How to Calculate Servo Motor Current From Required Torque
Short answer
Current follows commanded torque: divide required torque by the winding's torque constant, I = T/Kt. The continuous-current rating is a thermal limit, not a fixed draw. For the worked example of 3.02 N·m at 2160 rpm (683 W shaft), check the point on the 48 V torque-speed curve and size the supply from the drive's input-current spec.
On this page
- How do I calculate servo motor current from required torque?
- Which torque constant applies to my motor?
- Does the motor always draw its continuous current rating?
- What does the DC bus voltage change?
- How much shaft power is the operating point?
- How do I size the drive input and its breaker?
- How do I verify the numbers on the machine?
- Questions asked
Servo motor current is commanded torque divided by torque constant: I = T / Kt, with Kt taken from the datasheet of the exact winding you are buying. The motor's continuous-current rating is a thermal limit, not what it draws whenever it runs. Below, the current for a real operating point — 3.02 N·m of required torque at 2160 rpm on a 48 VDC bus, 683 W of shaft power — is calculated, checked against the torque-speed curve, and turned into drive input and breaker sizes.
How do I calculate servo motor current from required torque? #
Divide the torque the axis must deliver by the torque constant of that motor's winding: I = T / Kt. On winding data that lists 0.84 A per N·m, the motor draws 3.02 N·m × 0.84 A/N·m = 2.54 A for that demand.
The 0.84 A per N·m is an illustrative constant, not any specific motor's; replace it with the figure printed for your winding. The full method:
- Assemble the shaft torque: load torque from the 428.5 N thrust through the actuator, friction and drag, and acceleration torque from reflected inertia at the 1.3716 m/s² maximum. The 1.3 safety factor scales loads you have quantified; it does not create the inertia term, which you work out the way you would when calculating servo axis acceleration for torque sizing.
- Take Kt from the datasheet of the exact winding, in the current convention the manufacturer pairs with your drive type.
- Divide each torque by Kt to get the current for that phase of the move.
- Convert speed to rad/s, multiply by torque for shaft power, and locate the point on the torque-speed curve for your bus voltage.
- Compare the cycle's average current with the continuous rating, and acceleration current with the intermittent rating and its permitted duration.
- Size the drive's output stage for the motor current, and its supply and branch protection from the drive's input specifications.
- Verify by recording current through the whole move on the machine.
Which torque constant applies to my motor? #
Use the constant published for the exact winding and its current convention — on a three-phase servo, Kt depends on the convention the drive uses, so take the manufacturer's paired value instead of converting one convention into another.
One frame size usually comes in several windings, and each winding has its own Kt, its own continuous current and its own rated speed. Match the winding to your bus voltage and speed, then read Kt from that winding's row. Some datasheets print the inverse form, A per N·m; with that form you multiply the torque by the figure instead of dividing.
Does the motor always draw its continuous current rating? #
No. That figure is a thermal limit the motor may hold indefinitely; the motor pulls only the current the commanded torque asks for, which sits below the limit in steady work and briefly above it while accelerating.
Intermittent or peak ratings — a good rule of thumb is two to three times continuous — come with a permitted duration in the datasheet, and that duration is part of the rating. When the move ends, current falls to the holding level: a lifted load still needs T/Kt of winding current while stationary.
What does the DC bus voltage change? #
Bus voltage sets the speed the motor can reach before its torque falls away; it does not change the current a given torque needs, because Kt and the continuous-current limit belong to the winding.
Where a selection guide prints one motor against 24, 48, 72 and 96 VDC columns, the rated speed and rated power rise with voltage and the continuous current is the same winding figure in each column. Read the curve drawn for 48 VDC, and confirm the drive accepts a 48 VDC input and can deliver the motor current at 2160 rpm.
How much shaft power is the operating point? #
2160 rpm converts as ω = 2160 rpm × 2π / 60 = 226.2 rad/s, so the shaft power is P = T × ω = the torque from the calculation above × 226.2 rad/s ≈ 683 W — a calculated example for these inputs, and the operating point the 48 V curve must cover.
The current arithmetic means nothing if the motor cannot make torque at speed: if the 48 V torque-speed curve has already folded below the required torque by 2160 rpm, no supply current fixes it. The decision then is the next frame size up, or more reduction to trade speed for torque. Place the point inside the continuous region for a long lift, or inside the intermittent region for a short lift with the published duration respected.
How do I size the drive input and its breaker? #
Take supply and protection sizes from the drive's published maximum input current and inrush, never from motor phase current: at 48 VDC with an assumed 85% combined motor-and-drive efficiency, 683 W at the shaft draws about 16.7 A from the supply.
The arithmetic: I_supply = P / (η × V) = 683 W / (0.85 × 48 V) = 683 / 40.8 = 16.7 A. Replace the 0.85 with the efficiencies from your drive and motor data. For the branch device, the working rule of thumb is the drive's maximum continuous input current times 1.25 — a 20 A drive gives 20 A × 1.25 = 25 A — or the manufacturer's stated inrush figure, because the power-up surge that charges the bus runs two to three times rated input current. The drive manual's installation section governs the final choice. Where motor branch protection ends and drive protection begins is its own question, covered in when a machine motor needs a starter and when drive protection isn't.
With voltage and current settled, the remaining drive requirement is compatibility with the motor's feedback and the controller's command signal — the same check made when finding a servo drive that accepts a 10V analog command.
How do I verify the numbers on the machine? #
Record motor current through the whole cycle — accelerate, steady lift, decelerate, hold — from the drive's tuning software or its current monitor output, then check the peaks against the intermittent rating for their duration and the cycle average against continuous.
A lifted load should settle at a steady holding current; a climbing one points to binding or an unbalanced load rather than a sizing error. One safety note: the 48 V bus holds charge after input power is off, so let the drive discharge per its manual before touching wiring, and read current through the drive's isolated monitor rather than probing the bus directly.
Questions asked
Is inrush current the same as the peak current during acceleration?
No. Inrush is the power-up surge that charges the drive's DC bus, typically two to three times the rated input current as a rule of thumb. Peak torque current is winding current during acceleration, set by torque demand and limited by motor and drive ratings. Size the branch device from the drive's stated input and inrush figures, not from either motor rating.
Does the safety factor on load torque cover acceleration torque?
No. A safety factor scales the loads you have already counted; it does not create torque from accelerating inertia. Sum load, friction and acceleration torque first, then apply any factor once — and if the example torque figure already includes it, do not add it again.
What if my calculated current sits between the continuous and peak ratings?
Only for moves shorter than the duration published with the intermittent rating. Average the current over the complete repeated cycle and keep that value under the continuous rating; if the average lands above continuous, the motor is too small for that duty cycle and you need the next frame or more reduction.
How do I find a torque constant when only performance curves are published?
Read a point off the typical-performance graph: find the current the motor draws at a stated torque, then divide the torque by that current. The quotient is the torque constant for that winding in the graph's own current convention, which is the convention to use in the division.
Does the motor draw current while holding a lifted load still?
Yes. Mechanical output is torque times speed, which is zero at standstill, so input power stays low — but holding torque still requires winding current, and that current heats the windings at I²R for as long as the load hangs on the motor.