One VFD or Two for a Pair of Fixed-Displacement Pumps

Pneumatics and hydraulics Published 8 min read By AutomateDirectUSA engineering team

Short answer

Run both fixed-displacement pumps from one VFD only when they feed a common hydraulic circuit and can share speed and start/stop: size the drive for the summed nameplate full-load current, use open-loop V/F, and give each motor its own overload wired to stop the drive. Choose one drive per motor when the pumps need independent speed, fault isolation or unequal loading, and treat the future 50 hp drive as its own decision, sized when that motor's nameplate exists.

On this page
  1. When one drive is the right answer
  2. What a drive does to a fixed-displacement pump
  3. Size the drive from the nameplates, not the horsepower
  4. A separate overload for each motor, and what a trip does
  5. Starts per minute are the heat problem, not a drive-count problem
  6. Low speed and motor cooling
  7. The future pump drive is its own decision
  8. The decision, case by case
  9. Questions asked

Two fixed-displacement pumps on one hydraulic circuit can share one VFD, and for a unit built around two 15 hp motors that is the right buy, with three conditions: both pumps feed the same circuit, they always run and change speed together, and each motor keeps its own overload. Size the drive for the summed nameplate full-load current of both motors, run it in open-loop volts per hertz mode, and let either overload stop the whole drive. Do not size it for the 50 hp pump planned two or three years out; that drive is its own decision, made when that motor's nameplate exists. The sizing, the mode and the case-by-case decision follow.

When one drive is the right answer #

A single drive outputs one voltage and one frequency. Every motor connected to it turns at the same speed, starts with it and stops with it; nothing downstream regulates the motors individually. One drive therefore fits exactly when the pumps behave as one machine:

  • Both pumps feed one common circuit, so their flows add and the pressure is shared.
  • One speed command and one run command are acceptable; neither pump ever idles while the other works.
  • The motors match: same nameplate voltage, same rated speed and pole count. The multi-motor application notes the drive makers publish all list the same rated speed as a condition.
  • The load splits evenly by construction, since both pumps see the same pressure at the same displacement.

When the two motors instead drive one shaft through gearing or a common gearbox, the coupling is mechanical and the problem is different; that case is covered in load sharing between two VFD motors on one common load. A shared oil circuit is the easier case, because the fluid sums the two pump flows with no shafts to keep in step.

What a drive does to a fixed-displacement pump #

The drive controls shaft speed, and with a fixed displacement that is the same as controlling flow. The theoretical flow follows speed directly, before volumetric losses:

Q (L/min) = displacement (cm³/rev) × speed (rpm) / 1000

Calculated example, not a measurement: each pump is set to 20 cm³/rev by its manual swash-plate limiter and each motor is a four-pole rated 1,750 rpm. At 60 Hz each pump delivers 20 × 1750 / 1000 = 35 L/min, so the pair delivers 70 L/min. At 30 Hz the motors turn about 875 rpm and the pair delivers 35 L/min, half the flow at whatever pressure the circuit demands.

That last clause is the limitation. Slowing the pump cuts flow but never pressure-compensates: if an actuator stalls, the pump keeps pushing its current flow over the relief valve at relief pressure, and the torque stays with it. Pump torque follows pressure and displacement, not speed, so a slowed pump against full pressure still loads its motor near full torque. Cross-check with the same example: 35 L/min at 150 bar is 8.75 kW, about 12 hp of hydraulic power, exactly where a horsepower-limiting swash setting would put this motor. Choosing displacement from actuator demand in the first place is the power-unit problem covered in hydraulic power unit sizing for a lathe chuck retrofit; here the pumps exist and only the drive is in question.

Size the drive from the nameplates, not the horsepower #

The drive must carry the sum of both motors' nameplate full-load currents continuously, at your ambient temperature and altitude, after the derating its manual publishes. Never size it from the horsepower labels.

Worked example with example nameplate values, so read your own motors: each 15 hp nameplate shows 19 A at 460 V. The drive then needs a rated continuous output current of at least 19 A + 19 A = 38 A at its rating conditions. Take the frame above that rather than the exact fit: the swash limiters were set for horsepower limiting, which means these motors are meant to work near full load at full pressure, and this drive has no lighter future.

The multi-motor procedures in the drive makers' application notes agree on three settings:

  • Open-loop V/F control, not sensorless vector.
  • Motor data entered as one machine: rated current doubled and power doubled, 38 A and 30 hp in the example.
  • The motor-identification or autotune routine left off.

A separate overload for each motor, and what a trip does #

The drive measures one total current, so one motor can overload while the pair reads normal; the drive's electronic motor protection cannot cover two motors. NFPA 70 Article 430 requires overload protection for each motor, and the multi-motor drive instructions require the same. Install one overload relay per motor and set it from that motor's own nameplate, the same way setting overload relays from motor nameplate full-load current is done for a single-motor starter.

On a common circuit, wire both relay contacts into the drive's fault input so either trip stops the drive and both pumps. The circuit was designed for both pumps together; an unexpected half flow does the machine no favor that a clean stop does not.

How stops and the emergency stop are arranged across the pump drive and the valve solenoids is a separate safety question, covered in emergency stop on a hydraulic pump or solenoids only.

Starts per minute are the heat problem, not a drive-count problem #

Several starts and stops a minute are what wear this unit down: every start dumps inrush heat into the windings while the fan is barely turning, and shocks the circuit with full pressure. The drive's real contribution is not speed control, it is that the pumps never need to stop. Hold a low idle frequency and switch demand hydraulically with an unloading valve: normally open to tank, so at idle the pumps dump at a few bar; energized, it closes the tank path and sends oil to the actuators.

Calculated example of why the unloading matters: both pumps at full speed dumping 70 L/min across a relief valve set at 150 bar convert pressure times flow into heat, 15,000,000 Pa × 0.00117 m³/s, about 17.5 kW into the oil, a reservoir heater with no off switch. The same flow unloaded at 5 bar costs about 0.6 kW. Start the drive with the unloading valve open, so the ramp fights only inertia.

Keep the relief valve as the circuit's maximum-pressure protection: the drive and the unloading valve are controls, not pressure limits. And make the pump run command follow the machine cycle rather than individual valve states; that sequencing decision is the subject of why a hydraulic pump command should follow the cycle, not the valves.

Low speed and motor cooling #

A shaft-mounted fan moves much less air as frequency falls, and this load does not lighten with speed the way a centrifugal one does: pump torque follows pressure, so a pump idling at low frequency against pressure draws near full-load current with little cooling. Treat about 25% of rated speed as the caution point for a self-ventilated motor, a rule of thumb and not a rating, and commit the idle frequency by measurement instead: run at the intended idle point under pressure for an hour and watch the motor frame temperature. If it climbs past anything full-speed running produced, raise the idle frequency or add forced ventilation. Stay above the pump's minimum speed from its datasheet, too, because lubrication flow and case drainage depend on shaft rotation.

The future pump drive is its own decision #

The planned conversion, one 50 hp motor and a single variable-displacement pump two or three years out, does not change today's purchase, for three reasons:

  • A pressure-compensated pump normally runs at constant shaft speed and controls by destroking, so its drive, if it needs one at all, is a soft-start-and-idle duty, not the flow-control duty you are buying now.
  • A drive sized for the future motor would run today's 30 hp load far below its design point for years, and its multi-motor settings get discarded at the conversion anyway.
  • The future drive is sized from the future motor's nameplate current and that pump's duty, and neither exists yet.

If the owner insists on one purchase covering both eras, a drive rated for the 50 hp nameplate current also covers the summed 38 A requirement. Acceptable, provided that frame supports multi-motor V/F operation and the individual overload relays stay either way. The engineering default stands: buy for the nameplates you can read today.

The decision, case by case #

Case Decision
Both pumps on one common circuit, running and changing speed together, matched motors One V/F drive rated for at least the summed nameplate full-load current, a separate overload per motor, either trip stopping the drive
Independent pump speed, one pump idle while the other works, or faults must stay isolated One drive per motor, each sized from its own motor's nameplate current
Motors of different voltage or rated speed, or unequal pump loading One drive per motor; do not parallel them on one output
The future variable-displacement pump conversion Its own decision when the motor exists: size from that nameplate, and first check whether the compensator makes a drive optional

For the unit in front of you, two matched 15 hp motors on one circuit with demand-cycled starts, that is one drive rated near the summed nameplate current, open-loop V/F, two overload relays wired to stop the drive, an unloading valve for idle, and a 50 hp drive deferred to the day its nameplate exists.

Questions asked

Can the drive's own electronic motor protection replace the two overload relays?

No. The drive reads one total current, so a motor can overload while the pair looks healthy. The code and every multi-motor drive instruction require a separate overload for each motor. Set each relay from its own motor's nameplate: 125% of full-load current when the service factor is 1.15 or higher, 115% when it is 1.00.

Why open-loop V/F instead of sensorless vector for two motors on one drive?

Sensorless vector control builds a model of one rotor from the current the drive measures. With two motors in parallel the drive sees only the sum, so the model, and any torque or speed estimate derived from it, describes a motor that does not exist. Volts per hertz sends a fixed pattern both motors can follow, which is why multi-motor instructions specify it and tell you to skip the motor-identification routine.

How quickly can a drive-ramped fixed-displacement pump answer compared with a pressure compensator?

Slower, and predictably so. A compensator destrokes at constant shaft speed; the drive must accelerate or decelerate the whole motor-and-pump inertia, so hydraulic response takes roughly the ramp time you program, a large fraction of a second to several seconds. If the cycle needs faster flow changes, run the pump at fixed speed and switch demand with an unloading or directional valve instead of with speed.

What happens to the machine if one motor trips and the other pump keeps running?

The circuit sees about half its flow at the same pressure setting: actuators crawl, cycle times roughly double, and the drive cannot tell which motor failed. That is why the common-circuit wiring stops the drive on either overload trip. If one-pump operation is genuinely wanted for production, that is the two-drive configuration, where each pump has its own run command.

Keep reading

  • Explainer

    AC servo motor and VFD compatibility: what decides it

    A general-purpose V/Hz VFD cannot commutate a permanent-magnet AC servo: reported bench runs pushed 10–12 A into a 2 A motor with no usable torque, and a second servo grumbled and stalled. Buy a drive that documents the motor type, its feedback interface and a speed-control firmware variant, or a matched motor–amplifier pair, and commission uncoupled at the lowest command.

    Motors, gearboxes and drives sizing

  • Troubleshooting

    Hydraulic pump no pressure: phase rotation and 9-lead straps

    A pump motor that turns but builds no pressure means wiring: either reversed phase rotation at the pump motor starter, or a nine-lead dual-voltage motor still strapped for 440-480 V after a conversion to 220-240 V, which leaves about half of rated torque. Swap two line leads for the first fault; restrap from series to parallel for the second.

    Pneumatics and hydraulics

  • Explainer

    Load Sharing Between Two VFD Motors on One Common Load

    Two induction motors pulling one common load cannot be synchronized by giving both drives the same frequency reference: slip makes each shaft speed depend on its own share of the load. Put the master drive in speed control and the slave in torque-follower mode, with the slave's speed reference set a documented margin above the master and its speed limit verified. Independent loads each need their own closed speed loop, and the PLC hands out run, direction, reference and the coordinated stop.

    Motors, gearboxes and drives sizing