What Signals a ±10 VDC Analog Servo Amplifier Expects
Short answer
A ±10 VDC analog servo amplifier expects a bipolar analog command: sign sets direction, magnitude sets how hard the amplifier drives the motor, and the motion controller closes the position loop from encoder feedback. A replacement front end must supply bipolar analog outputs, encoder inputs and enable, fault and limit wiring — never raw step-and-direction pulses.

On this page
A ±10 VDC analog servo amplifier does not count pulses. It expects a bipolar analog command — a steady voltage anywhere between -10 VDC and +10 VDC, sign for direction and magnitude for how hard the amplifier drives the motor — and it expects the position loop to close somewhere else: the motion controller reads the axis encoder and trims that voltage until commanded position and actual position agree. That splits the interface into four jobs for whatever front end you connect: one bipolar analog output per axis, one encoder input per axis, enable and fault wiring, and limit or emergency-stop handling. This article defines each signal, shows why step-and-direction outputs do not fit the input, and gives the verification sequence to run before you command motion on a retrofit.
What the analog command actually is #
The command input is a level, not a train of edges. In the usual configuration the amplifier reads it as a velocity command: full positive voltage means full forward speed, full negative voltage means full reverse, and neutral means standstill. Full means the drive's rated maximum, and the mapping from volts to speed is that amplifier's own specification — take it from its documentation, because this article commits to the interface shape, not to a rating for any drive in particular. Some amplifiers are configured as torque (current) command instead, and the configured mode decides what one volt means at the shaft, so identify the mode before you substitute new hardware.
Sign conventions are not standardized either: some amplifiers invert the input. Never assume the sign; the verification sequence below measures it.
How hard the amplifier corrects each volt of command error is its loop gain, tuned axis by axis at commissioning. Tuned gains vary far more between axes than most engineers expect — the reason tuned KV factor values range from 0.6 to 3.7 why tuned KV factor values range from 0.6 to 3.7.
Where the position loop closes #
The amplifier closes its inner velocity or current loop; the motion controller closes the position loop from encoder counts. That is the defining wiring fact of this architecture: the encoder cable lands on the controller. Break the encoder line and the controller keeps commanding a voltage that nothing trims — the axis drifts to a limit, or sits at an error the controller cannot see.
| Signal | From | To | Role |
|---|---|---|---|
| Bipolar analog command (±10 VDC) | Motion controller | Amplifier | Sign sets direction, magnitude sets output level |
| Analog common | Controller | Amplifier | Reference the command is measured against |
| Encoder feedback | Encoder | Motion controller | Position counts the loop closes on |
| Enable | Controller | Amplifier | Permits amplifier output |
| Fault | Amplifier | Controller | Reports a drive trip so the controller stops commanding |
| Limits and emergency stop | Machine safety circuit | Both | Take the axis to a defined safe state |
Why step and direction does not fit the input #
A step-and-direction interface carries position increments: each step edge is one count, the direction level says which way, and the receiving device is expected to count the pulses and close its own position loop. A ±10 VDC analog command input has no counter behind it. Feed a pulse train into it and the amplifier sees a level bouncing between near zero and the step high, averages that train, and produces a small, directionless command — the axis hums, creeps or ignores you, and it never positions.
The repair is a different device, not different wiring: something that counts the pulses, closes the position loop from encoder feedback, and outputs an analog level. That is exactly the conversion covered in what converts step and direction pulses for an analog servo drive.
What a replacement front end must supply #
Keep the amplifiers, change what feeds them. Per axis, the front end has to provide:
- one bipolar analog output covering the amplifier's rated command span,
- one encoder input whose electrical format matches the installed encoders,
- an enable output and a fault input wired so a trip actually stops commanding,
- limit and emergency-stop inputs handled in hardware, not only in software.
Above the hardware, the control software must command analog axes, not only pulse axes. Software that emits nothing but step and direction is not a front end for these amplifiers, and the hardware decision comes first — that choice is walked through in choosing a motion controller for an analog servo Mach3 retrofit.
The encoder formats you will meet on drives of this class are incremental quadrature on A and B channels, often with an index for homing, in single-ended 5 V logic, differential line-driver levels or open collector. The controller input has to match the electrical form.
Verify the interface before you command motion #
Run these checks with the drives inhibited and the machine locked out under its own energy-control procedure: the enable, fault, limit and emergency-stop circuits you are about to exercise are stop functions covered by IEC 60204-1, the standard for the electrical equipment of machines, and the machine's risk assessment defines how each stop must behave.
- Trace and record. Identify command high, analog common, encoder channels, enable, fault and limit conductors in the existing wiring, and record connector and pin for each. Do not infer assignments from the drive being analog.
- Measure the command. Meter from command high to analog common; if the input is differential, meter across the pair. At neutral expect a reading near 0 V. Jog slowly in each direction and record which sign corresponds to which direction of travel, and whether the magnitude reaches the drive's rated span.
- Confirm the encoder path. Check the installed encoder's electrical format against the replacement controller's input specification before wiring it — the same discipline as verifying a servo drive supports EnDat 2.1 encoder feedback.
- Exercise the auxiliary circuits with output inhibited. Drop enable and confirm the amplifier releases the motor. Force the fault input and confirm the controller sees it. Open each limit and confirm motion stops.
- Command restricted motion. Low speed, minimal load, hand at the stop. Confirm the motor turns the way the command sign says and encoder counts increase with travel. If command polarity and encoder response oppose each other, the loop drives the axis to a limit: kill the command, then correct one sign convention in the controller configuration.
Worked example: command resolution of a replacement output #
This is an illustrative example with assumed inputs; take the real figures from the controller's own specification. Say the replacement controller's analog output is a 12-bit DAC spanning the full bipolar command, -10 V to +10 V.
- Span: 10 V - (-10 V) = 20 V
- Counts: 2^12 = 4096
- Resolution: 20 V / 4096 = 0.00488 V, about 4.9 mV per count
- Fraction of span: 1 / 4096 = 0.024%
If the amplifier maps its full rated output across that span — a mapping stated in its documentation — one count of command is about 0.024% of full output, finer than the mechanics of a router or mill resolve. The practical enemies of an analog retrofit are neutral offset and noise, not bit depth, which is why step 2 above measures the neutral value with a meter instead of trusting a nominal zero.
The decision #
- Amplifiers healthy and the encoder format readable: keep the amplifiers. Any motion controller that gives one bipolar analog output per axis across the amplifier's rated span, accepts the encoders, and handles enable, fault and limits will run them. Match the sign convention you measured, not the one on the drawing.
- Step-and-direction hardware you want to reuse: it cannot wire to these inputs directly. Put a pulse-to-analog conversion stage between the two, or change the drives.
- Undocumented encoder format, or an amplifier that fails under load: replace the amplifier and its feedback together as one decision. No front end translates a format it does not support, and no front end repairs a burned output stage.
Questions asked
What happens if you wire a step-and-direction output straight into an analog command input?
The amplifier sees a level flipping between near zero and the step high thousands of times a second and averages it: at 50 percent duty with a 5 V step high, the axis receives a steady unintended command of about 2.5 V, a quarter of full input, in one direction. It will hum, creep or sit still — it will not position. No wiring trick fixes this; the pulses need a device that counts them and closes the loop.
What should the analog command measure at neutral, and what if it is not zero?
Meter from command high to analog common: a healthy command sits within a few tens of millivolts of zero at neutral, with the acceptable offset being whatever the amplifier documentation states. A small offset drives slow drift with no command at all. Most amplifiers of this class have an offset or null trim, and the controller usually offers a software zero as well — set both before you tune the loop.
Does it matter whether the analog command is velocity mode or torque mode?
Yes. A velocity-mode input scales voltage to motor speed, so the controller's position loop works against a fast inner loop; a torque-mode input scales voltage to motor current, and the controller has to supply the damping instead. Substituting a controller without matching the configured mode means tuning the wrong structure from the first move. Read the amplifier's configured mode out of its documentation before connecting anything new.
When is it worth keeping the original amplifiers instead of replacing them?
Keep them when the encoders speak a format your controller can accept and the amplifiers hold up under load, because the power stage is the expensive half of the axis and the interface is wiring and configuration. Replace amplifier and feedback together when the encoder format is undocumented or an amplifier fails: a new front end cannot translate a format it does not support, and it cannot repair a burned output stage.