Pneumatics and hydraulics Published 9 min read By AutomateDirectUSA engineering team

Short answer

Size the pump's speed range by worst coincident peak flow, not average stroke volume: at 10 Hz a 3 mm peak-to-peak command needs 0.0942 m/s peak cylinder velocity, while 0.2 to 0.5 mm commands need only 6.7 to 16.7% of that flow. Size the drive for the motor's full-load current with 150% starting overload, and keep the relief valve as independent overpressure protection.

On this page
  1. Peak cylinder velocity sets the speed range, not average stroke volume
  2. Worked example: three 32 mm bore cylinders at 3 mm and 10 Hz
  3. Size the drive for the motor, the speed range for the flow
  4. Steps to size and set up the drive
  5. Fixed pump with relief, swash plate, or servo pump
  6. The decision, case by case
  7. Questions asked

Yes, a VFD can cut a fatigue rig's electricity bill, but only if the reduced pump speed still supplies the worst simultaneous peak flow, the required pressure and the servo valves' pilot demand. The number that sets the speed range is peak cylinder velocity, not average stroke volume: for sinusoidal displacement control it equals pi times frequency times peak-to-peak stroke. On a rig with four double-acting servo cylinders rated 3 mm peak-to-peak at 10 Hz, usually run at 0.2 to 0.5 mm on two or three axes at a time, the everyday tests need a small fraction of the rated peak flow. On a fixed-displacement pump holding pressure on a relief valve, every litre the axes do not use spills across that valve as heat, so the gap between rated flow and everyday flow is the saving. Size the drive hardware for the motor; size the speed setpoint for the flow.

Peak cylinder velocity sets the speed range, not average stroke volume #

For displacement-controlled sinusoidal motion the peak velocity follows from the commanded profile:

peak velocity = pi × frequency × peak-to-peak stroke

with frequency in hertz and stroke in metres. Peak flow per axis is the active piston area times that velocity: cap-end area for extension, annular area (bore minus rod) for retraction. Average flow over a cycle tells you nothing about the pump's worst moment, because a sinusoid moves fastest through centre and lingers near the ends of travel.

Command at 10 Hz Peak cylinder velocity Share of rated peak flow
3.0 mm peak-to-peak, rated case 0.0942 m/s 100%
0.5 mm peak-to-peak 0.0157 m/s 16.7%
0.2 mm peak-to-peak 0.00628 m/s 6.7%

The pump must cover the worst coincident combination, not the average. Axes that can peak in the same direction at the same instant add their flows; with different phases, evaluate the actual command profiles rather than multiplying one axis's flow by the axis count. Add servo-valve pilot flow and pump leakage on top. And if the lab starts running smaller amplitudes at higher frequency, the saving evaporates: peak velocity is proportional to both, so a faster, shorter test can demand as much flow as the rated one.

Worked example: three 32 mm bore cylinders at 3 mm and 10 Hz #

Inputs: three cylinders moving together (the heaviest stated usage is two or three of the four pistons at once); the rated profile of 3 mm peak-to-peak at 10 Hz; a 32 mm bore with a 16 mm rod; pump displacement of 12 cm³ per revolution at 1450 rpm with 90% volumetric efficiency at full speed; supply pressure of 150 bar; a 1 L/min allowance for pilot flow and leakage. The amplitudes, frequency and axis count describe the rig; the bore, rod, pump and pressure are example inputs — take yours from the cylinder and pump datasheets.

The rule in words: peak velocity is pi times frequency times peak-to-peak stroke; peak flow is active piston area times peak velocity; pump delivery is displacement times speed times volumetric efficiency; relief-valve heat is supply pressure times surplus flow.

The arithmetic:

  • Cap-end area: A = 0.785 × (0.032 m)² = 0.000804 m², about 804 mm².
  • Peak velocity: v = pi × 10 Hz × 0.003 m = 0.0942 m/s.
  • Peak flow, one cylinder extending: Q = 0.000804 m² × 0.0942 m/s = 0.0000758 m³/s = 4.5 L/min (1 m³/s = 60,000 L/min).
  • Retraction rides the annulus: 0.785 × (0.032² - 0.016²) m² = 0.000603 m², giving 3.4 L/min per cylinder. The servo valve routes whichever side is working, so the supply must cover the larger, extending side.
  • Worst coincident demand: 3 × 4.5 L/min + 1 L/min = 14.5 L/min.
  • Full-speed pump delivery: 12 cm³/rev × 1450 rpm × 0.90 = 15.7 L/min, so full speed covers the rated case with margin.
  • Everyday case, three axes at 0.5 mm and 10 Hz: 3 × 0.76 L/min + 1 L/min = 3.3 L/min. At a reduced-speed volumetric efficiency of 0.85, the pump needs n = 3.3 / (0.012 × 0.85) = 3.3 / 0.0102 = about 320 rpm.
  • Relief heat if the pump stays at full speed through that everyday case: surplus 15.7 - 3.3 = 12.4 L/min spilling at 150 bar, so P = 150 × 12.4 / 600 = 3.1 kW dumped into the oil (hydraulic kW = bar × L/min / 600).

All figures here are a calculated example for these inputs, not a measured rig result. Result and decision: the everyday profiles need roughly 320 rpm and the rated case needs full speed. Run the everyday profiles at about 320 rpm if the pump maker's reduced-speed data confirms the pump still builds the required pressure and keeps its lubrication there; if the maker's minimum permissible speed is higher, set the floor there and accept the smaller saving. Keep the pump able to reach full speed the moment a rated multi-axis profile is commanded, and interlock the speed limit to the active test profile — a slow pump on a fast profile starves pressure mid-reversal.

Size the drive for the motor, the speed range for the flow #

Small tests do not shrink the drive: it still runs the motor at full speed and pressure for the rated case. Three checks size it:

  • Continuous current at or above the motor's nameplate full-load current.
  • Starting overload of at least 150% of full-load current. Pump-industry guidance puts a VFD's peak starting current demand at 150% of full-load current, and a cold-oil pump adds breakaway torque on top.
  • Constant-torque capability below base speed. Volts-per-hertz control keeps rated motor torque available from base speed down, typically holding full torque from around 5 to 10% of speed upward; a drive sold only for variable-torque fan and pump duty can run out of current exactly at the low-speed, high-pressure point where this application lives.

Pressure sets the torque demand and flow sets the speed demand, so a slower pump at the same pressure asks for nearly the same torque — the drive saves energy by making less flow, not by working softer. The motor's shaft-mounted fan cools in proportion to speed, so continuous running well below base speed needs a separately powered fan on the motor, run at constant full speed.

Steps to size and set up the drive #

  1. Classify the power unit before anything else. A fixed-displacement pump holding pressure on a relief valve has the most to save. A pressure-compensated variable-displacement pump already destrokes at low demand, so log its input power across a representative cycle before spending on a drive.
  2. Collect every permitted test profile from the rig's controller: amplitude, frequency, active axes and their phase. On a PC-driven rig the profiles live in the control software; driving a fatigue test rig from PC software shows what that layer does.
  3. Calculate each axis's peak flow in both directions: cap-end area for extension, annulus area for retraction, at the pi × frequency × peak-to-peak-stroke velocity.
  4. Add up the axes that can peak in the same direction at the same instant, then add servo-valve pilot flow and pump leakage from the datasheets. With differing phases, work from the actual profiles, not from one axis multiplied by the axis count.
  5. Convert demand to pump speed with n = Q / (displacement × volumetric efficiency), using the pump maker's reduced-speed efficiency and its minimum permissible speed. If the datasheet lists only standard speeds such as 1500 or 1800 rpm, ask the manufacturer for reduced-speed data: internal leakage at low speed can swallow the output, starve the lubrication film or leave the pump unable to build pressure.
  6. Select the drive by the motor: nameplate full-load current continuous, at least 150% for starts, constant-torque configuration below base speed, and a separately powered motor fan for continuous reduced-speed running.
  7. Set the controls. Take closed-loop pressure feedback from a transducer on the P line, downstream of the pump and upstream of the axis valves, so it reads what every servo valve sees. Hold the lowest supply pressure that still covers load pressure, valve pressure drop and pilot pressure. Ramp pump-speed changes slowly so the pressure loop never overshoots and hammers the relief valve open, and store separate tuning sets per pressure level, because servo-valve gain moves with valve pressure drop. Let the speed setpoint follow the active test's demand rather than the valve states, the same demand-following argument made in why a hydraulic pump command should follow the cycle, not the valves.
  8. Keep the main relief valve in circuit, set as it is, protecting the same volume. The transducer, the controller and the drive can all fail; the relief valve is what stands between a failed speed loop and an over-pressurized rig.
  9. Commission at the everyday small-amplitude profiles first, then at the maximum permitted combination of amplitude, frequency, load and simultaneous axes. Trend supply pressure at high resolution to catch the droop at each reversal, which a slow display hides. Accept the retrofit when amplitude and phase stay stable, no pressure starvation appears, the relief valve stays closed in normal running, and motor and oil temperatures hold inside their established limits. Compare energy over complete equivalent test cycles, not instantaneous drive current.

Fixed pump with relief, swash plate, or servo pump #

Supply approach Where the energy goes What decides it
Fixed pump, relief valve, constant speed Surplus flow becomes heat at full supply pressure The state to retrofit; full flow always available
Fixed pump on a VFD Pump makes only what the active profile needs Pump must cover the worst coincident demand at reduced speed and stay lubricated
Pressure-compensated swash-plate pump Destrokes at pressure and cuts shaft power Compensator response must suit 10 Hz motion; already captures much of the saving
Servo motor pump per axis Flow on demand, no long throttling path Four precise axes at 10 Hz push response and cost beyond a first retrofit

For a relief-regulated fixed pump the VFD is the primary retrofit: the relief valve stays as protection and the drive sets speed. Two fixed-displacement pumps on one unit raise the drive-count question first, which one VFD or two for a pair of fixed-displacement pumps answers for that case. If the installed pump already destrokes, measure before buying: a compensator may already be capturing most of the saving, and a drive fighting the compensator's own pressure loop can hunt.

The decision, case by case #

  • Relief-regulated fixed pump with everyday profiles of 0.2 to 0.5 mm on two or three axes: retrofit the VFD, set the reduced-speed limit from worst coincident demand divided by displacement times reduced-speed volumetric efficiency, and interlock that limit to the active profile. The everyday-case relief heat, about 3.1 kW in the example, disappears.
  • Rated multi-axis commands: pump at full speed; drive and motor keep their full nameplate rating.
  • Pressure-compensated pump already installed: log electrical input power over a full cycle first, and add a drive only where the compensator leaves measurable relief or throttling loss.
  • Smaller amplitude at higher frequency: no speed reduction, because peak velocity scales with both; re-run the peak-flow calculation for each new profile before lowering the pump speed.

Questions asked

Can a variable-torque fan and pump VFD run this hydraulic pump?

Not on its variable-torque rating. A hydraulic pump is a constant-torque load: pressure sets the torque demand, so the drive must deliver full motor torque and current at reduced speed, where a fan or centrifugal pump needs only a fraction. Select the drive for constant-torque duty, with continuous current at the motor's full-load current and starting overload above that.

How slow can the pump actually run?

The pump manufacturer's minimum speed decides, not the drive. Below that limit, internal leakage takes a growing share of the output, lubrication and pressure capability suffer, and the pump may fail to build the required pressure. If the datasheet lists only standard speeds such as 1500 or 1800 rpm, request reduced-speed performance data before setting the drive's minimum-speed limit.

Does slower running also cool the servo valves?

Partly. Valve heating follows valve pressure drop times flow, so lower supply pressure and lower flow both help. On a displacement-controlled rig the valve still needs its pressure drop for response, so that throttling loss is hard to remove; the VFD's saving comes from the relief-valve loss, which is the larger share on a relief-regulated unit.

What if the lab drops amplitude but raises frequency?

The saving disappears, because peak velocity scales with frequency times peak-to-peak stroke: 1.5 mm at 20 Hz demands the same peak flow as 3 mm at 10 Hz. Re-run the peak-flow calculation for every new profile before lowering pump speed for it, and keep the drive's maximum-speed limit high enough to cover the rated case.

Keep reading

  • Troubleshooting

    Hydraulic pump no pressure: phase rotation and 9-lead straps

    A pump motor that turns but builds no pressure means wiring: either reversed phase rotation at the pump motor starter, or a nine-lead dual-voltage motor still strapped for 440-480 V after a conversion to 220-240 V, which leaves about half of rated torque. Swap two line leads for the first fault; restrap from series to parallel for the second.

    Pneumatics and hydraulics

  • Selection guide

    One VFD or Two for a Pair of Fixed-Displacement Pumps

    Run both fixed-displacement pumps from one VFD only when they feed a common hydraulic circuit and can share speed and start/stop: size the drive for the summed nameplate full-load current, use open-loop V/F, and give each motor its own overload wired to stop the drive. Choose one drive per motor when the pumps need independent speed, fault isolation or unequal loading, and treat the future 50 hp drive as its own decision, sized when that motor's nameplate exists.

    Pneumatics and hydraulics

  • Troubleshooting

    Why a CNC Hydraulic Pump Shows Zero Pressure After a Shop Move

    A hydraulic pump that reads zero right after a shop move is usually fed with two supply legs swapped: reversed phase sequence spins the pump motor backward, and a pump running against its rotation arrow cannot build pressure. Verify voltage and phase sequence at the disconnect first, jog the motor and compare with the pump's arrow, and only then test the hydraulics.

    Pneumatics and hydraulics