Why an AC servo hums and thermally trips before any jog

Servo and stepper motion Published 8 min read By AutomateDirectUSA engineering team

Short answer

Hum before any jog is the enabled axis holding position, and a thermal trip at standstill means it is doing that badly. Measure the current the axis draws while holding: above the motor's continuous rating the heating is real (brake drag, bind or loop oscillation), below it the drive's thermal model or motor data is wrong. Fix the mechanics, then run the drive's documented autotune.

On this page
  1. What the hum before a jog tells you
  2. The checks, cheapest first
  3. Where the current reading sends you
  4. Working a standstill trip: 6.2 A held on a 4.5 A motor
  5. Why an autotune fixes the hum once the mechanics pass
  6. Running the repair in order
  7. The decision for each case
  8. Questions asked

An AC servo that hums the moment the drive is enabled, before any jog, is not idling: an enabled positioning axis corrects its position error continuously, so the hum is the axis working at standstill. Hum on its own can be a healthy hold. A thermal trip at standstill is never normal, and one measurement splits it into two cases: the current the axis draws while holding. Above the motor's continuous current rating, the heating is real, and the torque demand comes from a dragging brake, a bound transmission, gravity or a position loop oscillating in place. Below the rating, the copper is not the problem and the drive's thermal model or entered motor data is. Run the checks below in order on any axis of this kind, a chipping-head positioner included.

What the hum before a jog tells you #

The position loop compares commanded and actual position continuously and requests corrective torque, so a shaft that stands still can still be working electrically. That is why the sound is there before the first move command: the axis is already closed-loop and already holding. A small, steady holding torque can be audible and harmless. The trip is what turns the sound into a fault, and the trip's source matters: a motor temperature input, the drive's internal thermal estimate and a power-stage temperature are three different limits with three different fixes, so the fault text is the first thing to record, not the first thing to clear.

The checks, cheapest first #

Each item names what it rules out and the check that confirms it. Stop at the first failure and fix it before tuning anything.

  1. Read the fault before resetting it. Note which indication tripped and whether the machine was cold or already running. An axis that trips the instant power is applied was never hot, so a cold trip points at the thermal estimate, the temperature circuit or the entered data, not at real heat; the opposite pattern, a trip only on cold starts, has its own diagnosis in why a servo axis trips motor overload only on cold start.
  2. Confirm what the motor actually is. A true AC servo and a plain AC motor with an encoder are identified and tuned by different routines. Match the motor nameplate to the motor type configured in the drive; a wrong entry corrupts the current limits and the thermal model together.
  3. Measure the holding current. With the drive enabled, the brake released and no command given, read the current on the drive's monitor, checking its documentation for whether the figure is rms or peak. Compare it with the continuous rating on the datasheet of the exact motor and with the limits configured in the drive. This number decides the branch.
  4. Check the brake releases. A holding brake that stays engaged makes the servo fight its own brake: hum, high current and a thermal trip, all before any motion. Measure the brake supply and confirm the release click and air gap against the brake's documentation; the release behavior is covered in what a servo holding brake does and does not do.
  5. Check for mechanical bind. A kinked chain, a seized gearbox, packed sawdust or a failed bearing loads the axis at standstill. Isolate the hazardous energy and secure the head against gravity before opening the transmission. A shaft that turns under the longest wrench in the plant proves little: leverage is not a torque measurement; the holding-current reading is.
  6. Check the feedback path. Inspect the coupling between motor shaft and encoder for slip or cracks, and where position feedback sits on the machine itself, check its drive coupling and scale. With the drive disabled, bar the axis through its travel and confirm the displayed actual position tracks the movement.
  7. Check the entered motor data. Current rating, resistance and feedback type in the drive against the nameplate and documentation.

Where the current reading sends you #

Above the continuous rating, the heat is real. Copper loss rises with the square of the current, so an axis drawing more than its rating while standing still is heading for the trip whatever the tune quality. The demand comes from a brake that drags, a transmission that binds, gravity on a vertical axis, or a loop oscillating hard enough to look like load. Sustained heating of this kind is the failure covered in why a servo motor overheats at standstill on a rack axis; on a vertical axis the holding work itself can be the load, the case in why a vertical axis servo motor overheats from counterbalance loss.

Below the rating, the copper is cleared. A standstill current under the continuous rating cannot heat the windings past their limit, so the thermal picture is the fault: a wrong thermal model or motor data, a temperature input reading wrong, or an estimate carried over hot from the previous run. Correct the data and re-commission; do not chase heat that is not there.

Rule of thumb: on a horizontal axis with the brake released and nothing but friction to hold, the standstill reading should be a small fraction of the rating. Treat a steady value above about a quarter of the continuous rating as drag or oscillation until the mechanism proves otherwise.

Working a standstill trip: 6.2 A held on a 4.5 A motor #

The machine that prompted this gives no numbers, so the inputs below are example values for a 750 W-class AC servo axis; repeat the arithmetic with your own readings. The results are calculated, not measured.

Inputs:

  • Holding current at standstill, read on the drive's current monitor with the axis enabled and the brake released: 6.2 A rms (example reading).
  • Continuous current rating of the motor: 4.5 A rms (from the datasheet of the exact motor; example value).
  • Per-phase winding resistance: 0.60 Ω at 25 °C (from the same datasheet; example value).
  • Resistance rise of copper with temperature: about 0.004 per °C (a property of copper).

The rule, in words: the copper loss of a three-phase servo is three times the square of the rms phase current times the per-phase resistance, with the resistance taken at winding temperature.

Arithmetic:

  • Loss at the standstill reading: 3 × (6.2 A)² × 0.60 Ω = 3 × 38.44 A² × 0.60 Ω ≈ 69 W.
  • Loss at continuous rating: 3 × (4.5 A)² × 0.60 Ω = 3 × 20.25 A² × 0.60 Ω ≈ 36 W.
  • Ratio: (6.2 ÷ 4.5)² ≈ 1.9, so the standstill loss is nearly double the rated loss, with zero mechanical output.
  • Hot winding, example at 100 °C: resistance = 0.60 Ω × (1 + 0.004 × 75) = 0.78 Ω, and 3 × 38.44 A² × 0.78 Ω ≈ 90 W.

Result: roughly 69 W into the windings while standing still, rising toward 90 W as the copper heats, against 36 W at rated current, enough to trip a correctly configured drive within minutes.

Decision: the standstill reading is above the continuous rating, so the trip is genuine heating. Do not reset and retry, and do not raise the following-error threshold to mask it; find the torque demand (brake, bind, gravity) or the oscillation, fix it, then autotune. Had the reading come in below the rating, this same arithmetic would have cleared the copper and sent the job to the thermal model and motor data instead.

Why an autotune fixes the hum once the mechanics pass #

When the brake releases, the transmission is free, the data is right and the axis still hums with the current swinging around the holding demand, the position loop is oscillating. Gains set for mechanics that no longer exist (a replaced gearbox, chain or coupling changes the inertia, compliance and backlash the loop sees) leave the controller correcting in alternating directions, and that electrical thrash heats the windings like real work even though the shaft barely moves. An oscillating axis typically announces itself as a buzz at one fixed frequency with a ripple visible on the current or velocity trace.

The drive's autotune, run exactly as its commissioning instructions describe, re-identifies the motor together with the mechanism it now drives and sets the response to match. Read the routine before enabling: some need free travel through a defined range, others identify with almost no shaft motion, and each states its clearance conditions. Investigate an aborted routine rather than restarting it. Tuning is no substitute for repair; an autotune against a dragging brake or bound gearbox will settle the loop while the trip stays. And on an axis whose position feedback sits on the machine, never uncouple the motor and enable it in position control: the shaft can spin while the measured machine position stands still, and the loop answers by demanding more motion. Uncoupled testing runs only in a manufacturer-approved test mode with the shaft secured.

Running the repair in order #

  1. Save the drive configuration and record the fault text, holding current, position error and thermal diagnostic as the baseline.
  2. Correct the motor and feedback data against the nameplates and documentation.
  3. Free the mechanism: repair the brake release, clear contamination, and restore the feedback; a coupling that has cracked or slipped between motor and encoder is replaced with a new flexible shaft coupling, not re-tightened.
  4. Run the drive's documented autotune with the travel and clearance its routine requires, and check the completion status.
  5. Apply and save the resulting settings.
  6. Re-enable without jogging and compare the hum, holding current and thermal diagnostic with the baseline; only then jog.

The decision for each case #

  • Current above rating, brake not releasing: repair the brake release circuit. The tune is fine; confirm the standstill reading falls before moving on.
  • Current above rating, mechanism free, horizontal axis: loop oscillation, so autotune, then re-check the reading.
  • Current above rating, vertical axis: the holding work is the load; restore the counterbalance, or the motor was undersized for holding from the start.
  • Current below rating, trip from cold: thermal model, motor data or temperature circuit; correct the data, re-commission, and the trip stops without touching the mechanism.
  • Feedback coupling slipped: re-couple, verify the actual position against mechanical travel, then autotune.

In every branch the holding-current reading is the hinge: measure it first and the rest of the diagnosis follows.

Questions asked

Can an enabled servo hum at standstill with nothing wrong?

Yes. An enabled axis corrects position error continuously, so a faint hold hum is normal, and the drive's own power-stage switching often adds a steady whine that shifts with load. What is never normal is a thermal trip, or a standstill current above the motor's continuous rating. Judge the axis by the current monitor and the temperature diagnostic; the sound alone tells you almost nothing.

Should I swap the motor for a known-good one first?

No. The same standstill trip comes from a dragging brake, a bound gearbox, a slipped feedback coupling, stale tuning or wrong motor data in the drive, so a swap proves nothing until the holding current has been read. A motor with shorted turns, by contrast, shows unbalanced winding resistance between phases, a check any motor shop makes in minutes. Measure first and condemn the motor last.

How long may an axis hold at its continuous current rating?

By definition, indefinitely. The continuous rating is the current the motor can carry without exceeding its temperature class in the rated ambient, for as long as the axis stands there. That is why the branch test compares the standstill reading with the rating rather than with the sound or the trip history: below it the holding is sustainable, above it the trip is only a matter of time.

Does a vertical axis change this diagnosis?

Yes. Gravity turns holding into real, continuous work, so a vertical axis draws standstill current by design and its counterbalance belongs in the sizing. Compare the reading across the travel with the balance active: current that climbs toward one end of the stroke points to a leaking or misadjusted counterbalance, while current high everywhere means the motor was chosen too small for holding duty.

Keep reading

  • Troubleshooting

    Why a Servo Shows a High Torque Alarm at Standstill

    A high torque alarm at standstill means the enabled axis is drawing real current against a position error, a holding brake, or an external load, and copper loss rises with the square of that current. Check the drive's actual RMS current against the motor's documented continuous standstill rating, then work the causes cheapest first: connectors and feedback, brake sequencing, loop stability and commutation, then cable interference.

    Servo and stepper motion

  • Comparison

    Brushless AC Servo Position Control and Holding Torque for a Lathe

    A brushless AC servo matches brushed DC accuracy on a lathe axis when the drive commutates sinusoidally, runs in torque mode with a motor-mounted encoder, and sits behind a reduction. It holds by active current through the position loop within the continuous stall rating, and a brake covers power-off hold.

    Servo and stepper motion

  • Troubleshooting

    Diagnosing a Servo Axis That Jogs in Steps With Fluctuating Current

    Stepping motion with a 1-2 A current swing and clean encoder feedback means torque demand is changing along the travel: check brake drag, coupling condition, gibs and screw alignment under load before substituting drives or motors. Record current and encoder error together, work the cheap checks in order, and let the uncoupled motor test separate mechanics from motor.

    Servo and stepper motion