Why a servo amplifier fault appears on all axes at once
Short answer
When the amplifier fault appears on every axis at the same moment, the cause is something all drives share: the E-stop chain, a motor overload relay, the amplifier feed contactor, the common control supply or the DC bus. Check that shared path in order of cost, and swap drives only after the fault narrows to one axis.

On this page
Three drives alarming in the same second is not three failures. When the amplifier fault appears on every axis at once, the cause sits in something all of them share: the emergency-stop chain, a motor overload relay wired into the enable path, the relay or contactor that feeds the amplifiers, the common control supply, or the shared DC bus. The controller watches one status or enable signal per drive, and that shared signal has dropped out. That changes the order of work. Measure the shared path before touching any drive, because swapping amplifiers between axes cannot tell a good card from a bad one when all of them show the same alarm. The checks below run from cheapest to most involved, with a worked example for the enable chain and a decision for each pattern.
What the alarm actually reads #
The name on the screen is misleading. On most controls the amplifier fault alarm is not a measurement of motor current, torque or bus voltage; the controller input sees one thing per axis, a healthy and enabled status signal from its amplifier, arriving as a wire or as a bus bit. Open the shared enable path, or drop the supply that feeds every amplifier's status circuit, and every axis loses that signal in the same instant, so every axis raises the same alarm at the same time. One tripped overload relay contact in the chain can do it, and so can one loose terminal on the distribution strip that feeds all three drives. The alarm text names the signal that vanished, not the part that made it vanish, which is why the root cause usually sits upstream of the wording on the screen.
Rule out the two causes that need no repair #
Two situations raise a genuine all-axes amplifier fault on a healthy machine, and both take a minute to confirm:
- A pressed emergency stop. The E-stop chain removes the enable or the power from every amplifier at once, which is the chain doing its job. If the alarms appeared when the E-stop went in and clear after you release it and reset the drives, there is no fault to find.
- An unused axis at power-on. A control that expects a configured axis and cannot detect one raises the amplifier fault for that axis at startup; an unused axis finished with a dummy termination plug is the classic case, and the machine's manual says which axis this applies to and that the message can be disregarded there.
An alarm on the axes the machine actually uses, at power-on with the E-stop released or in the middle of a cycle, is not in this category. Treat it as a real common-cause fault and work the list in the next section.
Work the shared path in this order #
One note before the first probe: lock the machine out, and before opening any enclosure verify with a meter that the drive's DC bus has bled down to zero volts, because bus capacitors hold a lethal charge after the power is off. Then check in this order, cheapest first:
- Motor overload relays. Find the overload relays in the control enclosures, most of them marked by a reset button on the body, look for a tripped flag, press each one to reset while the power is off, and check the fuses and circuit breakers in the same pass. One tripped overload contact in the enable chain drops every axis together. Confirming check: the alarms clear after reset. If the same relay trips again, the fault is the motor or branch that relay protects, not the shared chain.
- The enable chain. Measure it with the half-split in the next section instead of assuming it. Confirming check: full supply voltage across one contact, no voltage at the enable input.
- The relay or contactor that feeds the amplifiers. On controls that energize the drives in two steps, main switch first and run command second, amplifiers that show their fault state with only the main switch on are being powered too early. Confirming check: coil voltage present, or contacts closed, at a moment they should be open.
- The common control supply. Measure the supply that feeds every drive's enable and status inputs at the drive end, with everything energized, against the level the machine's manual states. A supply that reads its rated voltage with the drives disabled can sag below the drives' minimum once every coil and input draws at once. Confirming check: the measured level at the farthest drive under load.
- The common DC bus. Where one bus feeds all the amplifiers, a precharge fault or bus undervoltage trips every axis at once. Confirming check: bus voltage against the operating window in the drive manual.
- The connections every drive shares. A terminal strip, backplane or distribution block that all three amplifiers plug into can open one leg and alarm all three. With power off and verified, reseat the shared connectors and look for heat discoloration. Confirming check: the alarm pattern changes or clears after reseating.
Worked example: half-split the enable chain #
The enable chain is a series string of normally closed contacts from the positive terminal of the control supply to the enable input or coil. Illustrative example inputs: a 24 VDC control supply and eight contacts in series, made up of the main E-stop button, two guard switches and five overload relay auxiliary contacts, feeding the drive-enable coil.
With the chain healthy, the coil sees the full supply voltage and each closed contact shows about 0 V across it. With one contact open, no current flows: the open pair carries the full supply voltage and the coil carries 0 V.
- Measure across the coil. A reading of 0 V confirms an open somewhere in the eight contacts.
- Probe the node between contacts 4 and 5 to the negative rail. If it reads 24 VDC, contacts 1 through 4 are closed and the open is among contacts 5 through 8; if it reads effectively zero, the open is among contacts 1 through 4.
- Split the remaining four the same way, then the remaining two. Each reading halves the suspect set, 8 to 4 to 2 to 1, so three measurements put a single contact under the probes, and the contact with the full supply voltage across it is the open one.
Three measurements cover eight contacts and four cover sixteen, which beats probing eight contact pairs end to end. The same halving works on any series string of enable contacts, at whatever supply voltage the machine's manual states.
When a swap helps, and when it wastes a day #
Swapping hardware between axes separates a bad card from a good one only after the alarm is down to one axis. Three rules keep the swap productive:
- Swap amplifier cards or drives, not controller cards, when the suspect is the amplifier. The amplifier and power cards live on the drive chassis; the axis controller cards plug into the controller backplane. Confusing the two costs a day.
- Move the axis-select hardware with the card. Many controller cards carry a jumper or setting that tells the card which axis it drives; swap the card without moving it and the card commands the wrong motor. The reported result of that mistake is an axis running away at power-up plus motor-overheat alarms on both swapped axes, with the original alarm unchanged. A runaway after a swap is a wrong-command problem first, and motor phasing and runaway troubleshooting page walks through how runaway causes get separated.
- Read new alarms as wiring and settings before calling them new failures. Overload or communication alarms that appear right after a swap usually trace to phase order in the motor leads, so check U, V and W phasing first before condemning the card you just moved.
The swap gives a clean decision: if the alarm moves with the card, the card is the fault; if it stays with the axis position, the wiring, backplane or connector for that position is. The same follow-the-fault logic settles whether a servo motor fault follows the drive or the branch when a single-axis fault has both a drive-side and a wiring-side suspect.
One axis, heat-dependent: the thermal signature #
A different pattern means a different part. In one reported case, an X axis dropped out while the machine sat idle, with an audible clunk from the drive section; jogging reset it, it tripped again within minutes, and a rest of five to ten minutes let the drive power up and run briefly once more. Months earlier, the same machine's Z axis had shown the same pattern, and replacing that axis's amplifier card had cured it. That is the signature of a heat-dependent amplifier or connection: heat expands a cracked solder joint or a degrading power device until it opens, and cooling closes it again.
Confirm it by timing. Note the interval from reset to trip over several cycles. An interval that repeats and shortens as the cabinet warms is thermal. A fault that lands at one fixed point in the cycle, always at power-up or always at one command, is logic or settings, not heat. The fix in the thermal case is that amplifier card or its connections, identified from the machine's service documentation and matched by part number before fitting a different suffix. A trip at standstill with the motor doing nothing is a close cousin with its own diagnosis: why an AC servo hums and thermally trips before any jog. The mirror pattern, an overload that appears only on a cold start and clears once the machine is warm, points at a different mechanism again.
The decision for each case #
- The alarm appeared the moment the E-stop was pressed and clears on release and reset: normal operation, no fault.
- The alarm is on all used axes at power-on with the E-stop released: shared path. Overload relays, enable chain, amplifier feed relay, common control supply, common DC bus, shared connections, in that order.
- The alarm is on all axes mid-cycle with no E-stop pressed: the same shared-path order, with the amplifier feed relay and the control supply moved up, because a drop-out under load is usually a sagging supply or a contact opening.
- The alarm is on one axis only and there from power-on: follow-the-fault swap of that amplifier. Alarm moves with the card, replace the card. Alarm stays with the position, repair the wiring, backplane or connector for that axis.
- The alarm is on one axis after minutes of running and a rest brings it back: heat-dependent amplifier or connection. Confirm with the timing test, then repair or replace that amplifier.
- New alarms appear right after a swap: phase order and axis-select settings first, parts last.
Run the shared path before the swap test whenever more than one axis alarms at the same instant. That single rule separates the half-hour relay reset from a day of pointless card swaps.
Questions asked
The screens are on and the rest of the machine runs, so why is every servo axis faulted?
Because the enable chain feeds only the drives. Its contacts sit in the small control circuit that tells each amplifier it may run, not in the circuits that power the screen, the coolant or the hydraulics, so the rest of the machine can look perfectly alive while every axis reports its amplifier as unhealthy. That split is the clue that the fault is in the shared enable path rather than in any drive.
After every power-down I have to press a reset on each amplifier before it will run. Is that normal?
No, treat it as a symptom. An amplifier that needs a manual reset every cycle is latching an internal fault at power-up, most often because it is being energized before the run command that should enable it, or because the enable chain arrives in the wrong order. Resetting by hand gets the shift running but hides the cause, so trace the relay and contact timing that powers the amplifiers at startup.
What should I write down before calling for service?
The exact alarm text and any number shown on the screen, which axes showed it, whether it appeared at power-on or mid-cycle, how long the machine ran before tripping, whether a rest brought the drive back, and any card, relay or drive that was swapped between axes. That short list lets the service department aim at the shared path or at one amplifier before anyone opens the cabinet.
The relay feeding the amplifiers was already replaced and the alarms came back. Now what?
Treat the replaced relay as a partial fix and move one step back in the chain. A relay that was never the problem, or that keeps failing, points at what controls it: the coil feed, the contact that commands it, or a wire that bypasses it and energizes the amplifiers early. Measure the coil voltage at the moments the machine should be idle, and compare the wiring against the machine's schematic rather than against the part that was removed.