tee and the port reads as restriction; move it to the regulator side of the tee.
Restriction that only appears at speed is the same failure mode behind why a pneumatic cylinder will not sustain 5 m/s motion: the component is fine on the bench and starves the circuit at rate.
Worked example: spike size and chamber volume for a 2 in bore, 6 in stroke follower #
The application gives no dimensions, so this runs on stated typical values; every result is a calculated example for these inputs, not a measurement.
Inputs:
- Bore 2.00 in, stroke 6.00 in — assumed for a mid-size cam follower.
- Regulated supply at port A: 60 psig.
- Dead volume at full retract, head space plus line: 3.0 in³, assumed.
- Atmospheric pressure: 14.7 psia.
- Compression treated as isothermal, with the adiabatic figure quoted as the fast-cycle bound.
Rule in words: for a slow compression, absolute pressure times volume stays constant (Boyle's law). For a fast one, absolute pressure grows as the compression ratio raised to the power 1.4.
Arithmetic:
- Piston area = π/4 × (2.00 in)² = 3.14 in²
- Swept volume = 3.14 in² × 6.00 in = 18.8 in³
- Trapped volume, extended V1 = 18.8 + 3.0 = 21.8 in³; retracted V2 = 3.0 in³
- Absolute charge P1 = 60 + 14.7 = 74.7 psia
- With no relief flow, P2 = 74.7 psia × (21.8 / 3.0) = 74.7 × 7.27 = 543 psia = 528 psig, about 530 psig
- Fast-cycle bound, P2 = 74.7 psia × 7.27 to the power 1.4 = 74.7 × 16.1 = 1200 psia, about 1190 psig
- Relief set 10 psi above supply = 70 psig; force = pressure × area, so 3.14 in² × 60 psi = 188 lbf extending and 3.14 in² × 70 psi = 220 lbf at relief, a 32 lbf, 17 percent swing
- Chamber Vc for the same 10 psi band: (21.8 + Vc) / (3.0 + Vc) = (70 + 14.7) / (60 + 14.7) = 84.7 / 74.7 = 1.134, so 21.8 + Vc = 3.40 + 1.134 Vc, so 18.4 = 0.134 Vc, so Vc = 137 in³ — call it 140 in³ (2.3 L)
Decisions from those numbers: set the relief at 70 psig, teed at the port, with line and exhaust sized for the displacement flow. If a 17 percent growth in holding force over the retract is acceptable, fit no chamber; if the follower must track with flatter force, add about 140 in³ of volume. And read the no-relief figures as the reason you prove the exhaust before you run the machine: nothing in this circuit may be trusted to an untested relief path.
Softening the spring rate #
A cylinder charged through a relief valve is a stiff spring: force follows the compression ratio. Two changes soften it.
Put a non-relieving regulator and a volume chamber between supply and cylinder. The chamber adds dead volume, and added volume lowers the effective spring rate — the 140 in³ figure above is exactly that calculation. It also cuts air consumption, because the relief now rarely opens. Note the distinction between the gas volume at pressure and the free air it represents when you size the chamber or predict consumption: actual volume versus free air displacement in pneumatic actuators.
Then attack friction. Piston-seal stiction adds to resisting force on retraction and subtracts from delivered force on extension — a hysteresis band the pressure gauge cannot separate from the air force. Rolling-diaphragm cylinders cut it sharply, at the cost of checking stroke capability against the cam travel.
| Arrangement | What it gives | Main limit |
|---|---|---|
| Parallel relief on regulated supply | Full extension force, protected retraction | Relief path must be proven and flow-sized |
| Non-relieving regulator with volume chamber | Flat force, low air use | Chamber grows quickly as the band tightens |
| Rolling-diaphragm cylinder | Small friction hysteresis | Stroke must cover the cam travel |
| A weight over a pulley or lever | Constant force at any position | Needs the orientation and the travel |
| Mechanical spring | Passive, no air | Force varies with displacement |
Commissioning and pressure limits #
Run a gauge at port A through the complete mold profile, both directions, at operating speed — slow hand cycling hides every flow fault in this list. Accept the circuit when pressure rises to the relief setting and no further, the relief exhausts through each retract, and the follower holds the profile without lag or oscillation. Retest after any change to line length, flow controls or the relief setting.
Before opening any fitting, isolate and vent the circuit: the trapped volume is stored energy, and ISO 4414, the pneumatic systems standard, expects a means of isolation and depressurization that prevents unexpected re-pressurization. Keep settings conservative — a working ceiling of about 200 psi (14 bar) is the rule of thumb quoted for air-spring duty, and the governing limit is always the lowest rated pressure among the cylinder, relief valve, chamber, tube and fittings in the trapped-volume path.
Questions asked
Why does port A pressure climb so high when the cam retracts the rod?
Retraction shrinks the volume of air trapped at port A, and with no open relief path the pressure rises in proportion: half the volume means double the absolute pressure. In a 2 in bore, 6 in stroke cylinder with 3 in³ of dead volume, a 60 psig charge reaches about 530 psig at full retraction, and a fast cycle goes higher still. The rise is physics, not a faulty cylinder.
Do I need a gate or directional valve to switch between the regulator and the relief valve?
No. The relief valve is normally closed and only opens above its setting, so it can sit permanently in parallel with the regulated supply without consuming air during extension. A switching gate adds parts and recreates the exact fault you are fixing, because any element that can close isolates port A from the relief during retraction. Keep the path from port A to the relief inlet permanently open.
The relief valve exhausts during retraction, so why is pressure still too high?
That combination points to flow, not plumbing: either the relief valve is too small for the air the cylinder displaces at cycle speed, or a restriction sits between port A and the relief inlet — narrow tubing, elbows, or a partly closed flow control. Tee a second gauge at the relief inlet. A large difference from the port A gauge during retraction confirms restriction; matched high readings confirm an undersized valve.
How much added volume do I need to flatten the force?
For a 2 in bore, 6 in stroke cylinder at 60 psig, holding full-stroke retraction to 70 psig takes about 140 in³ (2.3 L) of added chamber. The requirement scales with swept volume and with how tight the pressure band is: halving the allowed rise roughly doubles the chamber. Size it from your own stroke, bore and force tolerance, not from a generic figure.
What pressure should the relief valve be set to?
Set it far enough above the regulator setting that normal extension does not vent air, and low enough that peak force stays within what the follower and the cylinder seals can take. Ten psi above supply is a workable band for a 60 psig circuit, giving about 17 percent force growth through the retract. Keep the whole circuit below the lowest component rating and below the roughly 200 psi rule of thumb for air-spring duty.