Torque mode DAC voltage capped with load cell feedback
Short answer
A torque-mode command that stops near half of its span is rarely the converter's limit: the reported default output limit already equals the full span, and a direct output test reached full voltage. Test the output with the amplifier input connected and disconnected, then trace the load-cell scaling — newtons handed to a loop that expects 16-bit counts, or a span built on the wrong cell capacity, produce the same plateau. Raise gains last.

On this page
A tension loop that tracks the request cleanly at low force and then stalls, with the torque command holding near half of its output span, is usually not a failed digital-to-analog converter. The reported tests already clear two suspects: the configured output limit sits at its default, which is the full span, and a direct output command reached full voltage. What remains is the interface and the arithmetic — whether the amplifier's input loads the converter down, and whether the setpoint and the feedback live in the same units on both sides of the loop. Work the checks in that order and reach for gains last: the reported gain change moved the stall without removing it.
What the plateau proves and what it does not #
The reported setup is a cable-driven tension axis on a servo motor: the load cell feeds the analog input as tension feedback, and the loop closes in software after the controller family's documented torque-control example. Tracking is good until the request reaches about 80 N. There the motor stops responding, the command output sits at 4-5 V of a ±10 V span, and the analog input is configured for 0-5 V. The motor and amplifier were separately verified to 200 N, so the drive has demonstrated more capacity than the loop is using.
Read that combination carefully. A converter that makes full voltage on a direct command but holds mid-span in closed loop is a converter being told to hold mid-span — or one whose voltage is lost between the card and the amplifier. The 200 N verification is capacity under its own conditions: record the command voltage it used, because if it ran near full command, a mid-span command is the same order of torque this stall needs. The three quantities that decide the case are the voltage the loop requests, the voltage present at the terminals and the torque the amplifier develops; the diagnosis is finding where they stop agreeing.
Clear the cheap causes first #
- Read the running axis's active limit, online. The default output limit equals the full span, so a default cannot hold the command at mid-span. But confirm what the running axis actually carries: a configuration saved or loaded from an application file can differ from the screen you checked.
- Run the direct output test twice, connected and disconnected. A single result taken with the amplifier attached proves less than it seems; the comparison convicts or clears the interface.
- Read back the loop's own numbers at the stall. Capture the setpoint and feedback values the loop actually holds, in its native units. If the application passes newtons into a channel that expects the 16-bit count scale, the plateau is a units collision, not a control problem.
- Check the loop's clamp settings. Many motion controllers freeze or clamp the integrator once the output saturates, and a saturation event at low tension can hold the command down afterward. Find the documented integrator-hold or anti-windup setting and read its state.
- Change gains last. Gains alter where the loop stalls, not why.
Repeat the output test connected and disconnected #
The documented test bypasses the servo loop and writes the analog output directly: on this controller family that means configuring the axis temporarily as an open-loop stepper and stepping known voltages with the Load DAC command. The PCI-7350 user manual documents the hardware underneath: two four-channel 16-bit DACs on the output side, updated at every PID loop. Treat the ±10 V range for what it is — a voltage range, not a drive-current rating; how much load the output is specified to drive comes from the manual's output specifications, not from the range.
- Save the current axis and loop configuration first, and record the active input range, enabled channels and filter settings.
- Put the machine in a safe test state with motion prevented and restrain the cable load: with the tension loop out of the circuit, a direct torque command can wind the cable hard.
- With the amplifier disabled through its documented procedure, drive a series of known output commands and measure the voltage at the controller's output terminal, amplifier input disconnected.
- Reconnect the amplifier command input, hold the same safe state, repeat the identical commands, and measure at both ends of the connection.
- If the voltage falls only when connected, the amplifier input is loading the output: compare its input impedance with the controller output's documented drive capability, and inspect the termination and the signal reference while the covers are off.
- Restore the closed-loop configuration and confirm feedback selection, polarity, limits and setpoint handling before enabling the loop again.
The reported direct test reached the full 10 V. When you compare results, say which way each was measured: a result taken with the input disconnected answers a narrower question than one taken connected, and loading is exactly the question this symptom leaves open. Matching a command interface is a two-sided specification problem — what the amplifier input needs, what the controller output can drive — the same matching exercise as finding a servo drive whose analog command input fits the controller.
Converting an 80 N setpoint on a 445 N load cell with a 0-5 V input #
Inputs, and where each comes from: the request at the stall is 80 N (reported symptom); the cell's full scale is 445 N (the figure quoted for the cell); the feedback channel is configured 0-5 V (reported setting); and the setpoint domain is the 16-bit count scale of the analog channel.
The rule, in words: with a zero-based linear map, the count-domain setpoint equals the requested force divided by the calibrated full-scale force, multiplied by the count span of 65,535; the feedback voltage at that force equals the same ratio times the input span.
The arithmetic, written out: 80 ÷ 445 = 0.1798 (18% of the cell's range); in counts, 80 ÷ 445 × 65,535 = 11,781.6, which is about 11,782 counts; in volts, the same ratio gives 0.1798 × 5 V = 0.90 V.
The result: at the stall the cell is working over barely the bottom fifth of its span — the correct count-domain setpoint is about 11,782 of 65,535, and the feedback channel should carry about 0.90 V at that force.
The decision: read back what the loop actually holds at the stall and set it against these two numbers. If the setpoint is not sitting where the conversion puts it, or the feedback volts contradict the measured force, the plateau is a scaling fault, and the conversion — not the gains — is the fix.
Check the nameplate before you scale. The reported figures for this cell disagree: 110 lb converts to about 489 N, roughly 10% above the full scale used above, and the same 11,782 counts would command about 88 N against a 489 N full scale. A drive-maker application note on web tension control (AN-SERV-002) builds its whole loop on the conditioner's span rather than on a printed figure; mid-range span faults of exactly this kind are a recognized failure mode of analog conditioning chains, and a walkthrough of converter span errors shows how to isolate one.
Why stronger gains only moved the plateau #
The reported numbers: the working set was Kp=70, Kd=1000, Ki=15, and a stronger set of Kp=90, Kd=1200, Ki=35 lifted the stall to 120 N — but left the readings too noisy to tell noise from oscillation. That result is diagnostic gold: a converter ceiling would not move when the gains change, so the plateau follows the loop's demand. It is also a warning, because the higher force arrived with worse evidence — what a loop pushed toward instability looks like from the outside.
Two habits follow. A command that stops rising while the error is still alive is the torque-loop cousin of saturation, and the discipline from the error-counter overflow alarm traced to torque saturation — establish what the loop demands and what limits it before touching gains — applies directly here. And how much command a given error produces is set by the loop's stiffness factor, which is not portable between axes: measured KV-factor variation across servo axis loops runs from 0.6 to 3.7, which is why the stronger set cannot simply be copied to the next machine.
Noise that rises with tension #
The reported filter is a 30 Hz low-pass configured in MAX on the load-cell channels. It helps at low tension; as tension rises, the noise floor climbs roughly with it, and vibration and switching sounds become audible at the higher forces. Sound and vibration are mechanical movement: that is not sensor noise riding on a clean signal, it is the system physically oscillating and the cell reporting it. The filter treats the measurement, not the cause, and past a point it removes your view of the problem.
Separate measurement noise from real oscillation before changing anything: record the raw feedback, the filtered feedback and the command voltage at the same time. Real oscillation moves periodically and appears in the command as well as the feedback, because the loop is reacting to it; sensor noise moves the feedback while the command stays quiet. The same separation settles whether a PID axis that buzzes at its setpoint is oscillating or merely reporting noise. If the record shows real oscillation, look at the mechanics — cell mounting, cable routing, resonance of the driven structure — and take the gains back toward the set that behaved.
The decision, case by case #
- Voltage that falls only with the amplifier input connected means the interface loads the output: match the input impedance against the controller output's documented drive capability, repair the wiring or reference, and leave the gains alone until the terminals agree.
- Voltage identical connected and disconnected but still mid-span in closed loop means the loop's demand is the ceiling: read back the setpoint and feedback at the stall, correct the units or the span with the conversion above, clear any integrator clamp, then re-tune on clean feedback.
- An active limit confirmed at the full span is cleared — do not revisit it.
- Nameplate figures that disagree are settled by known loads on the conditioner, not by either printed number.
- Stronger gains that raise the force while the record turns unreadable are a step backward: back them off, fix scaling and noise first, and tune last.
Questions asked
Why configure the axis as an open-loop stepper to test the output?
A servo axis configuration does not usually expose a raw write to its torque-command output; a temporary open-loop stepper configuration does, through the Load DAC command. It is a test arrangement only: the tension loop is out of the circuit and a direct command can move the axis or wind the cable. Restore the closed-loop configuration and confirm feedback selection, polarity and limits before enabling motion again.
Which capacity should I scale to when the nameplate figures disagree?
Scale to the calibrated full scale, established by hanging known loads and reading the conditioner's output, not to either printed figure. The reported pair, 110 lb alongside 445 N, cannot both be right, because 110 lb converts to about 489 N. A 10% error in full scale moves every converted setpoint by 10%, which is easily enough to matter in a tension loop.
Should I lower the filter cutoff below 30 Hz to quiet the load-cell signal?
Lowering the cutoff hides the noise from the loop and adds phase lag, which costs stability in a tension loop that has to react quickly. Filter only as much as the loop's response time allows, and only after deciding whether the noise is real movement. If the mechanics are oscillating, filtering the sensor leaves the oscillation in place and takes away your view of it.
Should I raise the gains to push past the tension plateau?
Gains change where the loop stalls, not why it stalls. Raising proportional gain multiplies whatever sits on the feedback signal into the command, so a stronger set on a noisy cell pushes the loop toward instability; in the reported case the higher force came with readings too noisy to interpret. Clear the output-loading and scaling questions first, then tune on clean feedback.