Troubleshooting
Why a servo motor overheats at standstill on a rack axis
Short answer
A servo that stays enabled after a stop keeps its position loop closed, so rack binding, an over-compressed engagement spring, an unbalanced load or slack-driven hunting keeps torque current flowing at zero speed until the winding fails. Measure the standstill current, uncouple the pinion to split mechanical from electrical causes, then set the drive's continuous limit to the motor's rated current and repair whatever kept the current high.

On this page
A servo that overheats at standstill on a rack axis is holding torque it should not need. Enabled means the position loop stays closed after the stop command, so binding, an over-compressed engagement spring, an unbalanced load or slack between motor and rack keeps torque current flowing at zero shaft speed — and because a drive maintains standstill torque indefinitely, nothing times out before the winding does. The order of work is fixed: measure the current after a stop, uncouple the pinion from the rack to split mechanical from electrical causes, then verify the drive's continuous and peak current limits against the motor's rating. Tuning comes last, because it cannot fix a bound rack.
Why standstill is where a servo burns #
At zero speed the shaft delivers no mechanical power, so every watt the winding generates stays in the winding as heat. Holding torque still needs current, and a drive will maintain standstill torque indefinitely — no timeout is waiting to save the motor. IEC 60034-1 calls continuous duty S1: a constant load held long enough for the motor to reach thermal equilibrium. The rated continuous current is the current the motor can carry in that state; it gets hot, then stops climbing. A winding that keeps getting hotter hour after hour is above its rating, whatever the display says. Copper makes that worse as it goes: winding resistance rises about 0.4 % per °C, so a hot winding produces more heat at the same current.
Two triage checks belong here. First confirm the motor type: a stepper holds full current at standstill by design and is supposed to run hot, so a stepper-driven axis belongs in why a stepper motor runs hot instead. Second, a drive that reacts quickly raises a torque alarm rather than a burnt winding; if yours does, why a servo shows a high torque alarm at standstill is the closer article. This one covers the quiet case — heat accumulating with no shutdown.
Causes in order of cost to check #
The symptom set: the axis moves normally, then holds at or near rated current after the stop command, heats over hours or days, and sometimes hums or buzzes while stationary. The symptom alone does not pick the cause; each candidate below carries its confirming check, cheapest first.
- Slack or compliance between motor and rack. Confirm by listening: a hum, buzz or high-pitched whine at standstill that stops when the axis is disabled, plus ripple on the current-monitor trace.
- Gain set too high. Confirm with a small reduction: the noise stops while mean current barely moves; if the noise returns under load, compliance is driving it, not gain.
- Offset or a never-reached in-position band. Confirm at the drive: the in-position flag never sets while stopped, and a free axis creeps when disabled.
- Over-compressed engagement spring or excess preload. Confirm by relaxing the spring toward the builder's setting — where none is written down, aim for smooth hand-travel with no perceptible backlash at the pinion — then re-measuring the standstill current.
- Rack binding or misalignment. Confirm by position: standstill current varies along travel, with a local peak at the tight spot.
- Unbalanced load. Confirm by carriage position or height: current that tracks it points at gravity, and counterbalance loss on a vertical axis is its own failure mode.
- Wrong motor data or limits in the drive. Confirm by reading the continuous and peak limit settings against the motor datasheet; anything above the rating is a protection gap.
The uncoupled standstill test #
This is the split that decides where to spend your time.
- Write down the motor's datasheet rating and the drive's limit settings before changing anything.
- Command a normal stop with the carriage mid-travel and read the standstill current from the operator display, the drive's current-monitor output or an ammeter on a phase lead. Note whether it settles or holds, then repeat at both ends of the rack.
- Listen while it holds. Noise means hunting; silence proves nothing — measure.
- Isolate the drive power under the machine's lockout procedure and support anything that can fall, because an enabled servo can move without a command; then inspect spring compression, rack alignment, backlash and coupling stiffness through the full travel.
- Disengage the pinion from the rack and repeat the standstill measurement.
- Read the result. Current that drops with the pinion disengaged makes it a mechanical case: relax the preload, realign the rack, counterbalance the load. Current that stays high with no load makes it an electrical or tuning case — offset, gain, wiring, or a motor and drive that do not match — and a brushless servo overheating with no load points at commutation first.
- If the drive trips an overheat alarm while the motor case is still cool, test the thermal switch before chasing current.
Why gain alone cannot fix hunting #
Slack between motor and load leaves the position loop tuned for a load it no longer feels, so the axis corrects endlessly at standstill and never rests. Lowering the gain moves the instability out of earshot but buys sluggish motion and leaves the play in place, so the noise returns under load. The remedy is mechanical: remove the backlash, keep any belt stage short and wide, do not re-use worn belts and pulleys, and avoid softer couplings than the joint needs. When the compliance is a worn or too-soft coupling between motor and pinion shaft, replace it with a flexible shaft coupling matched to the joint rather than re-using the old part.
The limit settings that let a motor burn #
A professional drive carries two current settings — a continuous RMS limit and a peak limit — and usually motor temperature monitoring as well. Set the continuous limit to the motor's rated continuous current and the peak limit to the motor's peak rating, used only for the short time the datasheet allows. Correct settings protect the motor; these motors burned anyway, so either the limits sit above the rating or the heating hides from the protection, as a filtered current reading that averages out hunting ripple does. A warning without a shutdown is not protection. Fix the gap before the machine runs unattended again, and wire the drive's motor-temperature input if it has one: a sensor in the winding acts on real temperature, not on an estimate. The opposite pattern — a servo axis that trips its motor overload only on cold start — has different causes again.
Standstill loss of a 6 A servo hunting with 4 A of ripple #
Inputs, each an example value standing in for the real one:
- Motor rated continuous current: 6.0 A — from the motor datasheet or nameplate.
- Winding resistance, line to line: 0.8 Ω — the datasheet's room-temperature figure.
- Standstill current on the drive display: 6.0 A, steady — the failure signature of a stopped motor holding its nominal current.
- Hunting ripple: 4.0 A RMS — read with a current probe or the drive's torque-monitor trace.
- Drive continuous RMS limit as found: 9.0 A — a raised setting, sitting above the motor's rating.
The rule in words: at standstill all winding loss is heat; the loss rises with the square of the total RMS current; a steady holding current and a hunting ripple add in quadrature; and for a three-phase servo the loss is about 1.5 × (RMS current)² × (line-to-line resistance).
The arithmetic:
- Total RMS current = √(6.0² + 4.0²) = √(36 + 16) = √52 = 7.2 A.
- Standstill loss = 1.5 × 7.2² × 0.8 Ω = 1.5 × 52 × 0.8 = 62.4 W, with zero power leaving the shaft.
- Loss at the rated point = 1.5 × 6.0² × 0.8 Ω = 1.5 × 36 × 0.8 = 43.2 W — the heat the motor sheds continuously.
- Excess = 62.4 ÷ 43.2 = 1.44, so the winding makes 44 % more heat than its continuous capability, for as long as the axis dwells.
That is a calculated example for these inputs, not a measurement, and it explains the failure: the total RMS sits under the raised limit, so nothing trips while the winding temperature climbs past its insulation class over hours or days. Decision: reset the continuous limit to the motor's rated value as the backstop, then treat this as the mechanical case it is — remove the slack, recheck the gain and re-measure. With the ripple down to 1.0 A the total is √(36 + 1) = 6.1 A and the loss 1.5 × 37 × 0.8 = 44.4 W, back at the rated point where temperature levels off. The pass condition is twofold: hunting noise gone, and case temperature flat after an energized dwell of about an hour — a rule of thumb, since motors of this size reach thermal equilibrium on that timescale. Still rising at the end of the hour means the standstill loss is still above what the motor sheds.
Acceptance before unattended running #
Verify the repair in the state that failed: representative moves, a stop, then a long energized dwell, watching current, sound and case temperature. Repeat at several points along the rack, because preload and alignment vary with position and a repair that passes at one end can fail at the other. The axis passes when it settles into its in-position band without noise, the current warning stays out, position holds through the full dwell, and the temperature stops climbing. Record the corrected limit settings with the machine documentation so the next drive swap does not resurrect the gap. Moving well was never the problem; the damage accumulated while stopped.
Questions asked
What standstill current is acceptable on a rack axis?
On a horizontal axis with no external pull, a healthy drive settles well below the motor's rating — a working rule of thumb is a third of rated current or less, which covers friction and preload only. A reading at or near rated means binding, a compressed spring, offset or hunting. Judge a vertical axis against its counterbalance instead: gravity is a real holding load there, and its standstill current is legitimate.
How do I measure standstill current without a drive display?
Use the amplifier's current-monitor output into a meter or scope, or clamp a true-RMS meter around one motor phase lead. A scope is worth the extra minute: a meter averages, and a hunting axis hides its ripple behind a plausible average, while the trace shows the oscillation that actually makes the heat. Take readings at several carriage positions, not just one.
Does a correctly set current limit make the fault safe to ignore?
No. A continuous limit at the motor's rating keeps the winding inside its thermal capability, but it protects by holding torque back, so a binding or hunting axis holds weaker and its following error grows while the mechanics keep wearing. Treat the limit as the backstop that prevents the next burnt motor, not as the repair; the mechanical or tuning cause still has to go.
Can I disable the axis between moves instead?
Only where the load cannot run away. Disabling drops holding torque to zero, so a horizontal axis, or a vertical one with a counterweight or brake, can rest between moves; an uncountered vertical axis will drop. Leaving a healthy axis enabled is normal because its standstill current is small, so disable-on-idle is a stopgap for an unfixed fault, not the fix.