Troubleshooting
Why a bias error LED stays on: the 22 V servo bias check
Short answer
A servo bias error LED watches the sum of the positive and negative 12 V bias rails and operates when that sum falls below 22 V. When the LED stays lit after every external bias load is disconnected, the transformer measures healthy and the board fuses have continuity, the fault is on the fault logic board itself, its bias supply or a rail shorted to ground, and that board is the part to repair or replace.

On this page
On an older three-axis servo chassis, one LED on the fault board can hold every axis down, and the bias error indication is easy to chase in the wrong place. That LED watches a single quantity: the sum of the positive and negative bias rails, +12 V and -12 V, and it operates when the sum falls below 22 V. If the LED stays lit after every external bias load is disconnected, transformer healthy and board fuses intact, the fault is on the fault logic board itself: its own bias supply circuitry or a rail shorted to ground. The decision in that case is to repair or replace the board and leave the transformer alone.
What the bias error LED watches #
The owner's manual for the chassis in this example, a 1980s machining center, section 5.5.7, documents the indication, labeled BIE on the fault logic board, with four facts and one instruction:
- The indication operates when the sum of the positive and negative bias supplies falls below the trip threshold.
- Each supply delivers roughly 2 A at peak, and an overloaded supply decreases significantly because of its holdback (current-limiting) capability rather than blowing a fuse.
- The positive supply tracks the negative, so a fault on one rail moves both readings.
- The most common bias error is one of the two supplies shorted to ground.
- The corrective action is to reset and retry the drive after the external bias loads are removed.
Every axis drive board on the chassis draws from that same pair of rails, so a collapsed bias supply takes all the axes down together instead of one at a time, the pattern covered in why a servo amplifier fault appears on all axes at once. That shared supply is also why the manual strips the loads off before it condemns anything: the short can sit on the fault board or on anything the rails feed.
Run the isolation test in this order #
The test is a controlled elimination, cheapest check first. Write each reading down; the decision depends on the whole pattern, not on one measurement.
- Power the chassis down and lock it out before touching anything. The supply capacitors hold charge after the line is off, so confirm the DC rails are discharged at the board before pulling a connector or probing a pin.
- With the power off, check both fuses on the fault logic board for continuity. In the reported case both read continuous, which rules out open fuse elements and nothing more. A drive that instead blows its input fuse at power-up is a different failure path, covered in why a servo drive blows the input fuse at power-up.
- Restore power and measure the small transformer on the servo chassis. The reported case read 117 V across the primary and about 19.6 V across each secondary, values consistent with a healthy front end, as the arithmetic below shows. A secondary near zero would send you to the transformer or its wiring; these readings do not.
- Power down, pull the three axis drive boards, the removable external bias loads on this chassis, plus any further external load the schematic lists. Power up and reset the drive with the machine's run signal to the amplifier off, so a fault that clears on reset cannot restart an axis without warning; servo amplifier instruction manuals make that the first step of every alarm reset.
- Read the LED. Cleared means the fault left the circuit with a load. Still lit means everything proven good so far, transformer, fuses and loads, is out of the circuit, and what remains is the fault board.
Measure both rails and check the arithmetic #
Put the meter's negative lead on supply common, the return the bias circuitry references, confirmed from the schematic or the board's printed labels, and measure each rail to common. Take the two magnitudes and add them; the threshold judges the sum, and tracking means one sick rail can smear both readings, so a single measurement proves nothing.
Calculated example, healthy board: the rails measure +12.1 V and -11.9 V. Sum of magnitudes: 12.1 V + 11.9 V = 24.0 V, comfortably above the 22 V trip level, so the LED stays off.
Calculated example, faulted board: the rails measure +11.9 V and -7.6 V. Sum: 11.9 V + 7.6 V = 19.5 V, below the trip level, so the LED lights. The negative rail is the primary suspect, a short from that rail to ground or a failed supply on that side, and the positive rail reads oddly too because it tracks the negative.
The transformer numbers deserve the same arithmetic, because they are the readings most often mistaken for a clean bill of health. Calculated example for the measured secondaries: 19.6 V AC RMS has a peak of 19.6 x 1.414, about 27.7 V. A bridge rectifier drops roughly 1.4 V (two junctions conducting in series, about 0.7 V each, a rule of thumb), leaving about 26.3 V of raw DC, and the linear regulation typical of a board this age needs only a few volts of headroom to hold a 12 V rail. The transformer can therefore support healthy rails with a wide margin, which is exactly why good transformer readings do not clear the board: rectification, regulation and the loaded output all live downstream, on the board itself.
If no schematic or silkscreen identifies the rail test points, common on a chassis of this age, do not stall on this step. The isolation result already condemns the board; the rail readings are confirmation, not the gate.
What the reported case proved #
Every cheap check passed: the primary at line voltage, both secondaries healthy, both fuses continuous, no visible damage on either board. With all three drive boards out of the circuit, the LED stayed lit. A replacement fault logic board had the servo drives powering up immediately. That outcome condemns the original board outright: with the front end, the fuses and every removable load proven good, the board is what remains, and the board is what you change. Stop spending time on the transformer and its wiring; they were measured, and they passed.
The decision for each pattern #
Run the isolation test, take the two rail readings, and commit to the row that matches.
| Pattern after the isolation test | Where the fault is | Decision |
|---|---|---|
| LED clears once the external bias loads are disconnected | A removed load or its wiring | Reconnect the loads one at a time; the one that relights the LED is the culprit, so repair that board or its harness |
| LED stays lit; one rail reads near zero or far low with every load off | A rail shorted to ground, or the board's own supply circuitry | Power off and measure that rail to common with an ohmmeter, comparing against the other rail; the shorted side reads distinctly lower. Repair or replace the fault logic board |
| LED stays lit; both rails sit at nominal and their sum clears the trip threshold | The threshold-sensing or LED circuit on the board | Confirm the meter is on supply common, then repair or replace the fault logic board; the rails are healthy but the circuit reporting on them is not |
| A transformer secondary reads near zero | The transformer or its wiring | Fix the front end first; the bias test means nothing without AC reaching the board |
Questions asked
Why can a fault on one bias rail pull both rail readings down?
Because the positive supply is designed to track the negative, one shorted load or one failed regulator can produce two bad meter readings, so two low rails do not mean two failed supplies. Disconnect the external loads first, then judge each side on its own: the rail that stays low with nothing connected is the faulty side, and the opposite rail will recover once that side is repaired.
Can I keep resetting the drive and run the machine with the bias error LED lit?
No. The bias rails feed the board's fault and drive-enable logic, so an under-voltaged board cannot be trusted to enable or block the drives correctly. Each reset into a shorted rail also pushes the supply through its holdback cycle again and risks taking a second component with it. The LED is doing its job: locate and clear the rail fault before the machine goes back into service.
Both rails sit low with every load disconnected, isn't that just overload?
No. With the external loads gone, the fault board's own draw is small against the documented peak of roughly 2 A per supply, so a rail near zero is a fault: a short to ground, a failed regulator or a failed rectifier on that board. Holdback is what makes overload look identical from the outside, since an overloaded supply is built to sag rather than blow a fuse, which is exactly why the manual's test strips the loads off before judging the board.
Is the old fault board worth repairing once a replacement has the machine running?
Yes, if you can obtain the schematic for it. Substitution proved the board, not the component: the rectifier, the regulator elements or the holdback and tracking circuitry are all still suspects, and component-level diagnosis starts from the circuit drawing and a powered bench test of each rail under load. A repaired original becomes a tested spare for the chassis, so the next bias fault is a board swap instead of machine downtime.