Transformer size for a servo motor: bus voltage and peak current
Short answer
A servo motor sets two supply limits: the rectified, unloaded bus voltage must stay under the motor's maximum bus rating even at high line, and the transformer VA must cover bus voltage times continuous current. For a 60 VDC, 10.2 A motor that is about 612 VA continuous, with the peak covered by bus capacitance or roughly an 800 VA toroid per axis.

On this page
Size a servo supply from two ratings on the motor datasheet, not from torque: the maximum bus voltage, which the rectified transformer secondary must never exceed even unloaded at high line, and the maximum continuous current, which sets the transformer VA at bus voltage times current. Peak current is a third quantity, but a transformer alone rarely covers it well; bus capacitance does that job cheaper. A motor with a hard bus-voltage limit and a known continuous rating therefore points at roughly a 600 VA supply with about a 40 VAC secondary, plus storage for the peak.
The two motor ratings that decide the supply #
Every number in this article comes from one concrete example motor, the kind sold for small CNC tables: 155 oz-in continuous stall torque, 4800 RPM no-load speed, 60 VDC maximum bus voltage, 10.2 A maximum continuous current, 43 A demagnetization current, Kt of 16.8 oz-in/A and Ke of 13.7 V/kRPM. Your datasheet overrides these values; the method does not.
The mapping is direct:
- Maximum bus voltage: a hard ceiling for the rectified, unloaded, high-line, regenerating bus. This decides the secondary voltage.
- Maximum continuous current: bus voltage times this current gives the continuous-duty VA. This decides the transformer size.
- Demagnetization current: an upper bound on peak current, never a working value. Set the amplifier's peak current limit below it, or the motor loses torque permanently.
Two cross-checks on this example motor show why datasheet conventions matter. Continuous stall torque divided by Kt gives 155 / 16.8 = 9.2 A, consistent with the continuous rating. But 4.8 kRPM times 13.7 V/kRPM is 65.8 V of back-EMF, above the bus limit, so the bus supports only about 4.4 kRPM before IR drop. Read whether Ke is stated line-to-line or phase, peak or RMS, on the exact datasheet, then size gearing or screw lead for the speed the bus actually supports.
For the torque calculation that precedes supply sizing, the page on calculating servo motor current from required torque works the load side; this article picks up where that one ends.
Choosing the secondary voltage #
A capacitor-input bridge rectifier charges to the AC peak, so the unloaded DC bus is the RMS secondary voltage times 1.414, minus the bridge drop (about 1.4 V for a two-diode conduction path):
V_bus ≈ 1.414 × V_secondary − 1.4 V
The commonly suggested 40 to 44 VAC range for a motor at this bus class spans the limit:
- 40 V secondary: 1.414 × 40 = 56.6 V; 56.6 − 1.4 = about 55 V unloaded. That leaves roughly 5 V of headroom.
- 44 V secondary: 1.414 × 44 = 62.2 V; 62.2 − 1.4 = about 61 V unloaded, already above the limit on a nominal line.
Three effects push the bus higher than that unloaded figure: high line at the service entrance (5 to 10 percent above nominal is common), regeneration pump-up during decel, and measurement anywhere but the bus terminals. So the top-of-range secondary fails the ceiling before any of them. The decision: pick the low end, about 40 VAC, and confirm the unloaded rectified voltage at the highest line voltage your shop sees. If that measurement reads above the motor's limit, change the transformer, not the expectation.
Sizing the VA for continuous and peak current #
Continuous duty VA is simply bus voltage times continuous current: 612 VA for this motor, so about a 600 VA transformer is the floor for one motor run gently. A capacitor-input rectifier draws current from the secondary in short high peaks, so its RMS input current runs above the DC load current; that is why the practical figure lands near 800 VA rather than 612.
The peak is a different problem. Set the amplifier peak limit at or below about 40 A, safely under the 43 A demag current. That peak is bus voltage times 40 A = 2400 VA, and it lasts only for the accel portion of a move. Buying a 2400 VA transformer to cover a fraction-of-a-second demand buys mostly idle iron. Covering the peak with bus capacitance instead, and sizing the transformer for the continuous demand plus duty-cycle average, is almost always the better machine. The one exception is an amplifier that cannot be current-limited; then the transformer must carry the full peak, with roughly 1.5 times the VA for each additional identical motor sharing the supply.
Sizing the supply for the example servo motor #
This worked example uses the thread's motor on a single-axis bench; treat the result as a calculated starting point for these inputs, not a universal rating.
Inputs, and where each comes from: maximum bus 60 VDC and continuous current 10.2 A (motor datasheet, as quoted above); secondary candidates 40 and 44 VAC (the commonly recommended range for this bus class); bridge drop 1.4 V (assumed, typical silicon bridge); peak current limit 40 A (chosen by you, below the 43 A demag rating); target transformer 800 VA toroid (a practical size for the continuous demand plus rectifier RMS margin).
The rule in words: first, the rectified unloaded bus is the secondary RMS voltage times 1.414 minus the bridge drop, and it must stay below the motor's maximum bus voltage. Second, the transformer VA must be at least bus voltage times continuous current, plus margin for the rectifier's peaked input current.
The arithmetic:
- 40 VAC secondary: 1.414 × 40 V = 56.6 V; 56.6 V − 1.4 V = 55.2 V, about 55 V. Below 60 VDC, with about 5 V of headroom.
- 44 VAC secondary: 1.414 × 44 V = 62.2 V; 62.2 V − 1.4 V = 60.8 V, about 61 V. Above the limit at nominal line.
- Continuous VA: bus voltage × 10.2 A = 612 VA.
- Peak VA at the chosen limit: bus voltage × 40 A = 2400 VA, covered by capacitance, not by upsizing the transformer.
Result and decision: a 40 VAC secondary passes the voltage check; the top-of-range option fails it. One 800 VA toroid with a 40 VAC secondary, its own bridge and its own capacitor bank covers the 612 VA continuous demand with margin, per axis. Two axes get two independent 800 VA supplies, so a hard accel on one cannot sag the other's bus.
Bus capacitance and regeneration #
The capacitor bank does two jobs. For peak support, size it from the move profile: C = I × Δt / ΔV, where I is peak current minus what the transformer supplies during the accel, Δt is the accel time, and ΔV is the allowed droop down to the amplifier's undervoltage trip and the voltage your target speed needs (bus divided by Ke, less IR drop).
Deceleration is the second job, and the harder one. A rectifier supply cannot sink energy, so the load's kinetic energy E = 0.5 × J × ω² (J the total inertia reflected to the motor, ω the speed in rad/s at decel start) pumps the bus up. The capacitance that absorbs it without tripping overvoltage is C >= 2E / (V_max² − V_nominal²). With only about 5 V of headroom at a 55 V bus, that budget is small; if the formula asks for more capacitance than fits, add the amplifier's regen clamp or shunt resistor, sized to its regen input rating.
Primary-side inrush matters too: an uncharged capacitor bank looks like a short at switch-on, so fit primary fusing and an inrush limiter. For the drive-side sizing that sits upstream of this choice, the article on sizing a VFD from load torque and motor current works the same load-first logic for line-fed drives.
Verify it under load before trusting it #
Four measurements close the loop:
- Unloaded DC bus at high line, below the motor's bus-voltage limit.
- Bus voltage during the fastest programmed move, captured on a scope: minimum droop above the undervoltage trip and above bus divided by Ke for the target speed.
- Bus voltage during that same move's decel: peak below the limit.
- Motor current during accel at or below the peak limit, RMS over a full cycle at or below the continuous rating.
Then run a worst-case duty cycle until temperatures settle and check the transformer, rectifier and motor case against their ratings. If the axis misbehaves electrically after commissioning, the page on a servo axis that jogs with fluctuating current is the next stop; this article's job ends at the supply.
Questions asked
What VA rating does a 60 VDC, 10.2 A servo motor need?
Multiply bus voltage by continuous current: 60 V times 10.2 A gives 612 VA, so about a 600 VA transformer covers one motor at continuous duty. Add margin for rapid moves, or cover the peaks with bus capacitance instead of a larger transformer. An 800 VA toroid per axis is a practical starting point that leaves headroom for the extra RMS current a capacitor-input rectifier draws.
Can I use a 44 VAC secondary on a 60 VDC servo motor?
Not safely. A 44 VAC secondary rectifies to about 62 V minus roughly 1.4 V of bridge drop, which is about 61 V unloaded on a nominal line. That already exceeds the motor's bus limit before line-voltage tolerance and regenerative pump-up. Pick the low end of the 40 to 44 VAC range, or measure the secondary at the highest line voltage your shop actually sees before committing.
How do I cover the peak current between 10.2 A and the 43 A demag limit?
Treat 43 A as a ceiling the drive must never reach: set the amplifier peak limit at or below about 40 A. At the bus voltage that peak is 2400 VA, which is brief, so cover it with bus capacitance or a transformer sized for it, not by hoping the 612 VA continuous rating stretches. Compute capacitance from C equals I times delta-t over delta-V, taking delta-t from your accel time and delta-V from the amplifier's undervoltage trip.